NOV. 2, 2012
Rev. 11/14/2012
PETER GUY
4954 ROAD 214
NEWCASTLE, CO 81647
TO WHOM IT MAY CONCERN:
WELL LOCATION: 4954 ROAD 214, NEWCASTLE, CO
THE WELL WAS PUMPED CONTINUOUSLY FOR 25.23 HOURS AT A FINAL PUMPING RATE
AVERAGE OF 1.657 GALLONS PER MINUTE. THE WELL DRAW DOWN DURING THE TEST
WAS .3 FEET AND IT RECOVERED FULLY WITHIN 90 MINUTES.
DATE OF TEST: 10/15-16/2012
APPROXIMATE STATIC WATER LEVEL: 63'
APPROXIMATE DEPTH OF WELL: 96.6'
HORSE POWER OF PUMP: 3/4 HP
APPROXIMATE PUMP SETTING:
DURING THE 25 HOURS OF CONSTANT PUMPING THIS WELL, A TOTAL OF 2,509
GALLONS WERE PUMPED OUT.
IN CONCLUSION, THE RESULTS OF THIS PUMPING DRAWDOWN TEST INDICATE THAT
THIS WELL SHOULD HAVE NO PROBLEM PRODUCING 700 GALLONS OF WATER PER
DAY. BASED ON A VOLUME OF 350 GPD FOR EACH HOUSEHOLD THIS WELL SHOULD
PROVIDE AN ADEQUATE VOLUME OF WATER TO ACCOMMODATE TWO HOMES.
THE TEST DATA OBTAINED IS REPRESENTITIVE OF ONLY CONDITIONS O[3S+ERVED (IPJ
OCTOBER 15th AND 16th AND DOES NOT ACCOUNT FOR POSS_BLF SF 4SONAt
VARIATIONS IN THE AQUIFER NOR LONGER PUMPING DURATIONS.
TOM PLATZER
STATE LICENSE #1106
AQUA TEC SYSTEMS, INC
P.O. BOX 488
GLENWOOD SPRINGS, CO 81602
PH# (970) 984-0311 FX# (970) 984-0312
DATE: 11/14/2012
PETER GUY
4954 ROAD 214
NEWCASTLE, CO 81647
TO WHOM IT MAY CONCERN:
WELL LOCATION: 4954 ROAD 214, NEWCASTLE, CO
PLEASE SEE THE WATER QUALITY TEST RESULTS CONTAINED IN THE OIL & GAS LAB
REPORT OF MARCH 21, 2012 FOR THE FOLLOWING CONTAMINANTS:
RESULTS MCL (MG/L)
ARSENIC <.004 .05
BARIUM 0.039 2.0
CHROMIUM <.010 .1
NITRATE 2.0 10
NITRITE <.061 1
SELENIUM .0078 .05
ANTIMONY <.02 .006
BERYLLIUM <0.0004 0.0004
NICKEL <.03 .1
THALLIUM .0010 .002
SULFATES 76.2 NONE
THE ADDITIONAL IOC'S WERE TESTED BY ACCUTEST AND REPORTED ON 11/14/2012
FOR THE FOLLOWING:
RESULTS MCL (MG/L)
FLUORIDE 0.58 4.0
ASBESTOS N.D. 7miI.F/L
CADMIUM <0.00020 0.0050
MERCURY <.001 .002
TOTAL NITRATE+NITRITE 0.43 10
CYANIDE <.005 .2
GROSS ALPHA 13(+OR-4pCi/L) 15 pCi/L
GROSS BETA 0.0 50 Pci/I
MESA LAB DID THE COLIFORM BAC -T USED TO DETERMINE IF DISENFECTION IS
WORKING, HOWEVER, NONE EXSISTS.
COLIFORM BACTERIA - ABSENT
OF THE CONTAMINANTS TESTED THERE WAS NONE THAT EXCEEDED THE MAXIMUM
CONTAMINATION LEVELS FOR THE STATE PRIMARY DRINKING WATER STANDARDS.
•