HomeMy WebLinkAboutEngineer's Report 08.10.2012.pdfOIL SERYICE August 10, 2012 PO Box 2844 Glenwood Springs, CO 81602 Ph 970-618-5033 Fax 303-216-2796 AFAB, Inc. 3 Seven Oaks Road Glenwood Springs, CO 81601 SCANNED Project No. C1009 Subsurface Analysis, Onsite Wastewater Treatment System (OWTS) Design Evaluation, and Design Criteria for Existing OWTS Accessory Building with a toilet and hand sink 3 Seven Oaks Road Garfield County, Colorado Justin, ALL SERVICE septic, LLC performed a subsurface analysis and onsite wastewater treatment system (OWTS) evaluation and design criteria for the existing accessory building at the subject property. The property is located in Missouri Heights, in an area where OWTS and wells are necessary. SITE CONDITIONS An accessory building with a sink and toilet, used by 2 -people daily, presently exists. The OWTS has already been installed and was observed during our site visit. SUBSURFACE The subsurface analysis was conducted by a review of an existing soil report and observations of soils on site. A Soil Investigation Report was compiled for the subject property on October 17, 2007 by Colorado Engineering & Geotechnical Group, Inc., Project # 073-0184. Three test holes were excavated as part of the soil investigation. Depths of the excavations varied from 5 -feet to 9 -feet. No groundwater or bedrock was encountered. Soils were described as clayey -silty sand with rocks and cobbles, brown to light brown, fine to coarse, medium dense to dense. A copy of the Colorado Engineering & Geotechnical Group, Inc. report is attached. DESIGN SPECIFICATIONS The OWTS design is based on a toilet and hand sink, used by 2 -people. An average daily wastewater flow of 70 GPD will be used. A design flow of 113 GPD is calculated and requires a minimum tank capacity of 141 gallons (minimum 750 gallons per regulations). A percolation rate of 25 MPI will be Page 2 used and is appropriate for the sandy soils described in the Soil Investigation Report. A minimum of 57 square feet with the use of gravelless chamber trenches is required. The OWTS installed includes a 1000 -gallon Norwesco septic tank, a 7 -hole Tuf-Tite distribution box, and five Biodiffuser ARC 36 chambers (61.7 square feet). The system appeared to be functioning properly at the time of the site visit. RECOMMENDATIONS • Install a 2 -way clean-out within 5 -feet of the building. • Insulate the pipe coming out of building with blue board if installation depth is less than 24 - inches. • Install effluent filter on outlet tee of septic tank. • Install observation port on last chamber in trench. • Trench area should be covered with native vegetation. • No heavy equipment should be used over absorption area and no large animals should be corralled over the absorption area. OPERATION INFORMATION AND MAINTENANCE The surface of the drain field should be seeded. Vegetation is an important factor in drain field performance. Erosion control should be practiced prior to and during re -vegetation. Geo -fabrics or plastics should not be used over the drain field. No heavy equipment, machinery, or materials should be placed on backfilled drain field. Livestock should not graze on the drain field. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a drain field. