HomeMy WebLinkAboutOWTS Design Report 10.03.2013SER!ICE
October 3, 2013
PO Box 2844
Glenwood Springs, CO 81602
Ph 970 -618 -5033
Fax 303.216.2796
Dale Titus
Drtitus0171 Agmail.com
Subsurface Investigation and Onsite Wastewater Treatment System Design
4- Bedroom Residence
171 Fairway Lane
Garfield County, Colorado
Dale,
Project No. C1058
ALL SERVICE septic, LLC performed a subsurface investigation and an onsite wastewater treatment
system (OWTS) design for the subject residence. The property is located outside of Glenwood
Springs, in an area where OWTSs are necessary.
SITE CONDITIONS
A 4- bedroom, single - family residence presently exists and is utilizing an existing OWTS. The house
is undergoing a remodel which will not result in an increased bedroom count; however, the existing
OWTS components will need to be relocated. A ditch runs along the west portion of the property.
There must be a minimum 50 -foot setback from the ditch the absorption area. The tank must be
located -at -least 5-feet-from-the-residence and the- drywell -a-ir inimur -of 25-feet-from-the-residence,
SUBSURFACE
The subsurface-was-investigated-by-digging-one—I-6-foot-profile pit and - three percolation-holes, as
indicated. The materials encountered in the profile pit consisted of 7.0 -foot of dark brown, moist,
clayey sand, underlain by light brown gravelly sand with 2 -inch to 6 -inch diameter cobbles to a depth of
13 -feet, underlain by light brown gravelly sand with 6 -inch tol -foot diameter cobbles to a maximum
depth explored of 16 -feet. No groundwater or bedrock was encountered. An average of 31 MPI
percolation rate will be used to design the OWTS, as described in Table 1.
P1 5 -feet
P2 8-feet
P3 5 -feet
Profile pit (16' with benches)
Backfill (upper 7 -feet
Backfiill (below 7 -feet
Page 2
DESIGN SPECIFICATIONS
The OWTS design is based on 4- bedrooms. An average daily wastewater flow of 900 GPD will be
used. The installation must include a 1250- gallon, two - compartment septic tank with an effluent filter
—on-th outlet -e Effluent will ravity- flowtto .ai °_xi 6 i2' deep drywell. De-pth of the dryw. 1l
must be measured below the inlet pipe.
The drywell will consist of clean, graded rock ranging from 1/2" to 2 1/2" in diameter. The rock will
extend from the bottom of the well to at least 2" above the inlet pipe. The sidewalls of the drywell
will be scarified. A covering of geotextile fabric will be placed over the aggregate before the drywell
is covered with soil. The backfill material shall be graded to deflect precipitation and surface
drainage.
The component manufacturers are typical of applications used by contractors and engineers in this
area. Alternatives may be considered or recommended by contacting our office. Construction must
be according to Garfield County Sewage Disposal Regulations, the Individual Sewage Disposal (ISDS)
Permit provided by Garfield County Building Department, and this design.
REVEGETATION REQUIREMENTS
An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the
entire disturbed are of the OWTS installation. A mixture of native grass seed that has good soil
Page 3
stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes
well with successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be
plated over the area. Until vegetation is reestablished, erosion and sediment control measures shall be
implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining
proper vegetation cover.
OPERATION INFORMATION AND MAINTENANCE
The property owner shall be responsible for the operation and maintenance of each OWTS servicing the
property. The property owner is responsible for maintaining service contracts for manufactured units,
alternating absorption systems, and any other components needing maintenance.
Geo- fabrics or plastics should not be used over the absorption area. No heavy equipment, machinery, or
materials should be placed on backfilled absorption area. Livestock should not graze on the absorption
area. Plumbing fixtures should be checked to ensure that no additional water is being discharged to
OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day
and harm an absorption area.
The homeowner should pump the septic tank every two years, or as needed gauged by measurement of
solids in the tank. Garbage disposal use should be minimized, and non - biodegradable materials should
not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water
softener should not be discharged into the OWTS. No hazardous wastes should be directed into the
OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for
domestic waste only.
