Loading...
HomeMy WebLinkAboutApplication- PermitGarfield County Building & Sanitation Department 108 8th Street, Suite #201 Glenwood Springs, Co. 81601 Office- 945-8212 Inspection Line- 384-5003 NO. Ct c* esS Job Address COG a. OA I l Qt,L o -Z a g/63-3 07b--1- -yriatto-A Nature of Work Building Permit /,9a e.P-le a393- /Y/-oo -351 Use of Building �„ ," .�� '��� 61--t Owner Contractor Amount of Permit $ 0259? a • 9� j Date Clerk ljnaA.,41, atlas - 1 - Permit No: GARFIELD COUNTY BUILDING PERMIT APPLICATION 108 8" Street, Suite 201, Glenwood Springs, CO 81601 Phone: 970-945-8212 / Far 970-384-3470 / Inspection Line: 970-384-5003 0140.5 Parcel/Schedule No: 2373^ iort- 36! AGREEMENT PERMISSION IS HEREBY GRANTED TO THE AP CANT AS OWNER CONTRACTOR AND/OR THE AGENT OF THE CONTRACTOR OR OWNER TO CONSTRUCT THE STRUCTURE AS DETAILED ON PLANS AND SPECIFICATIONS SUBMITTED TO AND REVIEWED BY THE BURRING DEPARTMENT. IN CONSIDERATION OF THE ISSSUANCE OF 11115 PERMIT, THE SIGNER_ HEREBY AGREES HI COMPLY WITH ALL BUILDING CODES AND LAND USE REGULATIONS ADOPTED BY GARFIELD COUNTY PURSUANT TO AUTHORITY GIVEN IN 3025201 CRS AS AMENDED. THE SIGNER FURTHER AGREES THAT IF THE ABOVE SAID ORDINANCES ARE NOT FULLY COMPILED WIT El IN THE LCOATION, ERECTION, CONSTRUCTION, AND USE OF THE ABOVE DESCRIBED STRUCTURE, THE PERMIT MAY BE REVOKED BY NOTICE FROM THE COUNTY AND THAT THEN AND THERE IT SHALL BECOME NULL AND VOID. THE ISSUANCE OF A PERSTE BASED UPON PLANS, SPECIFICATIONS AND OTHER DATA SHALL NOT PREVENT THE BURRING OFFICIAL FROM THEREAFTER REQUIRING THE CORRECTION OF ERRORS IN SAID PLANS, SPECIFICATIONS AND OTHER DATA OR FROM PREVENTING BUILDING OPERATION BEING CARRIED ON THEREUNDER WHEN IN VIOLATION OF THS CODE OR ANY OTHER ORDINANCE OR REGULATION OF THIS JURISDICTION. THE REVIEW OF SUBMITTED PLANS AND SPECIFICATIONS AND INSPECTIONS CONDUCTED THEREAFTER DOES NOT CONSTITUTE AN ACCEPTANCE OF ANY RESPONSIBILITIES OR LIABLITIES BY GARFIEID COUNTY FOR ERRORS OMISSIONS OR DISCREPENCIES. THE RESPONSIBILITY FOR THE57: ITEMS AND IMPLEMENTATION DURING CONSTRUCTION RESTS SPECIFICIALLY WITH THE ARITCTECT, DESIGNER, BUILDER AND OWNER. COMMENTS ARE INTENDED TO BE CONSERVATIVE AND IN SUPPORT OF THE OWNERS INTEREST. Gvfon.0B3 1 HEREBY ACKNOWLEDGE THAT 1 HAVE READ AND UNDERSTAND THE AGREEMENT ABOVE X0\40 { — 1013.5` Job Address: �� .Z 0062-- Gia U3 CA -re -EON Dn N Ge l t 1 Lot No:Block No: Subd. / Exemption: NI Lu -IA -ND C.'Ntamo'(OIu 2rviCifTy �DD A dry (32_ k_ gee. Ph: r Ph: �7—qlrq 3 ontrac r: Address �� "P�h: Lk. No. 4 ArcLiteet/E ear: F -n V �f d �°.(�eS x L 4() fir( Ph: ��7— 31 (pi Lic. No. 3 -i bC3 5 Sq.Ft. a( Bytldiag. Sq. F; ;of -ql ��p 1pt:� Height: No. of Ftao 6 Use of Bonding: 1r'."G.IL prA'tplc-7lit -14C. 7 _ Denc Work: ff SSS t 4soo 5-.-F. orr(CE &) Rii--1 1 to-troM5 tm- M zpiid6 Rao N\ 8 Class dr Work:'A. T it New o Alteien ❑ Remove T 63ortty\ r( A1'Sl*rn0 Addition 0 Move 9 10 Garage: o Single o Double Carport o Siegle o Doubk o Driveway Permit o On -Site Sewage Disposal o Site Plan (Septic) 11 Valuation of Wort:: SAdjusted «C�>0 Valuations: S C) -Ce CO. 12 Special Conditions: A SEPARATE ® BY THE ISSUED THISPERMIT BECOMES AUTHORIZED ISNOT CONSTRUCTION PERIOD OF IM I HEREBY CERTIFY APPLICATION AND PROVISIONS OF COMPLETED WITHIN GRANTING OF TO VIOLATE OR LOCAL LAW REGULATING OF CONSTRUCTION. ELECTRICAL STATE OF COLORADO. NULL COMMENCED OR WORK IS DAYS AT ANY THAT KNOW THE LAWS GOVERNING WHETHER A PERMIT DOES CANCEL THE NOTICE PERMIT IS REQUIRED AND MUST BE AND VOID IF WORK OR CONSTRUCTION WITHIN ISO DAYS, OR IF SUSPENDED OR ABANDONED FOR A TIME AFTER WORK IS COMMENCED. I HAVE READ AND EXAMINED THIS SAME TO BE TRUE AND CORRECT. ALL THIS TYPE OF WORK WILL BE SPECIFIED HEREIN OR NOT. THE NOT PRESUME TO GIVE AUTHORITY PROVISIONS OF ANY OTHER STATE OR CONSTRUCTION OR THE PERFORMANCE Plan Check Fee: (9�( t 013.58 Permit Fee: /559.35 Total Fee: Dated Permit Issued: ..°72.73 Oc/c Group: ConB e %11u d'��)/ c3,13 tp/l r it 4 I ..V�/�( Zoning: Setbacks: Manu. Home: /SDS No. &Fee: /N i�� R / : • 0 cfIf; fit AGREEMENT PERMISSION IS HEREBY GRANTED TO THE AP CANT AS OWNER CONTRACTOR AND/OR THE AGENT OF THE CONTRACTOR OR OWNER TO CONSTRUCT THE STRUCTURE AS DETAILED ON PLANS AND SPECIFICATIONS SUBMITTED TO AND REVIEWED BY THE BURRING DEPARTMENT. IN CONSIDERATION OF THE ISSSUANCE OF 11115 PERMIT, THE SIGNER_ HEREBY AGREES HI COMPLY WITH ALL BUILDING CODES AND LAND USE REGULATIONS ADOPTED BY GARFIELD COUNTY PURSUANT TO AUTHORITY GIVEN IN 3025201 CRS AS AMENDED. THE SIGNER FURTHER AGREES THAT IF THE ABOVE SAID ORDINANCES ARE NOT FULLY COMPILED WIT El IN THE LCOATION, ERECTION, CONSTRUCTION, AND USE OF THE ABOVE DESCRIBED STRUCTURE, THE PERMIT MAY BE REVOKED BY NOTICE FROM THE COUNTY AND THAT THEN AND THERE IT SHALL BECOME NULL AND VOID. THE ISSUANCE OF A PERSTE BASED UPON PLANS, SPECIFICATIONS AND OTHER DATA SHALL NOT PREVENT THE BURRING OFFICIAL FROM THEREAFTER REQUIRING THE CORRECTION OF ERRORS IN SAID PLANS, SPECIFICATIONS AND OTHER DATA OR FROM PREVENTING BUILDING OPERATION BEING CARRIED ON THEREUNDER WHEN IN VIOLATION OF THS CODE OR ANY OTHER ORDINANCE OR REGULATION OF THIS JURISDICTION. THE REVIEW OF SUBMITTED PLANS AND SPECIFICATIONS AND INSPECTIONS CONDUCTED THEREAFTER DOES NOT CONSTITUTE AN ACCEPTANCE OF ANY RESPONSIBILITIES OR LIABLITIES BY GARFIEID COUNTY FOR ERRORS OMISSIONS OR DISCREPENCIES. THE RESPONSIBILITY FOR THE57: ITEMS AND IMPLEMENTATION DURING CONSTRUCTION RESTS SPECIFICIALLY WITH THE ARITCTECT, DESIGNER, BUILDER AND OWNER. COMMENTS ARE INTENDED TO BE CONSERVATIVE AND IN SUPPORT OF THE OWNERS INTEREST. Gvfon.0B3 1 HEREBY ACKNOWLEDGE THAT 1 HAVE READ AND UNDERSTAND THE AGREEMENT ABOVE X0\40 { — 1013.5` FEE ESTIMATE 70(N&Q-\a-v-ki FINISHED LIVING SPACE: UNFINISHED DASEMENT: CRAWL SPACE: X 9.00 = X74.68= X 41.00 = GARAGE: X 18.00 = UNCOVERED PATIO/DECK: COVERED PATIO/DECK: X12.00 = X24.00 = misc. frflon71- -F/nusL j , MISC. TOTAL VALUATION: PLAN REVIEW FEE: (b /3, 57 PERMIT FEE: / SS9. N6 TOTAL: c 57a 9 MANUFACTURED NOME SET UP FEE: SEPTIC - PERMIT: PERK: I GARFIELD COUNTY BUILDING AND PLANNING 970-945-8212 MINIMUM APPLICATION REQUIREMENTS FOR CONSTRUCTION OF COMMERCIAL OR MULTI -FAMILY RESIDENTIAL BUILDINGS including NEW CONSTRUCTION ADDITIONS ALTERATIONS and MOVED BUILDINGS In order to understand the scope of the work intended under a permit application and expedite the issuance of a permit it is important that complete information be provided. Adequate and complete information will prevent delays in the plan review process. Reviewing a plan and the discovery that required information has not been provided by the applicant may result in the delay of the permit issuance and in proceeding with building construction. The owner or contractor may be required to provide this information before the plan review may proceed. This causes delays because other plans that are in line for review may be given attention before the new information may be reviewed after it has been provided to the Building Department. Please review this document to determine if you have enough information to design your project and provide adequate information to facilitate a plan review. If you do not, it may be helpful to obtain a book titled "Dwelling Construction Under the Uniform Building Code". This book is available to you through this department at our cost. Also, please consider using a design professional for assistance in your design and a construction professional