HomeMy WebLinkAboutEngineer ReportJanuary l 0, 2014
State of Colorado
Department of Local Affairs -Division of Housing
A TfN: Mr. Todd Anderson
1313 Sherman Street, Room 321
Denver, CO 80203
Re: D-9541·11'·5" x 20'-0" x 9'-0" Equipment Shelter
Dear Mr. Anderson:
1300 Davenport Drive
Minden. LA 7i055
omce (B00) 824-2614
Fax (318) 371-9210
WMv.fibrebond.co1n
Attached is the Plan Approval for the above referenced project Tiie COMCheck
Certificate for this building shows that the Envelope fails. We have attached .an analysis
report from MKK Consulting Engineers, Inc. regarding this building. The results of their
analysis show that "there is no energy savings achieved by increasing the wall and roof
insulation R-values .... Increasing the R-values traps more heat within the bui.lding and
more cooling is required to maintain the space temperature."
For this reason we are submitting this shelter as it would have been constructed using the
2009 IECC criteria in COM Check. We request that your office accept this reduced R-
value based on the annual energy consumption.
Please feel free to contact me at (318)-371-6319 if you have any questions or concerns.
Respectfully yours,
FIBREBOND CORPORAT!ON
/,) /,I ,./7 /,/ I',,,,/-"'' ,, ;J:>-··v--,,. t ,,,
Bob Norris, P.E.
Director of Engineering
COMcheck Software Version 3.9.2
Envelope Compliance Certificate
2012 IECC
Section 1: Project Information
Ptojecl Type: New Construction
Project Tit!e : D-9541
Construction Site: Owner/Agent
AT&T
Designer/Contractor:
Section 2: General Information
Building Location (for weather data):
Climate Zone:
Building Space Conditioning Type(s):
.a_ulJ!llng_J:yJ><!
Workshop
Denver, Colorado
Sb
Nonresidential
~· 228
Section 3: Requirements Checklist
Clirnate-Speclflc Requirements:
Bill Sanders
Fibre bond
Minden, LA
318-377-1030
Component Name!Descrlption Gross Cavity Cont.
Roof 1: Other Roof (b)
Exterior Wall 1: Solid Concrate:4" Thickness.Light Density, Furring:
None
Exterior Woll 2: Solid Concrete;4" Thickness,Ught Density, Furring:
None
Area or R-Value
Perimeter
194
165
90
Ex!erior Wall 3: Solid Concrete:4'' Thickness,Ughl Density, Fu£ring: 165
None
Exterior Wall 4: Sotld Concrete:4" Thlckness,Light Density, Furring: 90
None
Door 1·. Insulated Metal, Swing"1n9 21
Floor 1: S!ab·On-Grade:Unheated 63
R-Value
1'1.7
14.7
14.7
14.7
(a) Budget U-factors am used for software baseline calculations ONLY, and are not code requirements
{b) 'Other' components require supporting documentation for proposed U-factors.
Air Leakage, Component Certification, and Vapor Retarder Requirements:
[j 1. Conlinuous arr barrier is provided throughout the building thermal envelope.
Proposed
U-Factor
0.043
0.060
0.060
0.060
0,060
0.153
Budget
U-Factortal
0.027
0.078
0.078
0.078
0.078
0.370
0 2. Air barrier joinls and seams are sealed. The joints and seals ilre securely installed If~ or on the joint for Its entire length.
D 3. Pene!Jations of the air barrier and paths of air leoikoge are caulked, gasketed or otherwise sealed In a manner compatible witt1
the construction materials and locf'!tion. Joints and seals are sealed in Iha same manner or taped or covered with a moisture
vaJ)Of'-permeahle wrapping matefiaL Tha joints and seats are securely installed In or on ttle joint for i1s entire leng!h.
0 4. Ttie air barrier is continuous for all assemblies that are the thermal envelope and $Cross the Joints ond assemblies.
LJ 5. Recessed lighting fixtl1res Installed In the buitding envelope are Type !Crated as meeting ASTM E283, tested to «=2.0 cfm, and are
sealed with gasket or caulk.
Project Title: D-9541
Data filename: P:\EngineeringiCOMcheck\C0\0·9541 AT&T.eek
Report date: 12/30/13
Pago 1of10
Materials making up the air barrier have alr permeability <=D.004 cfm/fl2 or ere qualifying male rials as per Section C402.4.1.2.1.
