Subject: Foundation Construction Observation and Testing Review
Equipment Shelter Addition
TXP1 Compression Plant
Garfield County, Colorado
Terracon Job No. AD121050
As requested, the Terracon representative tested subgrade soil preparation and
structural fill compaction of the Equipment Shelter Addition at the TXP1 Compression
Plant in Garfield County, Colorado on as requested, part-time basis September 26 and
27, 2012. We reviewed our records of fill compaction (attached) in preparation of this
report. In summary, our review of this structure indicates construction in conformance
with our recommendations and the structural drawing number SC -001, Rev.B by
Samuel Engineering. Inc. dated 08/24/12 (their Job Number 12096-01).
We appreciate the opportunity to provide geotechnical services. If we can be of
further service, please call.
Sincerely,
Terracon Consultants, Inc.
John P. Withers, P.E.
Engineer
(1 copy sent)
FIELD DENSITY TEST REPORT
Report Number: AD12I050.0002
Service Date: 09/26112
Report Date: 09/28/12
Task:
lierracon
2308 Interstate Ave
Grand Junction, CO 81505
970-245-4078
Client
Elkhorn Construction Inc
Attn: John Dick
2181 45 1/2 Road
DeBeque, CO 81630
Project
Parachute Creek GC Building
Williams Gas Plant
DeBeque, CO 81630
Project Number: AD 121050
Material Information
Mat.
No.
1
Proctor
Ref. No.
Classification and Description
AD121050.0001 -314" Base Course
Field Test Data
Test
No.
Test Location
Meter Skid
1 SW corner of Meter Skid
2 Re -test of Test No. 1 dated
9/26/12
3 NW corner of Meter Skid
4 SE comer of Meter Skid
Datum: B.G. Below Grade
Lift / Mat.
Elev. No.
Laboratory
Test Method
Lab Test Data
Optimum
Water
Content
(%)
ASTM D1557 6.2
Probe
Depth
(in)
7' B.G. 1 8
7' B.G. 1 8
6' B.G. 1 8
6' B.G. 1 8
Wet Water
Density Content
(pct) (pct)
Max. Lab
Dry Unit
Weight
(pct)
139.9
Water
Content
(%)
Project Requirements
Water
Content
(%)
+/-
Minimum
Compaction
(%)
95
Dry Unit Percent
Weight Compaction
(pct) (%)
144.6 11.2 8.4 133.4 95
145.7 9.8 7 2 135.9 97
143.1 10.1 7.6 133.0 95
145.3 10.1 7.5 135.2 97
Serial No:
Comments: Test and/or retest results on this report meet project requirements as noted above.
Ramon Ortiz with Elkhorn Construction requested we stay on site until they were ready for test, 4 hours of standby time.
Services:
Terracon Rep.: Elias Acevedo
Reported To: Ramon Ortiz with Elkhorn Construction
Contractor: Elk Horn
Report Distribution:
(1) Elkhorn Construction Inc
Test Methods: ASTM 06938
Started:
Finished:
Reviewed By:
Robert Anderson
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
Carr.. 4.r.12 Rev Page 1 of 1
FIELD DENSITY TEST REPORT
Report Number: AD121050.0003
Service Date: 09'2712
Report Date: 09f28;12
Task:
1Terracon
2308 Interstate Ave
Grand Junction, CO 81505
970-245-4078
Client
Elkhorn Construction Inc
Attn: John Dick
2I81 45 1r2 Road
DeBeque, CO 81630
Project
Parachute Creek GC Building
Williams Gas Plant
DeBeque, CO 81630
Project Number: AD121050
Material Information
Mat.
No.
Proctor
Ref. No.
Classification and Description
1 AD121050.0001 -3.4" Base Course
Field Test Data
Test
No.
Test Location
Meter Skid
1 SW corner of Meter Skid,
subbase
2 NW corner of Meter Skid,
subbase
3 Middle of Meter Skid, subbase
4 SE corner of Meter Skid,
subbase
5 NE corner of Meter Skid,
subbase
6 Middle of Meter Skid, subbase
7 North Middle of Meter Skid,
subbase
8 South Middle of Meter Skid,
subbase
9 NW corner of Meter Skid,
subbase
10 Middle of Meter Skid, between
Anchors
Lift /
Elev.
Laboratory
Test Method
ASTM D 1557
Probe
Mat. Depth
No. (in)
Lab Test Data
Optimum
Water
Content
(%)
6.2
Wet Water
Density Content
(Pci) (pcf)
Max. Lab
Dry Unit
Weight
(pci)
139.9
Project Requirements
Water
Content
(%)
+1-2
Minimum
Com paction
(%)
95
Water Dry Unit Percent
Content Weight Compaction
(%) (pcf) (%)
5' B.G. 1 8 143.5 7.6 5.6 135.9 97
5' B.G. 1 8 112.1 7.4 5.5 134.7 96
4' B.G. 1 8 145.9 8.4 6.1 I37.5 98
3' B.G. 1 8 142.5 8.3 6.1 134.2 96
2' B.G. 1 8 144.8 7.8 5.7 137.0 98
1' B.G. 1 8 143.4 7.7 5.7 135.7 97
Grade 1 8 142.7 9.1 6.9 133.5 95
Grade 1 8 146.0 7.7 5.6 138.3 99
S.G. 1 8 142.3 5.9 4.3 136.4 97
S.G. i 8 139.4 6.5 4.9 132.9 95
Datum: B.G. - Below Grade Serial No: Std. Cnt. M:664
Comments: Test and/or retest results on this report meet project requirements as noted above.
Services:
Terracon Rep.: Elias Acevedo Started:
Reported To: Ramon Ortiz with Elkhorn Construction Finished:
Contractor: Elk Horn
Report Distribution:
(I) Elkhorn Cansiniclion Inc
Test Methods: ASTM D6938
Reviewed By:
Std. Cnt. D: 2263
Robert Anderson
Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable to the
actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials.
CR0007, 4.17.12. Rcti 5 Page 1 of 1