for construction of your project. To provide for a more understandable plan in order to determine compliance with the f i Yes No 33. Do you understand that the Building Department will collect a "Plan Review" fee from you at the time of application and that you will be required to pay the "Permit" fee as well as any "Septic System" or "Road Impact" fees required, at the time you pick up your building permit? Yes i/ No_ 34. Are you aware that you are required to call for all inspections required under the Uniform Building Code including approval on a final inspection prior to receiving a Certificate of O pancy and occupancy of the building? Yes ✓ No 35. Are you aware that the Permit Application must be signed by the Owner or a written authority be given for an Agent and that the party responsible for the project must comply witty the Unfform Codes? Yes__ No____ 36. Are you aware that twenty-four (24) hour notice is required for all inspections? Inspections will be made from Battlement Mesa to West Glenwood in the mornings and from Glenwood Springs to Carbondale, in the afternoon. All inspections must be called in by 3:30 p.m. the day before. Failure to give twenty-four (24) hour notice for inspections will delay your inspection one (1) day. Inspections are to be called in to 384-5003. 37. Are you aware that requesting inspections on work that is not ready or not accessi le will result in a $47.00 re -inspection fee? Yes___ No 38. Are you aware that prior to issuance of a building permit you are required to show proof of a driveway access permit or obtain a statement from the Garfield County Road & Bridge Department stating one is not necessary? You can contact the Road & Bridge Department at 625-8601. 39. Do you understand that you will be required to hire a State of Colorado Licensed Electrician nd Plumber to perform installations and hookups? The license number will be re fired at time of inspection. YesNo 40. Are you aware, that on the front of the building permit application you will need to fill in the Parcel/ Schedule Number for the lot you are applying for this permit on prior 6 • to submittal of the building permit application? Your attention in this is appreciated. Yes V No I hereby acknowledge that I have read, understand, and answered these questions to the best of my ability. Signature Phone:110''"l7;1 ((�tlays Project Name: IE �{9-Nf<CciUt�? - ��t) P4 -Ar Date / Dfr �° '/' (evenings) �r Project Address: OD (PZ C \ l ' C .f o/Dl9z E C 31(o).3 Note: If you answered "No" on any of these questions you may be required to provide this information at the request of the Building Official prior to beginning the plan review process. Delays in issuing the permit are to be expected. Work may not proceed without the issuance of the permit. *If you have answered "Not necessary for this project" on any of the questions and it is determined by the Building Official that the information is necessary to review the application and plans to determine minimum compliance with the adopted codes, please expect the following: A. The application may be placed behind more recent applications for building permits in the review process and not reviewed until required information has been provided and the application rotates again to first position for review. 8. Delay in issuance of the permit. 7 07/14/2004 05:40 970-8760911 BAILEYS GARAGE DOORS Fir Doors R & S Fire Doors combine the durability, security, efficiency and space saving advantages of a roiling service door with the added life and property saving benefits of automatic fire prolecion. Underwriters Laboratories 3-Hour/Claas'A' !abet or Oversees Catlficsle of Compliance is furnished standard. (Refer to the Listing Summary below for conditions affecting approvals by vadotm testing agencies.. Acceptance of the listing for vaiiesone in wall aorretrudbn should be verified with the budding authority having )taisdlction.) Fire Doors are designed to close automatically from a fully open position — activation of the dosing dnvhce with the door in the down position may cause damage. Fre Doom are not designed for use in high cycle applications — a secondary nonrated door Is r000tn- mended In those situations, . Listing Summary PAGE 02 7N6ng Agency V tJtboraaeslea FactoryMutual (bias( File Number R-11680 R-6580 J.I. DTOHIAC Hourly Rating 3 Hour 114 Hour 3 Hour Wall Construction Masonry Drywall' or Masonry Masonry Jamb Type Com: ate Block Brick 16Ot. (mkt)'Sand Stud. Sled Tube, Wood Stud, Concrete, Block, Brick Concrete Block Brick Label Size 12' Wide 12 High 120 Sq. Ft Max 12' Wide 12' High 120 Sq- Ft Max. 12' Wide 12' High 120 Sq. Ft. Max. Oversize 24' Wide 24' High 576 Sq. Ft. Max. 24' Wide 24' HIgh 576 Sq. Ft. Max. 18' Wide 18' High 324 Sq. Ft. Max. Jambs must be continuous members from floor to structure above. Slmsand attachment of members is to be determined to provide adequate mounting and support for the size and weight of the door. Fail Safe Release Devices By Solid State Securities, Inc. Distributed By R & S Manufacturing, Inc. Standard feature on all Model SS90 release devices is en adjustable time delay of up to 30 seconds: Medd SSSFII• standard base model. Medal 8$91-8: standard base model with additions/ relay contacts Model SSnSe standard base model with additional relay contacts, and battery bade -up for power lost Madel SSW-: standard bass model with adddional relay contacts, bat - 4 WY hank -UP Mt flredoor down thea motor °perlost and m avoiding a logic memechanical release rd to electrically Ne OpWlsi Yale Beard: can be added to any model, allows a standard audio warning or an optional warning tailored to your specific needs. O10ary Sank -alt In Systema: to support a motor operator during a power failure. NOW for additional lnforma0on please consult factory. 11/22/2004 13:11 9204585620 • . 'RODUCT SPECIFICATIONS SHEBOYGANPAINTCO PAGE 81 Lee SHEBOYGAN PAINT COMPANY 1439 NORTH 25th STREET P.O. BOX 417 SHEBOYGAN, WI 53082-0417 DATE OF PREPARATION 05/25/04 PRINTED DATE 11/22/04 EMERGENCY TELEPHONE (920) 458-2157 CUSTOMER SERVICE custserv@shebpaint.com TRADE NAME PREMIUM WM GREEN AQUA ENAMEL CUSTOMER PART NUMBER WEIGHT PER GALLON (density) PERCENT SOLIDS PERCENT WATER PERCENT SOLVENT % EXEMPT SOLVENT VOC (WITH WATER AND EXEMPT SOLV): VOC (LESS WATER AND EXEMPT SOLV): MFG. PRODUCT NO. 73-5184F : Waste Mgnt-A11 • 9.43 POUNDS BY WEIGHT BY VOLUME 37.33 26.87 PERCENT HAPS BY WEIGHT VOC LBS PER GALLON SOLIDS• VOC KILOGRMS PER KILOGRMS SOLIDS: VOC HAPS LBS PER GALLON SOLIDS . VOC HAPS LBS PER LBS SOLIDS FLASHPOINT (FAHRENHEIT) APPLICATION REDUCTION CURE SUBSTRATE COVERAGE. VISC @ 80 F CRYPTOMETER GLOSS PA 50.14 56.73 12.25 16.05 .28 .35 1.15 LBS/GAL 137.81 2.69 LBS/GAL 322.37 7.36 4.28 .33 2.58 .20 : N/A SPRAY/ROLL/BRUSH : NONE -WATER IF NEEDED : AIR DRY : METAL : 430.995 SQUARE FEET @ 1 : 95-100 KU : 22-34#2 WEDGE 80-100®1 MIL, HIGH* : 8.5-9 COMMENTS ***Q.C.NOTE-pH AFFECTS VISCOSITY*** FLASH POINT NOT APPLICABLE DUE TO PRESENCE OF WATER GMS/LITER GMS/LITER MIL NO LOSS r 11/22/2004 13:11 9204585620 • SHEBOYGANPAINTCO PAGE 02 73-5184F PAGE: 1 MATERIAL SAFETY DATA SHEET FOR COATINGS, RESINS AND RELATED MATERIALS HAZARD RATING 0 - MINIMAL 3 - SERIOUS 1 - SLIGHT 4 - SEVERE 2 - MODERATE * - CHRONIC HMIS RATING HEALTH - * 2 FLAMMABILITY - 0 REACTIVITY - 0 SECTION I SHEBOYGAN PAINT COMPANY 1439 NORTH 25th STREET / P.O. BOX 417 SHEBOYGAN, WI 53082-0417 DATE OF PREPARATION 05/25/04 EMERGENCY TELEPHONE (920) 458-2157 EMAIL: cuetsery@shebpai.nt.com PRODUCT CLASS TRADE Mame SURFACE COATING PREMIUM NM GREEN AQUA ENAMEL MPG PRODUCT N0. 