Air leakage of fenestration. Windows/non-glazed sliding and swinging doors/skylights with no weepage openings <= 0.20
cfm/ft2. Skylights with weepage <= O.JO cfm/ft2. Curtain walls/storefront glazing<= 0.06 cfm/ft2. Doors: glazed s-.1Anglng
entrance/revolving/rolling<= 1.00 cfm/ft2. Doorn: garage <= 0.40 cfrn/ft2.
Exceptions:
O Fie!d·fabrlcated assembt!es.
0 8. Doors and access openings from conditioned space to shafts, chutes stairways and elevator lobbies ara gasketed, weatherstripped or
sealed.
Exceptions:
O Door openings required to comply with International Bullding Code as per Section C402A.4.
LJ 9. Stairway and shaft vents are provided l'Y'ilh Class I motorized dampers with a leakage rate<= 4 cfmlft2. Dampers are installed with
controls so that they are capable of automat!cal!y opening upon activation of any fire alarm or the interruption of power to 1he damper.
0 1 O. Outdoor air supply and exhaust openings are provided with Class IA motorized dampers having a leakage rate <=4 cfm/ft2.
Exceptioris:
O Gravity (nonmotorlzed) dampers having a leakage ra!e <=20 cfm/ft2 are permitted for exhaust and relief dampers for buildings less
than three stories in height above grade, or where the design outdoor air Intake or exhaust capacity <=300 cfm.
O Dampers smaller than 24 inches in either dimension are permitted to have a leakage <=40 cfrn/ft2.
0 11. Cargo doors and load Ing dock doors arc weather sealed.
0 12.Building entrance doors have a vestibule equipped with self·dos!ng devices.
Exceptions:
O Building entrances with revolving doors.
O Doors not intended to be used as a building entrance by the public, or intended solely for employee use.
D Doors that open directly from a space less than 3000 sq. ft. in area.
O Doors used primarily to facilitate vehicular movement or materials handling and adjacent personnel doors.
O Doors opening directly from a steeping/dwelling unit.
0 13.Component R-values & U·factors labeled as certified.
0 14.No roof insulation Is Installed on a suspended celrlng with removable ceiling panels.
0 15. '0lher' components have supporting documentation for proposed U·Factors.
0 16.lnsulation lhslalfed according tornanufacturer's instructions, in substantial contact with the surface being insulated, aid ln a manner
that achieves the rated R·value without compressing the Insulation. Except when Instructed othemise, edge joints between overlapplng
layers of continuous insulation are staggered.
0 17 .Radic:mt panels and associated components, designed for heat transfer from lhe panel surfaces to tha oe<:upants or indoor space are
insulated With a minimum of R·3.5
Minimum Skylight-Daylighting Requirements:
0 16.ln enclosed spaces> 10,000ft2 directly under a roof with ceiling heights >15 ft. and used as an office, lobby, atrium, concourse,
corridor, stora!Je, gymnasium/exercise center, convention center, automotive service, manufacturing, non.refrigerated warehouse, relait
store, distribution/sorting area, transportation, or workshop, the following requirements apply unless exempted:
O The daylight zone under skylights is >= half the floor area;
O The skylight area to dayl!ghtzone Is>= 3 percent with a skylight VT>= 0.40; or a minimum skylight effective aperture>"' 1 percent.
Exceptions~
D Spaces where the proposed general llghting power densities c:: 0.5 W/ft2..
0 Areas with obstructions thal block direct beam sunlight on>= 1/2 of !he roof over the enclosed area for more than 1,500 daytime
hours per year between 8 am and 4 pm,
0 Spaces where the daylight zone under rooftop monitors Is> 50 percent of the enclosed space floor area.
-----------~-------------·
Project Title: 0·9541
Data filename: P:\Engineering\COMcheck\C0\0·9541 AT&T.eek
Report date: 12/30/13
Page 2of10
0 19.Skylights in office, storage, automotive service, manufacturing, non-refrigerated warehouse, retail store, and distribution/sorting area
have a measured haze value> 90 percent unless designed to exclude direct sunlight.
Additional Efficiency Package Requirements:
0 1. The reduced interior lighting power option has been selected as the additlonal efficlenc:;y package required by th ls energy code,
Requlremenls for this package are applied lo the interior IJghtlng allowance calculations. Full compliance with this efficiency option
requires inspection and varification that the interior lighting allowances and fixture sf'..hedule found In the Interior lighting report are
compliant and deemed to pass.