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. The effluent filter should be cleaned annually, or as needed. Non -biodegradable materials should not be placed into the OWTS. Grease should not be placed in drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. Please call with questions. Sincerely, ALL SERVICE septic, LLC 0.0tA (1.1 Ov-)6AA8 Carla Ostberg, MPH, REHS 3 copies Page 3 Cut in hillside near OWTS installation. Another cut bank near OWTS installation. Side of accessory building. Plumbing comes out of building here. Recommend installing clean-out within 5 -feet of building. Inlet tee of septic tank. installation of effluent filter. Outlet tee of septic tank. Recommend Page 4 Page 5 Approximate location of gravelless chamber trench. Recommend fencing off field area and discontinue use for any staging, trailer parking, or large animals. Native vegetation should be re-established in the area over the trench. iL HOUSE PARCEL 4 0 0 PROPERTY LINE ACCESSORY BUILDING N EXISTING 1000 -GALLON, TWO-COMPARTMENT SEPTIC TANK DISTRIBUTION BOX ARC ADS CHAMBERS J O SITE PLAN AND EXISTING OWS NOT TO SCALE Date: 08/13/12 Revision: Designed By: CO Drawn By: ANG P.O. Box 2844 Glenwood Springs, Colorado 81602 Phone 970.618.5033 Fax 303.216.2796 AFAB, Inc. Seven Oaks Road Glenwood Springs, Colorado 81601 Project Number: C1009 W1.0 Sheet 1 of 7 DESIGN ACCESSORY BUILDING WITH TOILET AND HAND SINK FOR USE BY TWO PEOPLE TOILET = 24.8 GALLONS/PERSON/DAY HAND SINK = 8.4 GALLONS/PERSON/DAY (24.8 + 8.4) x 2 = 66.4 GALLONS/PERSON/DAY (ROUND TO 70 GPD) AVERAGE DAILY FLOW = 70 GALLONS DESIGN FLOW = Q = 1.5 x 70 =113 GALLONS TANK: 113 x 30 HOUR RETENTION TIME = 142 GALLONS EXISTING 1000 -GALLON, TWO-COMPARTMENT TANK ABSORPTION AREA: PERCOLATION RATE = 25 MPI CALCULATED ABSORPTION AREA = Q/5 x SQRT 25 = 113 SF 50% REDUCTION, GRAVELLESS CHAMBER TRENCHES TOTAL AREA REQUIRED = 56.5 SF 56.5 SF/ 12.34 SF PER CHAMBER = 5 CHAMBERS EXISTING 5 BIODIFFUSER ARC 36 CHAMBERS Dale: 08/13/12 Revision: Designed By: CO Drawn By: ANG P.O. Box 2844 Glenwood Springs, Colorado 81602 Phone 970.618.5033 Fax 303.216.2796 AFAB, Inc. Seven Oaks Road Glenwood Springs, Colorado 81601 Project Number: C1009 W2.0 Sheet 2 of 7 A II P.O. Box 2844 ' I } Glenwood Springs, Colorado 81602 RR Phone 970.618.5033 SE6VI1 .: r. Fax 303.216.2796 s i m zof rn • 1 PREPARED THIS DETAIL RASED ON INFORMATION PROVIDED TO ADS. NTS AS REQUESTED. ADS HAS NOT PERFORMED ANY ENGINEERING 0 IEPENOENTLY VERIFIES' THE INFORMATION SUPFUEO. THE INSTALLATIO NS ANG ME NOT SPECIFIC FOR THIS PROJECT. THE DESIGN ENGINE IT IS THE DESIGN ENGINEERS 'RESPONSIBILITY TO ENSURE THE DE JCABLE NATIONAL. STATE, OR LOCAL REQUIREMENTS AND TO ENSURE THIS PROJECT. m6 A Z 9 I G _ •_•30.0.): li, ''' r r y . tt AFAB, Inc. Seven Oaks Road Glenwood Springs, Colorado 81601 Project Number: C1009 r ot pm.. ri FG�w z ��� �— .. o -at • *ad. =ri 0 ill T Miiral i i :min lir _114c) I D, 31111 O 1111.11.- ni MI- a IIII- W 4 IMAND /110 g3 :MNS i MMus i Mli1, IN i MawrNNW �_ Revision: 08/08/12 Designed By: CO Drawn By: ANG 01\ �, i mil In n 1 o E ; z %Q u, m W3.0 Sheet 3 of 7 lflL + P.O. Box 2844 rp r S �; tf Phone 9 0 61r8. 033 olorado 81602 SEBYICE ) Fax 303.216.2796 A U m -i D u. iWA A m r A N Nr W N x7 -w rn WW N 44.0 , lissmisomi 11 -��, • :1 AFAB, Inc. Seven Oaks Road Glenwood Springs, Colorado 81601 Project Number: C1009 i Mil RAI i 111 m 11 1.--i----'' x a r eZ_�'W Asir N m y m N ' S n r 1 n A n r W cn .- NI^ m m N .��• 8 /WI. lila fill �� 7? 1: al JTP 17FEB97 ii .'a o p ' IraI Z Vam m IIIIIIIII A 11 ��- 11 1 zn �741 I n 1 m � ' m ` Revision: 08/08/12 Designed By: CO Drawn By: ANG N § 10 GALLON SEPTIC TANK IORWESCO BONIFACIUS MN - S .p In -. J` N, DIMS UPDATED' A 4 S 6)M-- Wfill1 _ j„ `r. 12 A ' O r O, 88 on ru QL W4.0 Sheet 4 of 7 _ cm -1 Z r -nm In mm r ttl .i 0 N z m 0 x X$ n1 fill P.O. Box 2844 Glenwood Springs, Colorado 81602 SEE Fax Phone 970.618.5033 Fax 303.216.2796 ar Z s 0 r rn C7 P1 — D N A 8 N o C. °D r A GI n D AFAB, Inc. Seven Oaks Road Glenwood Springs, Colorado 81601 Project Number: C1009 r rn N UI A L V Pl 01:1 r to J -A P1 Ca N 1000 GALLON SEPTIC TANK NY1 •Sft3VSINOG 'IS nns3muoue r xiP \i z Z 31 H Revision: 08/08/12 Designed By: CO Drawn By: ANG S C a rn tsv a A w mg W5.0 Sheet 5 of 7 o rn N i n 4TUF'TITE 7-Hole Distribution Box Tuffince OdWiratuftti©[fI N `NM Tom