73'51641 SECTION II - HAZARDOUS INGREDIENTS ACGIH TLV ACGIE STEL OSHA PEL OSHA CEILING LEL % VAPOR PRESS % BY NT INGREDIENT CASE PPM mg/m2 PPM Ing/m.3 PPM mg/m3 PPM mg/m3 VOLUM nm/Ng DEG P W9ht Mf Glycol Ether Compd.(ekin) 111-76.2 20.00 100.050.00 240.0 1.100 0.600 • 69. 7.27 A Secondary Butyl Alcohol 70-92-2 100.0 300.0 150.0 450.0 1.700 12.50 • 63. 4.59 C Ammonia 7664-41.7 25.00 37.00 15.00 24.00 50.00 35.00 16.00 6460. 0 60. 0.29 MON-HAZARDOUS COMPONENT: Nater 7732-16-5 0 --- 50.1 C.I. Pigment Green *7 1326-53.6 10.00 15.00 s --- Iron (III) Oxide (duet) 51274.00.1 5.000 10.00 a --- Barium Compound (Insoluble) 7727.43-710.00 5.000 Y --- 10.1 NI -This chemical 1s eubjeet to reporting proccdurea outlined in the NS.CODein Department Of Natural Resource', Administrative Cods Chapter NR44S. A -This toxic chemical is subject to the reporting requirements of Election 311 of the Emergency Planning and Community Right -to -Know Act of 1986 (40073721. VNAP s VOLATILE HAZARDOUS AIR POLLUTANT C -Thin toxic ebomitel i0 subject to the reporting requirements of both 'action 313 of the Emergency Planning and COnitnity Right -to -Know Act Of 19E6 (40CPR372) and the Wisconsin Dept. of Natural Resources Adminietrativs Code Chapter NR445. REAP • VOLATILE HAZARDOUS AIR POLLUTANT (akin) • OSHA Skin Absorption Hasard SECTION III - PHYSICAL DATA BOILING RANGE 211-490 F VOC RG/KG SOLIDSa.13 VOC (WITH WATER AND EXEMPT SOLV1 - 1.18 LES/GAL % HAPS H7 WEIGHT-. 7.36 VAPOR DENSITY EVAPORATION RATE VAPOR D5tSITY NGvIER THAN AIR EVAPORATION RATE SLOWER THAN ETHER VOC (LEES WATER AND EXEMPT SOLV) - 2.69 LBS/GAL 136 GM5/LITER 322 CMS/LITER %VOLATILE %VOLATILE MIGHT SPECIFIC AVO SOLV BY WEIGHT EY VOLUME PER GALLON GRAVITY DENSITY 62.67 73.13 9.4295 1.132 3.03 SECTION IV - FIRE & EXPLOSION HAZARDS PROPER SHIPPING NAME - WATER EASED PRODUCT, DOES NOT SUSTAIN CONEUSrION NONCOMBUSTIBLE (ASTM D4206) SNIPPING LABEL - KEEP SROM pea-Ex/00 LABEL FLASHPOINT N/A SRTfNGUIEXIMC MEDIA, Water based product. Plachpoint for thio product 3.a SLpte4 •p N/A or Rot Applicable due to the prcacaee of water. If water has boiled off, Chill product may exhibit properties of a Class II, IIIA, or IISA liquid. needed, extingu&phing agent! for Clam! a firms my be timed, If 14/22/2004 13:11 9204585620 9-EBOYGANPAINTCO PAGE 03 • 73-5184F PAGE: 2 UNUSUAL Fine & Rx!LOSION HAZARDS, Water based product. Sealed containers may explode if exposed to extreme hent. Preece containers may expand and leak coatente when thawed. Neter soluble Liquide ere non -accumulators of static charge. Static protection preceut.ionn Ruch an container bonding or grounding would not be necessary. Plash point Listed as N/A or not applicable due to the presence of water. Reference NPCA "Evaluation of the rite Hazard of water -Borne Coatings" SPECIAL FIRS FIGHTING PROCSoUISS: Water may be used to cool cloned containers to prevent pressure buildup. Keep people away from any Eire fighting operations invOlving chemicals. Near s self-contained positive pressure breathing apparatus in addition to full protective gear. SECTION V - HEALTH HAZARD EFFECTS OF OVEREXPO9USE: Irritation of the reepiratory tract or acute nervous system depression characterized by headache dizziness, staggered gait, conruelon, unconaciousneee, cora. There is no applicable information available regarding the carcinogen potential for this product an a whole, however any relevant information regarding any ingredient's status as a potential. eunpect, or confirmed carcinogen is lfetnd in SECTION V of the MEDS. Chronic overexposure may damage the liver and/or kidneys, blood cells, cause cardiac sensations', hearing effects, and/or cause birth or fertility defects in lab animals. Repeated and prolonged exposure to some lolvent. has been associated with permanent brain and nervous system damage. Intentional misuse by deliberately concentrating a inhaling vapors from thin product may be harmful or fatal. Chronic ovelexposure may cause blood disorders. This product contain. a glycol ether compound which is on the Pcnnnlyvania Right -to -Know List. Chemical Name: ethanol, 2 -botany- CAS, 111-76-2. Chronic overexpoeure may cause damage co the liver, kidney, eyes, and/or respiratory system. Prolonged and continuous exposure to excessive concentration of duet of any kind without (Laing a duet mask may have an adverse pulmonary effect on some people. Thie overexposure may result in coughing, sputum, and reduced lung capacity. Pre-existing asthmatic conditions may woreen. persona with lung diocese(' should not work in dusty areae unless a phyeirian certifies their fitness to wear a respirator. (OSHA 1910,134). Liquid paint does not readily release duet. This product contains Pigment Green 07 which is currently listed by OSHA and ACGIH as a nuisance dual particle. Exposure Limits For Inert and Suirance Dust Particulate' Not Otherwise Claesitied: OSHA (FEL). TVA .15 mg/m3 (total duet) 5 mg/m3 (reepirable fraction). ACGIR(TLV): TWA a 10 mg/m3 (total duet). This product contains a copper compound. C.I.Pigment Slue 1E CAS, 147-14-8; C.I.Pignont Green 7 CASA 1124.53-6) and C.I. Pigment Green 34 CA5114302-13-7 RRE EXEMPT PROM REPORTING REQUIREMENTS UNORR THE CATAGORY 'COPPER COMPOUND9" from the list of toxic chemical. under section 113, EPCRA, Exposure Limits For Iron Oxide (fume): (CASA 1309-37.1) OSHA (PEI): TWA .10 mg/m3 (as total particulates) ACGIH(TLV): TWA e 5 mg/m3. This product contoinn Iron Oxide, which is currently listed by OSHA a ACGIE as a fume hazard. Overexposure results in a nuisance duet type hazards to the eyes, ears & nose. Injury to the akin or mucous membranae can occur by rigorous .kin cleaning or direct mechanical action for removal of dust. Prolonged overexposure without proper respiratory protection may cause ■iderosie, a benign pncumsoonioeia that produces no adverse health effect,. This product contain. Barium Sulfate, which is listed by OSHA and ACGTH .s a nuisance dust. Long term overexposure to barium euirate duet may produce benign Pneumoconiosis termed "boritenia" end may reduce lung function. This product contains Calcium Carbonate, which is listed by OSHA and ACGIR as a nuisance duet hazard. Excessive exposure result. in irritation to eye., earn. noon. Injury to akin or mucous membranes can occur by direct mechanical action or by rigoroun akin cleaning for removal of dirt. This product contains Crystalline Silica !Quartz). Prolonged overexposure to respirable silica dust may Coude eilicoaia, A non -cancerous lung di- . Cryetalline silica is also considered a probable carcinogen by IARC and a, a reasonable anticipated human carcinogen by NTP. Silicosis is made worse by Smoking. Exposure Limits For Barium Sulfate, (CAS, 7727-41-7) OSHA (PELI: TWA 1.10 mg/m3 (total dust). 