---------------------~------------·------------
Project Title: D-9541
Data nlename: P:\Engineerlng\COMcheck\CO\D-9541 AT&T.eek
Report date: 12/30/13
Page 3 of 10
COMcheck Software Version 3.9.2
Interior lighting Compliance
Certificate
2012 IECC
Section 1: Project Information
Project Type; New Construction
Project TIUe : 0~9541
Construction Site: Owner/Agent:
AT&T
Section 2: Interior Lighting and Power Calculation
A
Workshop
Designer/Contractor:
8i!I Sanders
Fibre bond
Minden, LA
318-377-1030
B
Floor Area
c
Allowed
Watts/ft2
228 1.2
D
Allowed Watts
274
Total Allowed ~Valls= 274
Section 3: Interior Lighting Fixture Schedule
A
Fixture ID: Description I Lamp I Wattage Per Lamp I Ballast
Workshop (228 sq.ft.)
Unear Fluoroscen! 3: 48" TB 32W: Electronic:
Linear Fluorescent 4: 48" TS S2W: E!ectror1ic:
Section 4: Requirements Checklist
Lighting Wattage:
D 1. Total proposed watts must be less than or equal to total attowed watts,
Allowed Wattage: 274 Proposed 'vValtage: 108
Complies: YES
Mandatory Requirements:
B c D E
Lamps/ #of Fixture {CXD)
Fixture Fixtures Watt.
2 2 56 112
2 56 56
Total Proµosed Watts= 168
0 2. Dwelling units (complete Independent living facilities) vlithin commercial buildings are no! required to comply with Interior lighting
requirements of this code provided tlla! >=75 percent of the permanently installed fixtures other !hon low voltDge lighting conlaln only
high efficacy lamps.
U 3. ManL1a1 Controls: Each encfose<l space has manual lighting contiu!. Remotely localed manual controls are labelled for area of servk:e
and Indicate on/off st<1tus.
Exceptlon(s):
O Securlly/emergency areas 'Nith 24-hour operation.
O Stalrwaystcorrldors that are means of egress.
D 4. light Reduction Controls: Each space required to have a manual control also allows for reduclng the connected lighling load by at least
50 percent by either controlling all luminaires, dual switching of alternate rows o! lumlnaires, alternate !uminakes, or alternate lamps.
switching the middle lamp lumlnaires independently of olher lamps, or switching each tuminalre or each lamp.
Exceplion(s):
O Only one lumh1alre (lamp< 100 W) In sp.:ice.
O An occupant-sensing device controls U1e area.
Project Title: 0-9541
Data filename: P:\Engineerlng\COMcheck\CO\D-9541 A i&T .eek
Report data: 12130/13
Page 4 of 10
0 5.
0 7.
D 9.
D The area Is a corridor, equipment/store rooms, restrooms, public lobby, elec.fmech. room, or sleeping unit.
O Areas !hat use< 0.6 \'Vatts/sqJt.
O Daylight spaces having automatic daylighting controls.
Automatic time switching conlrol::; are installed and have i:in override switching device. The override switching device <1llows for<"' 2
hour operation cycle within spaces<= 5000 sq.fl., munual operation, and ls readily accessible and loc.ated where the operation of the
connected lights are visible or comm1..micated to the sv.titch.
Exception(s):
O Sleeping units, patient care areas; and spaces where automatic shutoff would endanger safety or security or where lighting is
lnlended for 24·hour operation.
O Emergency egress lighting.
O Spaces where lighting is conlrolletl with occupancy sensors.
O Malls, arcades, auditoriums, single tenant relail spaces, industrial faclli~es and arenas that are<= 20,000 sq.ft. are permil1ed
exc:,eed lhe 2-hour operation cycle limit when a captive key dev!C(i override switch ls Installed.
Occupant sensors are Installed In the followlng spaces and automatically turn lighting off within 30 minutes of au occupants leaving the
space: Classrooms, conference/meeting/training rooms, ernployee lur1ch and bref.lk rooms, private offices, storagefjanitorial roorns,
restrooms, and other spaces<= 300 sq.ft. Automatic-on sensors set power on <50 percent power.
Excspfion(s):
O Full power autornalic--on controls are permitted where manual-on operation would endanger the safety or security or the room or
building occupants.