own • Injection molded HDPE • Non -corrosive ■ Simple to install • Easy to level In a septic environment, no other material can match High Density Pcdyethylene in delivering a lifetime of trouble-free service. Tuf-Tite Distribution Boxes are injection molded, using only premium HDPE which contains no fillers or foam. Tough Problem Providing simple, reliable, cmcI perrrnnent means for divitind ptb tank effluent tow. TUF-TITE Solution A strong, stable, permanent, non-conosivo Tut -Tito Distribution Pox, with Tut -Tito Sped Levek:r in Bch outlet. Snap -in pipe seals They're patented Simply insert your PVC pipe and push it through the flexible, polyethylene Tuf-Tite seal. Pipes fit watertight. Installation couldn't be easier. They're permanent Unlike cement -based pipe grout. Tuf-Tice seals will not crack or corrode in septic conditions. They stay pliable and watertight permanently. Stackable Riser Easiy extend the top of the box to grade, in 6" inorements. Stackable HDPE Risers interlock firmly and accept a screw -on lind or grate. P.O. Box 2844 Glenwood Springs, Colorado 81602 Phone 970.618.5033 Fax 303.216.2796 AFAB, Inc. Seven Oaks Road Glenwood Springs, Colorado 81601 Project Number: C1009 W6.0 Sheet 6 of 7 LTOF'TITE 7 -Hole Distribution Box 7HD2 • Injection molded. Exceptionally strong. • Domed Lid is ribbed for exceptional strength. ■ Patented snap -in pipe seals simplify installation. 14-1/2' Darned Lid Can be anchored to box ar Riser vrith 4 stainless screws. Optional Risers. They stack, In 6" - increments, to 6" extend Box to - grade. 6" Ftttings inctuded. The 7HD2 comes complete with a Domed Lid and 9 snap -in fittings of your choice. INSTALLATION IS JUST THIS SIMPLE 1. Position the Distribution Box on level virgin soil. Do not place box on a concrete slab. 2. Install the inlet pipe and outlet pipes. Be sure the bottoms of all pipes rest on virgin soil. 3. Level the Distribution Box and all pipes as needed. 4. Backfill the pipes to within two feet of the Distribution Box. Recheck the level of the box, then backfill up to the top lid ridge. 5. Install and adjust Tuf-Tile Speed Levelers. 6. Place lid on the Distribution Box and finish backfilling. Choice of Fittings S-35 Pipe Seal, ton. ■ Sewer and Drain ■ SDR 35 ■ ASTM 3034 ■ Thin Wall ■ 1500 Lo. Crush S-40 Pipe Seal, for. ■ Schedule 40 ■ 4" Coiugated P-10 Plug, for unused holes Tuf-TiteSpeed Levels; TM Contrd the flow of effluent from the Distribution Box. Simply insert a Speed Leveler into each nutlet pipe. Rotate each Speed Leveler so the flow is distributed as desired. Available for 3" or 4" PVC pipe. Versatile Options Drain Grate Black 16" x 16" HDPE grate. ADA compliant. Can be affixed to Box or laser with 4 stainless corner screws. 6" Riser Stackable 16" x 16" HDPE Riser provides 6" elevation 10 the Box or Riser. Ribbed for added rigidity. 4:TUF'TITE' Drainage and Sepbc Products rut -Tit& Ca potation 1200 flex Court Lake Zurich, Illinois 60047 51 599 Tir-Tte Caporauon Ft -win 7HD2-3. Printed in USA Water -fight Lids anti Risers by Tuf-Tet& ALL SERYICE P.O. Box 2844 Glenwood Springs, Colorado 81602 Phone 970.618.5033 Fax 303.216.2796 AFAB, Inc. Seven Oaks Road Glenwood Springs, Colorado 81601 Project Number: C1009 W7.0 Sheet 7 of 7 i 1 HOUSE PARCEL4 0 0 11 11 11 11 PROPERTY LINE ACCESSORY BUILDING EXISTING 1000 -GALLON, TWO-COMPARTMENT SEPTIC TANK DISTRIBUTION BOX ARC ADS CHAMBERS N O SITE PLAN AND EXISTING OWS NOT TO SCALE Date: 08/13/12 Revision: Designed By: CO Drawn By: ANG ALt MICE P.O. Box2844 Glenwood Springs, Colorado 81602 Phone 970.618.5033 Fax 303.216.2796 AFAB, Inc. Seven Oaks Road Glenwood Springs, Colorado 81601 Project Number: C1009 W1.0 Sheet 1 of 7 • NC;1"19144r --a�rt 7�...-.-....... w-..�.. r .... 4,1 _C C,7 (J IP D 0 C) !NI{-�"1 {, E i JC. 8 Q w 2r c7=' JJ x4 0 0 0 v