5 mg/m3 (respirable) ACGINITLVI. TWA -10 mg/m3 (total duct(. Exposure Limits For Calcium Carbonate: ICAS4 1337-65-31 OSHA (PEL)1 TWA e15mg/m3 (total duet), Sag/ttl (respirable) ACGIH(TLV)t TWA '10mg/m3 (total dust). expomere Limit.. For Silica -Crystalline. (Cage 14008-60-7) (Quartz) 09HA (PELI: TWA a 0.1 mg/m3 (as respirable duet( ACGIHITLV)i TWA a 0.1 mg/m3 (as respirable traction). MEDICAL CONblttONI PROW! TO AOGRAVATION BY EXPOSURE: Preexisting eye, akin. central nervous system, dtgeetivc tract, and respiratory tract. May adversely affect germane with liver, kidney 6 blood terming organ disorders. ROrrrt(g) OF ENTRY. Inhalation, akin contact absorption, eye contact. Products that are free-flowing liquids or p,eten are not expected to have routes of exposure for dust. Dried product rneidue may exhibit dust inhalation hazards. IRIALATION: May cease moderate irritation to the respiratory tract. Overexposure may have toxic and/cr narcotic effects. May cause congestion, headache, diszinese, weaken., naunea, and/or drowsiness. FIRST AID: Remove ea fresh air. If flatting Si difficult, give oxygen. 1! not breathing, give artificial respiration and get emergency medical esoietance. XYZ CONTACT: Liquids or vapors may cause severe Irritation and/or chemical burns to the eye.. Chronic overexposure may cause eye damage, conjunctiva or corneal injury. FIRST AID; Immediately flush eyes and eyelids with large amounts of water for 1S min. Hold eyelids apart t0 ensure flushing of the entire area. Get prompt medical attention. 11/22/2004 13:11 9204585620 SHEBOYGANPAINTCO PAGE 04 73-5184F PAGE: 3 SkIN CONTACT: May elute moderate to severe akin irritation. May cause burning sensations, defecting and/or dermatitis. Chronic overexposure MAY cave* akin crocking end/or eczema, FIRST AID: Remove contaminated clothing and ahoea. Naafi .arca with Beep and water. Get medical attention a9 needed. SKIN ABSORPTIOIP: May be absorbed through akin tiesuce. Chronic overexposure to the akin without using protective barriers (glove', Aprons, etc.) may cause toxic effects, INGESTION, Single dose oral toxicity is Low. May cause irritation to the gaetroiateetlnal tract. Ingestion may cause nausea, discomfort, diarrhea, dizziness and vomiting. FEAST AID: DO NOT INDUCE vOMITINGI Contents of this product pose an inhalation hazard. If aspirated into the lunge, may rause cbemtcal pneumonitle and/or pulmonary edema which can be fatal. Never leave individual unattended, keep head low to prevent aspiration. BEEK IMMEDIATE MEDICAL ATTRNTIONI SECTION VI - REACTIVITY DATA STABILITY: UNSTABLE KK_STABLB INCOMPATAIILITY (Materials to avoid)! Keep away from all oxidizing materials. avoid strong acids a alkalis (cauttSce) and never distill solvents to dryness. Material can react violently under such conditions. MAZARDOUS DECOMPOSITION PRODUCTS. Oxides of carbon, nitrogen and/or sulfur & other toxic gases and irritating vapor, like aldehydes, amines, HCN,and incompletely burned hydrocarbons. HAZARDOUS POLYMERIZATION: May Occur Kx_Nill Not Occur CONDITIONS TO AVO!D, Container is not a pressure vessel. Do not stack pails mare than S high. KEEP FROM PREEZING! SECTION VII - SPILL OR LEAK PROCEDURES STEPS TO BE TAW IN CASE MATERIAL IS RELEASED OR SPILLED. bike apillad area and collect with inert absorbent material. If in a confined area. avoid breathing vapors and vee a respiratory protection device (See Section VIII). Follow local, state and federal epill notification procedures. WASTE DISPOSAL: Consult licensed waete bundling and/or transportation facility. Follow local, state and federal waste regulations. Do not incorporate into municipal sewage treatment !militia'''. Empty containers retain product residue, follow label and MSDS warnings even after container is emptied. SECTION VIII - SAFE HANDLING & USE INFO RESPIRATORY PROTECTION, In outdoor or open areae with unrestricted ventilation, if needed. use NIOSE approved duet mask to protect from overapray airborne particulate,. In restricted erten, use NIOSK approved combination organic vapor/ammonia respirator with dust particulate pre -filter. In confined areae, use an airline type respirator hood or self contained breatning apparatus. Consult the OSHA confined apace regulations. VENTILATION: Provide sufficient ventilation to keep duet/ airborne particulate and organic vapor concentrations below OSHA peraanal expoaun, limits (SEW. Remove all remake, dust, or fumee formed by welding, flame cutting, sanding or grinding surfacer' coated with this material. Provide proper respiratory protection if ventilation or exhaust is inadequate. SKIN PROTECTION REQUIREMENTS. Chemical rssietant glovos'are recommended. Use neoprene, nitrile. or butyl rubber. Cover on much of the exposed akin an po1eihle with appropriate impervious clothing. If skin erotism are used, keep the area protected by the cream to a minimum. Do not use skin creams to protect akin when working with acids or acid eotalyats. WYE PRQTECTIOMI Eyn protection ahnuld be worn in any type of industrial operation. The use of chemical goggles and a full face shield Co prevent splash from liquids is recommended, Contact lenses should not be worn. OTHER PROTECfIVB EQUIPMENT: Using a suit or spree to prevent contamination of clothing is recommended. Prevent prolonged skin contact with contaminated clothing. Remove and wash ell contaminated clothing before re -use. Never wear contaminated clothes' or Rhode away from the workplace. Use an industrial type professional cleaning service, do not Weigh et home. HYGIENIC PRACTICES: Emergency eye wash 'stations Ind 9atety showers are recommended. Nash hands prior to eating, using the washroom or smoking. Precautions must be taken 90 that person, handling this product do not breathe the vapors or bays it contact the akin or note. In 'pray operation*, protection must be afforded against exposure to both vapor and spray mint. SECTION IX - SPECIAL PRECAUTIONS PRECAUTIONS TO BE TAKEN IN HANDLING AND STORAGE: Follow safe warehousing procedure,. Avoid puncturing the cantainat. Race containers away from excessive heat. KERP FROM PRESSSNGI OTT(ER PKSCaittONS. Maintain a clean work area. Coe only in a well ventilated area. VHAP-Volatile Hatardou9 Air Pollutant CAUTION, DO NOT TAKE INTERNALLY. Avoid breathing vapor/dust. WARNING! This product contain, chemicalo known to the State of CaiLfornia to cause cancer or reproductive harm. 13/72/2004 13:11 9204585620 SHEBOYGANPAINTCO PAGE 05 73-5184F PAGE: 4 NOTICE, The HMIS rating for this material involves data and interpretations compiled from the various material suppliers of the cemponnnt ingredients. Thin information Will vary from supplier to supplier. The rating in intended for rapid and general identification of this product's hazard'. To adequately deal with the safe handling of this material, ell information contained In the MSog must he rnviewed an part of an ongoing Hazard Communication Program. Thi' product complier' with the Toxic Substances Control Act (TSCAI 40 en 700-799. The Material Safety Data Sheet (MEDS) complied with 29 CPR 1910.1200. Hazardous communication Std. In thn event of a TRANSPORTATION RFLATSb INCIDENT involving this product. CALL 1-B00-5BB-1D05. Avoid prolonged contact between this produce and ride, @Liver, copper, braes, aluminum and any alkali metal alloys. (for example, pumps, yips', 'pray gunn, storage Containers) OrPO , 414 S NlatikTa Sntr mime.% Leos ' Gafield County Building and Planning 108 8th Street Ste 201 Glenwood Springs, Colorado 970-945-8212 Plan analysis based on the 1997 Uniform Building Code Project Number: Project Name: Address: Occupancy: S3,S1,B-H4,F1 Construction: V-N:V-N Date: February 17, 2005 Contractor: Rudd Architect: Guy Engineer: Report By: A. Schwaller NOTE: The code items listed in this report are not complete listing of all possible code requirements It is a guide to selected sections of the code. intended to be a in the 1997 UBC. SECTION # 1 -Office, 2nd story storage SEPARATION DIRECTION BOUNDARY AREA INCREASE NORTH Property line 25.0 Feet EAST Property line 80.0 Feet SOUTH Property line 60.0 Feet WEST Property line 60.0 Feet Allowable area increased 100.