Oaylightzones have either Individual lighting conlrols independent from 1hat of lhe general are<i lighting that are aflhe-r manual or
automatrc and serve zones «= 2,500 sq. ft Zones under skylights more than 15 feel from the perirnc~ter have Ugh!ing controls separate
from daylight zones adjacent to vertical fenestration.
Exceptlon(.s):
O Contiguous daylight zones spanning no rnore than two orientafions an:·} allowed to be controlled by a single controllfng davice.
O Daylight sp<1ces enclosed by walls or ceiling heigh I partitions and conlalning two or (ewer light fixtures are not required to have a
separale &Wilch for gp,neral area lighting.
Automatic daylight zone controls are capable or reducing power to< 35 percent using continuous dimming ballasts and
daylight-sensing controls OR, are capable of automatic power reduction uslng slcp-dlmming mull!-level switching and daylight-sensing
c.ontro!s having Bl least two control channels per zone and at least one control step in the 50 -70 percent range and another<= 35
percent of design power.
Medical tasK lighting or <:trt/hlstory display lighting daimed lo be exempt rrom co111pliance has a control device independent of !he
control of the nonexempt lighting.
D 10. Separate control device for display/accent lighting, case lighting, task lighting, nonvisua! lighting, under-shelf/cabinent lighting, lighting
for sale, and demonslra!ion lighling.
0 11. Holet/moti,;I sleeping ln1its and guest suites have control device(s) at thE: entry door that contrn! all permanent luminaires end swilclled
receptacles.
0 12. Exit signs 5 Watts or less per sign.
D 13, Tandem wired one·lamp and three-lamp ballasted lum!nalres (No single-!an1p l>alla::>l$).
Excepfion(s):
U flec'fronic high·frequenz;y b~lliJSI:;
O Lutninaircs not on same swilch.
O Recessed luminaires 10 ft. apart or surface/pendant not continuous.
O Luminafres on emergency circuits.
Additional Efficiency Package Requirements:
o 1. The reduced interior lighting µower op1ion has been selected as the additional efficiency package required Uy this energy code.
Requirements for lhls package arc applied to the interior lighting allowance U<lku!ations. Full compliance wilh this efficiency option
requires inspection and verification that the Interior lightlng allowances and fixture s<::hedule are comp!ianl and deemed to pass.
Section 5: Compliance Statement
Con1pllance St<Jtement. The propo8ed lighting design representedjn this document 1$ consistent wrth the bu1!dmg plans, spec1ficalions
and other calculations submitted with this permit application Tl)/Prol:J ed ligh!ingv·;tem has been designed to meet the 2012 IECC
requirements in COMch(lckVerslon 3 9 2 and to comply w1I (he mend fory reqwr rnls m the Reqrnremen!s Che:rlfst / /).,...._;_,, 'Li f "f··r" , /'A ~1\ l,J, J.. v'~'' ,,_/ ··1 1,( / . J_{lj, I£ -
Name ·Tide Slgnatu}e Date '
Project Tlt!e: 0-9541
Dal.a filename: P:\Engineering\COMcheck\C0\0-9541 AT&T.eek
Report date· 12/30113
Page 5 of 10
COMcfieck Software Version 3.9 . .2
Exterior Lighting Compliance
Certificate
2012 IECC
Section 1; Project Information
Project Type: New Construction
Project Tiiie: D-9541
Exterior Lighting Zone; 2 (Light industrial area with limlted 11ighttime use)
Construction Site: Owner/Agent: Designer/Contractor:
AT&T Bill Sanders
Flbrebond
Minden, LA
'318·3?7·103C
Section 2: Exterior lighting Area/Surface Power Calculation
A B c D
E1derior Area/Surface Quantity Allowed Tradable
Watts Wattage
I Unit
Main entry 3 ft or door width 20 Yes
Total Tradab!e Watts~=
Total Allowed Watts=
E
Allowed
Watts
IB xC)
60
60
60
Total Alkiwed Supplemental W.t'lt!sh = 600
~ Wallage tr.adeoffs are only allowed between tradab!e areas/sur races .
F
Proposed
Watts
27
27
... A supple1nenla! allowance equal lo 600 watts may be applied toward compliance of boU1 non-tradable and tradable areas/surfaces.