ADDITIONAL CONSTRUCTION NOTES
If design includes a pump, air release valves and weep holes should be installed to allow pump lines
to drain to minimize risk of freezing. Excavation equipment must not drive in excavation of the
absorption area due to the potential to compact soil. Extensions should be placed on all septic tank
components to allow access to them from existing grade.
INSTALLATION OBSERVATIONS
ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation
should be performed before backfill, after placement of OWTS components. Septic tanks, distribution
devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL
SERVICE septic, LLC should be notified 48 hours in advance to observe the installation.
LIMITS:
The design is based on information submitted. If soil conditions encountered are different from
conditions described in report, ALL SERVICE septic, LLC should be notified. All OWTS
construction must be according to the county regulations. Requirements not specified in this report
must follow applicable county regulations. The installer should have documented and demonstrated
knowledge of the requirements and regulations of the county in which they are working.
Please call with questions.
Sincerely,
ALL SERVICE septic, LLC
x C Y o iL^I
Carla Ostberg, MPH, REHS
Page 4
awb :,... �/CF
Reviewed By: : `` IiER9fi:v 1
f . �:
o
.. ,:
38882 r
Richard H. Petz, i3: " • .:-.4k::
�11..,Ar ECG
GARFIELD COUNTY
Percolation Test and Soils Data Form - TABLE 1 - PROJECT
C1058
Performed by All Service Septic, LLC
PROFILE PIT 16 -feet
Date of Test: 9/30/13
0 to T Sand, clayey, dense, moist, dark brown
7' to13' Sand, gravelly, light brown, cobbles 2" to 6" in diameter
13' to 16' Sand, gravelly, light brown, cobbles 6" to 1' in diameter
Hole No. Hole Depth Interval Measurement at Measurement at Change (in.) Percolation Rate
(in.) (min.) Start of interval End of Interval (min./in.) MPI
(in.) (in.)
1 60" 10 7.50 7.75
0.25
10 7.75 8.00
0.25
10 8.00 8.125
0.125
0.125
10 8.125 8.25
10 8.25 8.50
0.25
0.25
40
10 8.50 8.75
10 8.75 9.0
0.25
2 60" 10 6.25 6.50
0.25
10 6.50 6.75
0.25
10 6.75 7.25
0.50
10 7.25 7.50
0.25
10 7.50 7.75
0.25
10 7.75 8.00
10 8.00 825
0.25
025- 40-
- - - --
3 96" 10 5,50 6.50 1,00
-- -
1.00
0.75
10 6.50 7.50
add water 10 7.00 7.75
add water 10 5.25 6.00
10 6.00 6.75
0.75
0.75
10 6.75 7.50 0.75
13
AVERAGE = 31 MPI
LOT 29
2
ti 50' MIN.
0
16' x 16' x 12' DRYWELL
WITH 4' CONCRETE
PERFORATED RISERS
4" DIA SDR 35 SEWER
LINE (SLOPE 2
1% MIN TO DRYWELL)
1250- GALLON,
TWO - COMPARTMENT,
CONCRETE SEPTIC TANK
WITH EFFLUENT FILTER
4" DIA SDR 35 SEWER
LINE WITH CLEANOUT
(SLOPE 2% MIN TO TANK)
N
0' 15' 30'
Scale: 1" = 30' =0"
00
PROPOSED
ADDITION
LOT 30
1.131 ACRES
4- BEDROOM
RESIDENCE
1 - -- - - ---
THE LOCATION OF EXISTING AND PROPOSED IMPROVEMENTS SHOWN ARE
NOT THE RESULT OF A PROPERTY SURVEY. THE LOCATIONS ARE
APPROXIMATE. IT IS THE HOMEOWNERS DUTY TO ENSURE ALL
CONSTRUCTION AND IMPROVEMENTS LOCATIONS ARE ACCURATE. ALL
SETBACK DISTANCES SHOULD BE CONFIRMED PRIOR TO EXCAVATION.