% for ope -- Sec. 505.1 FL NAME OCC and truck repair. FIRE PROTECTION 25.0 Feet 80.0 Feet 60.0 Feet 60.0 Feet n area on 3 sides. MAX FLR AREA ALLOWED RATIO STATUS 2 Storage TOTAL FOR FLOOR 1 Office 1 Repair Garage TOTAL FOR FLOOR BUILDING TOTAL -- Sec. 504 and Table 5-B 31 ok B ok S3 ok 4470 4470 4470 11526 15996 20466 16000 0.28 ok 16000 0.28 ok 16000 0.28 ok 16000 0.72 ok 16000 1.0 ok 32000 0.64 ok i Code review for: Project Id.: Address: The actual height Page # 2 of this building is 25. feet. OTHER ELEMENT Interior Bearing wall Interior nonbrg wall Structural Frame Exterior Struct Frame Shaft Enclosure Floor/Ceiling Assembly Roof/Ceiling Assembly Stairs BUILDING ELEMENTS Table 6-A MATERIAL RATING Any Any Any Any Any Any Any Any 0 hr 0 hr 0 hr 0 hr 1 hr 0 hr 0 hr None NOTES See footnote #1 See Footnote #9 NOTE: See Section 711 for shaft enclosure exceptions. FOOTNOTES: 1) Elements in an exterior wall located where openings are not permitted or where protection of openings is required, shall be protected against external fire exposure as required for exterior bearing walls or the structural frame, whichever is greater. -- Table 6-A, footnote 1 9) In areas with vehicles or airplanes, the floor shall be of noncombustible, nonabsorbent materials. -- Sec. 307.2.2 Page # 3 Code review for: Project Id.: Address: PENETRATIONS OF FIRERESISTIVE ASSEMBLIES WALLS ASSEMBLIES -- Sec. 709.6 Through penetrations: 1) Penetrations shall be installed as tested in the rated assembly. -- Sec. 709.6.2 2) Penetrations shall be protected by an approved penetration firestop system and shall have an F rating of not less than the required rating of the wall penetrated. -- Sec. 709.6.3 Exception: When penetrating items are steel, ferrous or copper pipes or steel conduits and the wall is concrete or masonry, the annular space shall be permitted to be grout or mortar. The minimum thickness is the thickness required to maintain the fire rating. The maximum size of the penetrating items is equivalent to a 6 -inch diameter and the opening is a maximum of 144 square inches. -- Sec. 709.6.1 Membrane penetrations: The requirements are the same as for through penetrations. -- Sec. 709.7 Exceptions: 1. Steel electrical outlet boxes that do not exceed 16 square inches provided that the area of such openings does not exceed 100 square inches for any 100 square feet of wall area. Boxes on opposite sides of the assembly shall be separated by a horizontal distance of not less than 24 inches. 2. Sprinklers with metal escutcheon plates. Noncombustible penetrating items shall not be connected to combustible materials on both sides of the membrane unless it can be confirmed that the fire -resistive integrity of wall is maintained. -- Sec. 709.7 Page # 4 Code review for: Project Id.: Address: SMOKE and FIRE DAMPERS -- Sec. 713.10 and 713.11 Dampers shall be accessible for inspection and servicing: 1. Penetrations through area separation walls. Penetrations through occupancy separations. 2. Penetrations of the fire -resistive construction of horizontal exit walls or corridors serving as a means of egress. Exception: Openings for steel ducts penetrating the required fire -resistive construction of corridors are not required to have smoke dampers when such ducts are of not less than 0.019 -inch thickness (26 gage) and have no openings serving the corridor. 3. Penetrations of shaft enclosures. Exceptions: 1. Duct penetrations by steel exhaust air subducts extending vertically upward at least 22 inches above the top of the opening in a vented shaft where the airflow is upward. 2. Penetrations of a fire -resistive floor forming the base of a shaft enclosure may be protected by fire dampers listed for installation in the horizontal position. 3. Smoke dampers are not required when shaft is exhaust only, and is used for continuously operating fans. 4. Penetrations of the ceiling of fire -resistive floor -ceiling or roof -ceiling assemblies. Exception: Smoke dampers are not required. 5. Penetrations of an atrium enclosure element. Exception: Smoke dampers are not required. 6. Penetrations of exterior walls where protection of openings is required. Exception: Smoke dampers are not required. 7. Penetrations of areas of refuge. Exception: Ventilation system designed to supply outside air during an emergency. 8. Smoke dampers are required in smoke barriers and elevator lobbies. Code review for: Project Id.: Address: DRAFT STOPS: If there is combustible construction stops shall be installed so that the exceed 1,000 square feet and so that Page # 5 in the floor/ceiling assembly, draft area of concealed space does not the horizontal dimension between stops does not exceed 60 feet. -- Sec. 708.3.1.1.3 If there is combustible construction in the roof/ceiling assembly, draft stops shall be installed so that the area of concealed space does not exceed 3,000 square feet and so that the horizontal dimension between stops does not exceed 60 feet. -- Sec. 708.3.1.2.2 OCCUPANCY SEPARATIONS -- Table 3-B S3 -S1 lhr S3 -B lhr A customer waiting room not exceeding 450 sq.ft. with an exit to the exterior is not required to be separated. -- Sec. 302.1 exc. 2.5 S1 -B Ohr HEATING EQUIPMENT SEPARATION: FOR S3 OCCUPANCY: A 1 hr. occupancy separation is required around boiler or central heating unit greater than 400, - - Sec. 302.5 FOR S1 OCCUPANCY: A 1 hr. occupancy separation is required around boiler or central heating unit greater than 400, - - Sec. 302.5 FOR B OCCUPANCY: A 1 hr. occupancy separation is required around boiler or central heating unit greater than 400, - - Sec. 302.5 SECTION # 1 EXIT REQUIREMENTS: FL NAME rooms containing a 000 BTU input. rooms containing a 000 BTU input. rooms containing a 000 BTU input. NUMB MIN MIN PANIC HALLWAY/ DOOR NOTES OCC EXITS WIDTH HDWR CORRIDOR SWING 2 Storage TOTAL 1 Office 1 Repair Garage TOTAL 45 2 9.0 No 45 2 13.5 No 45 58 103 2 2 2 9.0 11.6 20.6 No No No N/A N/A N/A N/A N/A N/R N/R N/R Out Out Page # 6 Code review for: Project Id.: Address: In areas where 2 exits are required, the minimum separation is 1/2 of the maximum diagonal of the area or floor. -- Sec. 1004.2.4 When 2 exits are required, exits must be arranged so that it is possible to go in either direction from any point in a corridor or hallway to a separate exit, except for dead ends not exceeding 20 feet in length. - - Sec. 1004.2.6 Exit signs are required from all areas where 2 or exits are required. - - Sec. 1003.2.8.2, Exception 2 No point to be more than 100 feet from an exit sign. Main exterior exit doors which obviously and clearly are identifiable as exits need not be signed when approved. -- Sec. 1003.2.8.2, Exception 1 Door swing is based on Sec. 1003.3.1.5 except as noted. Occupant load factor is based on Table 10-A. Number of exits is based on Table 10-A except as noted. Exit width is in inches and based on Sec. 1003.2.3 and Table 10-B Exit width is to be divided approximately equally among exits. - - Sec. 1003.2.3.2 Width shown for all areas is based on other egress components. Width shown for 1st floor is based on other egress components. Width shown for other floors & basements is based on stairways. - - Table 10-B For the minimum width of doors, see Sec. 1003.3.1.3 