Section 3: Exterior lighting Fixture Schedule
A
Fixture ID: Description I Lamp I Watta!;je Per Lamp I Ballast
Maio entry (3 It of door width): Tradable Wattage
LED 1: LED Other Fixture Unit 28W:
Section 4: Requirements Checklist
Lighting Wattage:
B c D E
Lamps/ #of Flxlurc (CXD)
Fi)(ture Fixtures Watt.
2 27 27
Total Trndable Proposed Walls:: 27
LJ 1. Within each non·fradable area!suriace, total proposed walls must be Jess than or equal lo total Eitlowed watts. /\cross all tradable
areas/surfaces, tolal proposed watts n1ust be less Lhan or equal to lola1 allowed watts.
Compllanca: Passes.
Controls, Switching, and Wiring:
O 2. All exemption claims are associated with fixiures that have a conlrol device Independent of the control of the nonexempt lighting.
0 3. Lighting 110t designated for dusk-to.dawn operation Is controlled by e1U1er <i a photosensor {with tlme switch), or an astronomical lime
switch.
O 4. Lighting designa!ed for dusk-to-dawn operation Is controlled by an as!ronomlC'.al lime switch or pho!osensor.
D 5. All lirne switches are capable of retaining programming an<l the Uma selling during loss of power for a period of at least 10 hours.
Exterior Lighting Efficacy:
Project Title; 0·9541
Data filename: P;\Engineering\COMcheci<\CO\D-9541 AT& T.cck
Report date: 12/30/13
P<ige 6 of 10
0 6. All exterior building grounds luminalres that operate at greater than 100W nave minimum efficacy of 60 lumenfwatt.
Exceptions:
O Lighting that has bean claimed as exempt and Is identified as such in Section 3 tabts above.
O Lighting tl1at Is specifically designated as required by a health or life safety statue, ordinance, or regulaUon.
O Emergency lighting that Is automatlcally off during normal building operntion.
O Lighting that is controlled by motion :;;ensor.
Section 5: Compliance Statement
Compliance Statement: The proposed exterior lighting design r sented In this document Is consistent with the building plans. specifications
and other calculations submitted with this permit appllca!lon. hep posed lighting stem has been designed to meet the 2012 IECC
-----··----------·--·--··-···---·
Project Tll!e: D-9541
Data filename; P:\Engineering\COMcheck\CO\D-9541 AT&T.eek
Report date: 12/30113
Page 7 of 10
COMcf1ecl< Software Version 3.9.2
Mechanical Compliance Certificate
2012 IECC
Section 1: Project Information
Project Type: New Construction
Project Title : D-9541
Construction Site: Owner/Agent
AT&T
Section 2: General Information
Building Location (for weather data):
Climate Zone:
Denver, Colorado
5b
Section 3: Mechanical Systems list
Ql!antlt:-: Sy~.t~m JYP.(:!.~ ... PE.~\!.r!ptlo)11
2 HVAC System 1 {Single Zone):
HAaling: 2 each· Central Furnace, Electric, Capacity= 21 kBl1.r/i1
No minimum efHciency requirement applies
Designer/Contractor:
Bill Sanders
Flbrebond
Minden, LA
318·377-1030
Cooling: 2 each -Other, Capacity i= 62 kBtulh, Air·Coofed Condenser, Air Economizer
No minimum efficiency requirement applies
Fan System: None
Section 4: Requirements Checklist
Requirements Specific To: HVAC System 1 :
O 1. Newly purchased equipment meets lhe efficiency requirements
U 2. Integrated air economizer ls required tor individual cooling sys!ems and allows modulation of outdoor air and retum ;;iir dampers to
provide up to 100% of tile design ~uppfy air quantity as 01.Jtdoor arr fol' cooling. All oir economizers shall be capable of automalically
reducing outdoor air inttike to lhe design minimum outdoor air Quantity when outdoor air lntal(e will no lrn1ger reduce cooling energy
usage.
0 3, Air economizer dampers c~in be sequenc~d with the cooling equlprnen! and not controlled exclusively by mixed air tempernlure.
E.xcepflon(s):
O System controlled from space temperature (such as single-zone systems).
lJ 4. Cooling system provides a means to relieve excess 0~1tdoor air during economizer operation.