OWTS
SITE PLAN AND PROPOSED O
= 7
('
rho
Date: 10/03/13
Designed By: CBO
Checked By: RHP
Drawn By: ANG
P.O. Box 2844
Glenwood Springs, Colorado 81602
Phone 970.618.5033
Fax 303.216.2796
Titus Residence
171 Fairway Lane
Garfield County, Colorado
Project Number: C1058
W1.0
Sheet 1 of 3
PLAN VIEW
SWALE OR BERM
TO DIVERT
SURFACE
RUNOFF
DRYWELL DRAIN FIELD SPECIFICATIONS
4" PVC INLET LINE I
FROM SEPTIC
TANK
MANHOLE
COVER
CROSS SECTION
NATURAL
GRADE
INLET FROM
SEPTIC TANK
EXTENT OF
EXCAVATION
SLOPE FOR DRAINAGE
16'
DISPERSAL
GRAVEL SHOULD
16' BE 1/2" TO 2 1/2"
12'
a
4 -
SIDES OF
EXCAVATION
OBSERVATION
PIPE
WITH PVC CAP
CONCRETE LID
WITH MANHOLE
COVER
PLACE AN 8 -INCH BED OF GRAVEL -
PRIOR TO PLACING CONCRETE RINGS
FOR STABILITY
16'
DRYWELL DETAILS
NCI -O SCA F
P.O. Box 2844
Glenwood Springs, Colorado 81602
Phone 970.618.5033
Fax 303.216.2796
Titus Residence
171 Fairway Lane
Garfield County, Colorado
Project Number: 01058
GEO- FABRIC
DISPERSAL
GRAVEL
BERM OR
SWALE
SLOTTED PVC OBS. PIPE
TO EXTEND TO BOTTOM
OF DRYWELL
4 FOOT DIAMETER
CONCRETE
PERFORATED RINGS
Date: 10/03/13
Designed By: CBO
Checked By: RHP
Drawn By: ANG
W2.0
ShAnt 2 of 3
DESIGN
4- BEDROOM RESIDENCE
(75 GAL /PERSON /DAY x 2 PERSONS /BEDROOM x 4 BEDROOMS)
AVERAGE DAILY FLOW = 600 GALLONS
DESIGN FLOW = Q = 1.5 x 600 = 900 GALLONS
TANK:
900 x 30 HOUR RETENTION TIME = 1125 GALLONS
USE 1250 - GALLON, TWO- COMPARTMENT TANK
ABSORPTION AREA:
PERC RATE = 31 MPI
CALCULATED ABSORPTION AREA = QI5 X SQRT 31 = 1002 SF
16 FT LONG X 16 FT WIDE X 12 FT DEEP BELOW INLET = 1024 SF
FINISHED
GRADE
SEWER LINE -
4" SCHEDULE
40 P.V.C.
SLIP -ON PVC CAP
DO NOT GLUE
EFFLUENT LINE - 4"
SCHEDULE 40 OR 4" SDR
35 P.V.C.
INSULATED COPPER TRACER
WIRE MAY BE INSTALLED TO
LOCATE LINE IN FUTURE
CLEANOUT DETAIL
Septic Tank with the Addition of an Effluent Filter -1250 Gallon, 2 -Comp.
Concre.o Rises
S cpe Grou'rc
Awcy Frorn disc's
Tap of tee to come tc
1" from top a{ tank lid
Inlet Tee \�
ORENCO BRAND NAME
NOT ENFORCED
2"
v
Liq.lc _eve'
TANK DETAIL
NCI TO SCALE
ter Cartridge Handle
(acid cut to dcsircd height)
Tan( Adapter 'cost or batted)
Ven: O'itice
Gent Discharge
Moc. Io: ng Dischorge Orifices
Va.; t inlet Forts
-; ter Cartridge
1" uent Filter
Date: 10/03113
Designed By: CBO
Checked By: RHP
Drawn By: ANG
'DU
BICE
P.O. Box 2844
Glenwood Springs, Colorado 81602
Phone 970.618.5033
Fax 303.216.2796
Titus Residence
171 Fairway Lane
Garfield County, Colorado
Project Number: C1058
W3.0
ShRRI 3 nE 3