For the minimum width of hallways, see Sec. 1004.3.3.2 For the minimum width of corridors, see Sec. 1004.3.4.2 For the minimum width of stairways, see Sec. 1003.3.3.2 FOOTNOTES: FLUSH AND SURFACE BOLTS: Manually operated edge- or surface -mounted flush bolts and surface bolts or any other type of device that may be used to close or restrain the the door other than by operation of the locking device shall not be used. When automatic flush bolts are used, the door leaf having the automatic flush bolt shall not have a door knob or surface -mounted hardware. The unlatching of any leaf shall not require more than one operation. -- Sec. 1003.3.1.8 Page # 7 Code review for: Project Id.: Address: LOCKS AND LATCHES: Regardless of the occupant load served, exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. -- Sec. 1003.3.1.8 Key -locking hardware may be used on the main exit when the main exit consists of a single door or pair of doors if there is a sign stating THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS. When unlocked, door(s) must swing without operation of any latching device. -- exc. LANDINGS AT DOORS: 1) A floor or landing shall be provided on each side of doors. When access for persons with disabilities is required. the floor or landing shall not be more than 1/2 inch lower than the threshold. When access is not required, the maximum is 1 inch. -- Sec. 1003.3.1.6 2) Landings shall have a width not less than the width of the stairway or width of the doorway, whichever is the greater. Where a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing dimension to less than one half it required width. The minimum length in the direction of exit travel is 44 inches. -- Sec. 1003.3.1.7 TRAVEL DISTANCE: (distance to an exit) The maximum travel distance in this building is 200 feet. -- Sec. 1004.2.5.2 Travel distance shall not be limited within an exit enclosure or exit passageway. -- Sec. 1005.2.2 Page # 8 Code review for: Project Id.: Address: BUILDING ACCESSIBILITY: 1) This building including each tenant shall be provided with at least one entrance which complies with the accessible route provisions of CABO/ANSI A117.1. At least 50 percent of all entrances shall be accessible. -- Sec. 1103.2.3 2) When more that one exit is required from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress. -- Sec. 1104.1.1 3) When an exit stairway is part of an accessible means of egress, the stairway shall have a clear width of not less than 48 inches between the handrails. The stairway shall either incorporate an area of refuge within an enlarged story -level landing or shall be accessed from an area of refuge. -- Sec. 1104.1.2 The area of refuge shall have direct access to the stairway that serves it. -- Sec. 1104.2.1 4) Each area of refuge shall be sized to accommodate one wheelchair space not less than 30 inches by 48 inches for each 200 occupants, or portion thereof. -- Sec. 1104.2.3 5) If the area of refuge is not within the stairway, it shall be separated from the rest of the story by a smoke barrier having at least a one- hour fire -resistance rating. Smoke barriers shall extend to the roof or floor deck above. Doors shall be smoke and draft control assemblies with a rating not less than 20 minutes. -- Sec. 1104.2.4 6) Two-way communications are required. -- Sec. 1104.2.5 7) Each area must be identified by a sign stating AREA OF REFUGE and the international symbol of accessibility. -- Sec. 1104.2.7 8) NOTE: Exit stairways in buildings protected throughout by an approved automatic sprinkler system are NOT required to incorporate an area of refuge. -- Sec. 1104.1.2, Exception 2 Page # 9 Code review for: Project Id.: Address: AREA SEPARATION WALL REQUIREMENTS: 1) The area separation wall is required to be a 2 hr fire assembly. Openings are limited to 25 percent of the length of the wall and protected with a 1 1/2 hour assembly. -- Sec. 504.6.2 2) If the building has a projection, 1 hr. protection is required on the exterior wall each side of the area separation wall equal to the depth of the projection.-- Sec. 504.6.3, exceptions If the projection has a concealed space at the area separation, wall, the area separation wall must extend through the projection. 3) If the area separation wall terminates at an inside corner, see the article in 'Building Standards' Sep/Oct 1982 for requirements. 4) A 30 inch high parapet wall is required above the roofing. Sec.504.6.4 See exceptions for alternate protection at roof. The faces shall be noncombustible for the uppermost 18 inches including counterflashing and coping materials. -- Sec. 504.6.5 VENTILATION: All areas customarily occupied by humans shall be provided with natural ventilation by means of openable exterior openings with an area of not less than 1/20 of the total floor area or shall be provided with a mechanically operated ventilation system. Such system shall be capable of supplying a minimum of 15 cubic feet per minute of outside air per occupant. -- Sec. 1202.2.1 WALL AND CEILING FINISH: 1) Wall and ceiling finish materials are required to comply with Sec. 804.1 and Table 8-B. 2) Carpeting on the ceiling is required to have a Class I flame spread rating. -- Sec. 804.2 3) Textile wall coverings shall have Class I flame spread rating. and shall be protected by automatic sprinklers or meet the acceptance criteria of U.B.C. Standard No. 8-2 -- Sec. 805 4) Toilet room floors shall have a smooth, hard nonabsorbent surface that extends upward onto the walls at least 5 inches. - - Sec. 807.1.1 5) Walls within 2 feet of the front and sides of urinals and water closets shall have a smooth, hard nonabsorbent surface. - - Sec. 807.1.2 Page # 10 Code review for: Project Id.: Address: INSULATION NOTES: 1) All insulation material including facings are required to have a flame -spread rating of 25 or less and a maximum smoke density of 450 unless it is in a concealed space and the facing is in contact with a wall or ceiling. -- Sec. 707.3 exc.2 2) Foam plastic insulations are required to be protected. -- Sec. 2602 ACCESSIBLE FACILITIES: NOTE: Except as noted, section numbers listed below are from CABO/ANSI A117.1 - 1992 WATER FOUNTAINS AND WATER COOLERS: At least 50 percent of drinking fountains, but not less than one, provided on every floor shall be accessible. -- UBC Sec 1105.4.1 Accessible units must comply with the following: 1) Spout is to be within 36 inches of the floor. -- Sec. 4.15.2.1 2) Spout arranged for parallel approach shall be located 3 inches maximum from the front edge. Spouts of cantilevered units with knee and toe clearances shall be located 15 inches minimum from the vertical support and 5 inches maximum from the front edge. - - Sec. 4.15.2.2 3) Spouts shall provide a flow of water 4 inches height minimum. - - Sec. 4.15.2.3 4) Operable parts shall be located at or near the front edge of the unit and shall comply with 4.25.4 -- Sec. 4.15.3 5) A cantilevered unit is required to extend 17 inches minimum from the vertical support. Clear knee space must provide a clear area of 8 inches in depth at 27 inches high and 11 inches at 9 inches minimum above the floor. -- Sec. 4.15.4.1 6) Forward approach units shall comply with 4.2. Units in alcoves shall comply with 4.2.4.4. Units not having the necessary knee and toe clearance or clear space under them shall comply with 4.2.4 and have a clear floor space that allows a person in a wheelchair to make a parallel