Generic Requirements: Must be met by all systems to which the requirement is applicable:
U 1. Plant equipment and system capacity no greater than needed lo meet loads
Exceplion(s):
U Standby equipment automatically off when primary system Is operating
O Multiple. units controlled to sequence operation as a func!io11 of load
D 2. Minimum one tempcro!um control device per system
0 3. Minimum one humidity control d~vice per installed hurnidiflcationfdeMumldification system
U 4. Load calcu!al!ons per ASHRAE/ACCA Standard 1B3.
D 5. Automatic Coolrols: Setback to 55°F (heat) and 85"F (cool); 7·dsy dock, 2-hour occupant override, 10·hour backup
Exception(s):
Project Title: 0.9541
Data Olename: P:\Engineering\COMcheck\C0\0-9541 AT&T.eek
Report date: 1213.0113
Page 8 of 10
O Continuously operatlng zones
O 2 kW demand or less, submit calculations
0 6. Automatic start controls that can automatically adjust the daily start time of the HVAC system are pfovlded for each system.
D 7. Outside-air source for ventilation; system capable of reducing OSA to required minimum
0 8. R-6 supply and return air duct Insulation in unconditioned spaces
R-8 supply and return air duct insulation outside the building
R-8 insulation between ducts and the buiding exterior when ducts are part of a building assembly
Exceptlon(s):
O Duels located within equipment
O Ducts with interior and exterior temperature difference not e:icceeding 15°F.
0 9. Ducts sealed -longibJdinal seams on rigld ducts; transverse seams on all ducts; UL 181A or 181 B tapes and mastics
0 10.0peratlon and maintenance manual provided to building owner
0 11. Thermostatic controls have 5"F dead band
Exception(s):
O Thermoslals requiring manual changeover between heating and cooling
0 12.Demand control ventilation (DCV) present for high design occupancy areas (>25 person/1000 ft2 in spaces >500 ft2) and served by
systems with any one of 1) an air-side economizer, 2) automatic modulaHng control of the outdoor air dampar, or 3) a design outdoor
airflow greater than 3000 cfm.
Exceptlon(s):
O Systems with heat recovery.
O Multiple-zone systems without DOC of lndlvldua! zones communicating with a central control panel.
O Systems with a design outdoor airflow less than 1200 cfm.
D Spaces where the supply airflow rate minus any makeup or outgoing tremsfer air requirement Is less than 1200 cfm.
O Ventilatlon for process loads only.
0 13.Motorized, automatlc shutoff dampers required on exhaust and outdoor air supply openings
Excepffon(s):
O Gravity dampers acceptable in buildings <3 stories
0 14.Automatic controls for freeze protection systems present
0 15.Each fan system has an energy recovery system when percen1 outdoor air at full design airtlow rate:::.= 70"/o AND design supply fan
airflow rate>= 5,000 cfm.
Exc13pfion(s):
O Laboratory fume hood systems with a total exhaust rate .t= 5000 cfm.
O Systems serving spaces fhat are not cooled and heated to <60"F.
O Systems with more than 60% of the outdoor heating energy is provided from site-recovered or site solar energy.
o Systems exhausting toxlc, flammable, paint, or corrosive fumes or dust.
O Systems requiring dehumidification with cooling coll energy recovery In series with the cooling coil.
O Systems expected to operate< 20 hrs per week when outdoor air percentage>= 30%.
D Where the largest exhaust source Is less than 75°/D of the design outdoor airflow.
0 16. Meehan.lea! systems shall meet commlsslonlng and complet!on requirements Jn Sectlon C408.2.
Section 5: Compliance Statement
C-Ompliance statement: The proposed mechanical design repres
and other calculations submll\ed with this permit appllcatlon. T
Cha ter 8, requirements ln COMcheckVerslon 3.9.2 and 1
n this document is consistent with the bullding plans, specifications
d mechanical s stems have been designed to meet the 2012 IECC,
heckllst.
~ 1L-u~'
Section 6: Post Construction Compliance Statement
0 HVAC record drawings of the actual instaHatlon, system capacities, calibration infonnation, and performance data for each equipment
provlded to the owner.
0
0
·. rnenl and system provided to the owner by the mechanical contractor.
Written HVAC balancing and operation eport
ovlde .. d· ~the wner.
ompletnc . ~ -· · · -·
(L ~ T e a ve post construction requ!rel11€nts
(;,W1 -------
------·----·· ---··--···-----
Project Title: D-9541
Data filename: P:\Englneering\COMcheck\CO\D-9541 AT&T.eek
Report dale: 12/30/13
Page 9 of 10