HomeMy WebLinkAboutElectrical Inspection ReportInspection Report Page 1 of 1 COLORADO STATE ELECTRICAL BOARD INSPECTION REPORT / CORRECTION NOTICE Date Received: 26 -MAR -14 Permit Number. 753015 Contractor/HomeOwner: Address: Type of Inspection: Action: P &.1 Electric, Inc. Encana Story Gulch Compressor Site Complete Final Accepted Comments or Corrections: Regarding Correction Item # 2 from last inspection: The meter building is mounted on a skid. This entire skid is has been classified as a Div 2 area. Boundary seals are installed for the skid, not the building. Required seal fittings at cable tray boundary ok. Inspectors Name: Norman Feck Phone Number: 303-869-3442 Date: 26 -MAR -14 COLORADO STATE ELECTRICAL BOARD DEPARTMENT OF REGULATORY AGENCIES 1580 Logan St. Suite 550 Denver, Colorado 80203-1941 Phone: (303) 894-2985 https://www.dora.state.co.us/pts/real/Ep Web_Inspection_GUI.Process_Page 4/9/2014