approach. -- Sec. 4.15.4.2 Page # 11 Code review for: Project Id.: Address: TOILET FACILITIES: 1) A 60 inch diameter unobstructed turning space is required in the toilet room. -- Sec. 4.16.3, 4.2.3 & Fig. B4.2.3 2) Water closet shall be mounted adjacent to a side wall or partition. The distance from the side wall or partition to the centerline of the water closet shall be 18 in. Sec. 4.17.1 3) When the accessible water closet is not in a stall: The clear floor space shall be 48 in minimum in front of the water closet and 42 in from the center line of the water closet on the side not adjacent to the wall. -- Sec. 4.17.2 & Fig. B4.17.2 4) When the accessible water closet is in a stall: The stall shall be 60 in wide minimum and 56 in deep minimum for wall hung water closets and 59 in deep minimum for floor mounted water closets. -- Sec. 4.18.3.1 If the door swings into the stall, the required depth shall be increased by 36 inches minimum. -- Sec. 4.18.3.2 & Fig. B4.18.3.1 Page # 12 Code review for: Project Id.: Address: 5) The bars are to be 33 to 36 inches above the floor and shall be provided on the rear wall and on the side wall closest to the water closet. -- Sec. 4.24.2.2 & Figs. B4.17.3, B4.17.4 and B4.18.3.1 a) Side grab bar is required to start within 12 inches of the back wall and extend to 54 inches from the back wall. (The minimum length of the bar is 42 in) -- Sec. 4.17.4.1 & Figs. B4.17.3 and B4.18.3.1 b) The rear bar shall be 24 in long minimum, centered on the water closet. Where space permits, the bar shall be 36 in long minimum, with the additional length provided on the transfer side. -- Sec. 4.17.4.2 & Figs. B4.17.3, B4.17.4 and B4.18.3.1 6) The top of the seat on the water closet is required to be 17 to 19 inches above the floor. -- Sec. 4.17.3 & Fig. B4.17.3 7) Accessible urinals shall be of the stall type or wall hung with the rim at 17 inches maximum above the floor. -- Sec. 4.19.2 8) A clear area of 30 X 48 inches minimum is required in front of the urinal. Privacy shields shall not extend beyond the front edge of the urinal rim, unless they are 30 inches apart minimum. -- Sec. 4.19.3 9) Accessible lavatories shall be mounted with the rim 34 inches maximum above the floor and a clearance of 29 inches minimum from the floor to the bottom of the front edge of the apron. -- Sec. 4.20.2.1 & Fig. B4.20.3.1 10) It shall extend 17 inches minimum from the wall. The clear knee space shall be 8 inches in depth minimum at 27 inches minimum above the floor and 11 inches in depth minimum at 9 in minimum above the floor. The dip of the overflow shall be ignored when checking the clearances. -- Sec. 4.20.3.1 & Fig. B4.20.3.1 11) A clear floor space of 30 X 48 inches minimum shall be provided in front of the lavatory and shall extend 19 inches maximum under the lavatory. -- Sec. 4.20.3.2 & Fig. B4.20.3.2 12) Water supply and drain pipes under lavatories shall be insulated or otherwise treated to protect against contact. -- Sec. 4.20.4 13) The bottom of mirror is required to be within 38 inches of the floor. -- Sec. 4.16.6 & Fig. B4.20.3.1 SECTION # 2 -Welding shop and latex paint spraying booth Code review for: Project Id.: Address: SEPARATION DIRECTION BOUNDARY AREA INCREASE NORTH Property line 60.0 Feet EAST Property line 80.0 Feet SOUTH Property line 0.0 Feet WEST Property line 0.0 Feet Allowable area increased 50.% for open - - Sec. 505.1 FL NAME Page # 13 FIRE PROTECTION 60.0 Feet 80.0 Feet 0.0 Feet 0.0 Feet area on 2 sides. OCC MAX FLR AREA ALLOWED RATIO STATUS 1 Welding 1 Latex Paint Shop TOTAL FOR FLOOR BUILDING TOTAL - - Sec. 504 and Table 5-B H4 ok 1017 7650 0.13 F1 ok 930 12000 0.08 1947 9252 0.21 1947 9252 0.21 The actual height of this building is 25. feet. EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION Table 5-A NORTH For Bearing Occupancy Wall H4 0 hour F1 0 hour EAST For Bearing Occupancy Wall H4 0 hour F1 0 hour SOUTH For Bearing Occupancy Wall H4 4 hour F1 1 hour WEST For Bearing Occupancy Wall H4 4 hour F1 1 hour Non -Bearing Wall 0 hour 0 hour Non -Bearing Wall 0 hour 0 hour Opening Protection None None Opening Protection None None Construction Material Any Any Construction Material Any Any Non -Bearing Opening Construction Wall Protection Material 4 hour Not Allowed Any 1 hour Not Allowed Any Non -Bearing Opening Construction Wall Protection Material 4 hour Not Allowed Any 1 hour Not Allowed Any Exterior wall rating for H4. -- Sec. 503.4.7-2hr O.K. Parapet Required No No ok ok ok ok Parapet Required No No Parapet Required Yes Yes Parapet Required Yes Yes less than 2500sf Page # 14 Code review for: Project Id.: Address: None No fire protection requirements for openings. 3/4 hour Openings are to be protected with 3/4 hr fire assemblies. 50% of the area of the wall maximum. -- Table 5-A, Footnote 5 & Sec. 503.2.2 Maximum single window size is 84 sq.ft. with no dimension greater than 12 feet. -- Sec. 713.8 Not Allowed Openings are not permitted in this wall. Parapet If exceptions do not apply, exterior walls indicated require a parapet wall not less than 30 inches above the roofing. The parapet wall is required to have the same fire rating as the wall. The uppermost 18 inches shall have noncombustible faces including counterflashing and coping materials. -- Sec. 709.4.2 EXCEPTIONS: 1) When roof is a two-hour assembly. 2) When the roof is entirely of noncombuxtible material. 3) One-hour walls with one-hour fire -resistive roof construction per exception #5 4) Wall is not required to be fire -resistive and openings are not restricted. -- Indicated by 'No' above. See section 709.4.1 for details and additional exceptions. OTHER BUILDING ELEMENTS MATERIAL Any Any Any Any Any Any Any ELEMENT Interior Bearing wall Interior nonbrg wall Structural Frame Exterior Struct Frame Floor/Ceiling Assembly Roof/Ceiling Assembly Stairs Table 6-A RATING 0 hr 0 hr 0 hr 0 hr 0 hr 0 hr None NOTES See footnote #1 See Footnote #18 FOOTNOTES: 1) Elements in an exterior wall located where openings are not permitted or where protection of openings is required, shall be protected against external fire exposure as required for exterior bearing walls or the structural frame, whichever is greater. -- Table 6-A, footnote 1 18) In areas containing hazaradous materials, the floor shall be of noncombustible, liquid -tight construction. -- Sec. 307.2.2 Page # 15 Code review for: Project Id.: Address: PENETRATIONS OF FIRERESISTIVE ASSEMBLIES WALLS ASSEMBLIES -- Sec. 709.6 Through penetrations: 1) Penetrations shall be installed as tested in the rated assembly. -- Sec. 709.6.2 2) Penetrations shall be protected by an approved penetration firestop system and shall have an F rating of not less than the required rating of the wall penetrated. -- Sec. 709.6.3 Exception: When penetrating items are steel, ferrous or copper pipes or steel conduits and the wall is concrete or masonry, the annular space shall be permitted to be grout or mortar. The minimum thickness is the thickness required to maintain the fire rating. The maximum size of the penetrating items is equivalent to a 6 -inch diameter and the opening is a maximum of 144 square inches. -- Sec. 709.6.1 Membrane penetrations: The requirements are the same as for through penetrations. -- Sec. 709.7 Exceptions: 1. Steel electrical outlet boxes that do not exceed 16 square inches provided that the area of such openings does not exceed 100 square inches for any 100 square feet of wall area. Boxes on opposite sides of the assembly shall be separated by a horizontal distance of not less than 24 inches. 2. Sprinklers with metal escutcheon plates. Noncombustible penetrating items shall not be connected to combustible materials on both sides of the membrane unless it can be confirmed that the fire -resistive integrity of wall is maintained. -- Sec. 709.7 Page # 16 Code review for: Project Id.: Address: SMOKE and FIRE DAMPERS -- Sec. 713.10 and 713.11 Dampers shall be accessible for inspection and servicing: 1. Penetrations through area separation walls. Penetrations through occupancy separations. 2. Penetrations of the fire -resistive construction of horizontal exit walls or corridors serving as a means of egress. Exception: Openings for steel ducts penetrating the required fire -resistive construction of corridors are not required to have smoke dampers when such ducts are of not less than 0.019 -inch thickness (26 gage) and have no openings serving the corridor. 3. Penetrations of shaft enclosures. Exceptions: 1. Duct penetrations by steel exhaust air subducts extending vertically upward at least 22 inches above the top of the opening in a vented shaft where the airflow is upward. 2. Penetrations of a fire -resistive floor forming the base of a shaft enclosure may be protected by fire dampers listed for installation in the horizontal position. 3. Smoke dampers are not required when shaft is exhaust only, and is used for continuously operating fans. 4. Penetrations of the ceiling of fire -resistive floor -ceiling or roof -ceiling assemblies. Exception: Smoke dampers are not required. 5. Penetrations of an atrium enclosure element. Exception: Smoke dampers are not required. 6. Penetrations of exterior walls where protection of openings is required. Exception: Smoke dampers are not required. 7. Penetrations of areas of refuge. Exception: Ventilation system designed to supply outside air during an emergency. 8. Smoke dampers are required in smoke barriers and elevator lobbies. OCCUPANCY SEPARATIONS -- Table 3-B H4 -F1 lhr Code review for: Project Id.: Address: HEATING EQUIPMENT SEPARATION: FOR H4 OCCUPANCY: A 2hr occupancy separation is required around boiler or central FOR F1 OCCUPANCY: A 1 hr. occupancy boiler or central -- Sec. 302.5 SECTION # 2 EXIT REQUIREMENTS: FL NAME heating unit. -- Sec. 302.5 Page # 17 rooms containing a separation is required around rooms containing a heating unit greater than 400,000 BTU input. NUMB MIN MIN PANIC HALLWAY/ DOOR NOTES OCC EXITS WIDTH HDWR CORRIDOR SWING 1 Welding 1 Latex Paint Shop TOTAL 10 9 19 2 1 2 2.0 1.8 3.8 No No No N/A N/A N/A Out 8 N/R Out In areas where 2 exits are required, the minimum separation is 1/2 of the maximum diagonal of the area or floor. -- Sec. 1004.2.4 When 2 exits are required, exits must be arranged so that it is possible to go in either direction from any point in a corridor or hallway to a separate exit, except for dead ends not exceeding 20 feet in length. -- Sec. 1004.2.6 Page # 18 Code review for: Project Id.: Address: Exit signs are required from all areas where 2 or exits are required. - - Sec. 1003.2.8.2, Exception 2 No point to be more than 100 feet from an exit sign. Main exterior exit doors which obviously and clearly are identifiable as exits need not be signed when approved. -- Sec. 1003.2.8.2, Exception 1 Door swing is based on Sec. 1003.3.1.5 except as noted. Occupant load factor is based on Table 10-A. Number of exits is based on Table 10-A except as noted. Exit width is in inches and based on Sec. 1003.2.3 and Table 10-B Exit width is to be divided approximately equally among exits. - - Sec. 1003.2.3.2 Width shown for all areas is based on other egress components. Width shown for 1st floor is based on other egress components. Width shown for other floors & basements is based on stairways. - - Table 10-B For the minimum width of doors, see Sec. 1003.3.1.3 For the minimum width of hallways, see Sec. 1004.3.3.2 For the minimum width of corridors, see Sec. 1004.3.4.2 For the minimum width of stairways, see Sec. 1003.3.3.2 FOOTNOTES: 8) The number of exits is based on Sec. 1007.4.1 FLUSH AND SURFACE BOLTS: Manually operated edge- or surface -mounted flush bolts and surface bolts or any other type of device that may be used to close or restrain the the door other than by operation of the locking device shall not be used. When automatic flush bolts are used, the door leaf having the automatic flush bolt shall not have a door knob or surface -mounted hardware. The unlatching of any leaf shall not require more than one operation. -- Sec. 1003.3.1.8 LOCKS AND LATCHES: Regardless of the occupant load served, exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. -- Sec. 1003.3.1.8 Page # 19 Code review for: Project Id.: Address: LANDINGS AT DOORS: 1) A floor or landing shall be provided on each side of doors. When access for persons with disabilities is required. the floor or landing shall not be more than 1/2 inch lower than the threshold. When access is not required, the maximum is 1 inch. -- Sec. 1003.3.1.6 2) Landings shall have a width not less than the width of the stairway or width of the doorway, whichever is the greater. Where a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing dimension to less than one half it required width. The minimum length in the direction of exit travel is 44 inches. -- Sec. 1003.3.1.7 TRAVEL DISTANCE: (distance to an exit) The maximum travel distance in this building is 200 feet. Sec. 1004.2.5.2 Travel distance shall not be limited within an exit enclosure or exit passageway. -- Sec. 1005.2.2 VENTILATION: All areas customarily occupied by humans shall be provided with natural ventilation by means of openable exterior openings with an area of not less than 1/20 of the total floor area or shall be provided with a mechanically operated ventilation system. Such system shall be capable of supplying a minimum of 15 cubic feet per minute of outside air per occupant. -- Sec. 1202.2.1 INSULATION NOTES: 1) All insulation material including facings are required to have a flame -spread rating of 25 or less and a maximum smoke density of 450 unless it is in a concealed space and the facing is in contact with a wall or ceiling. -- Sec. 707.3 exc.2 2) Foam plastic insulations are required to be protected. Sec. 2602 Page # 20 Code review for: Project Id.: Address: GLAZING REQUIREMENTS All glazing in hazardous locations is required to be of safety glazing material. Sec. 2406.3 & 2406.4 Locations: 1) Glazing in ingress and egress doors except jalousies. 2) Glazing in fixed and sliding panels of sliding door assemblies and panels in swinging doors other than wardrobe doors. 3) Glazing in storm doors. 4) Glazing in all unframed swinging doors. 5) Glazing in doors and enclosures for hot tubs, whirlpools, saunas, steam rooms, bathtubs and showers. Glazing in any portion of a building wall enclosing these compartments where the bottom exposed edge of the glazing is less than 60 inches above a standing surface and drain inlet. 6) Glazing in fixed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24 -inch arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60 inches above the walking surface. 7) Glazing in an individual fixed or operable panel, other than those locations described in items 5 and 6 above, than meets all of the following conditions: A. Exposed area of an individual pane greater than 9 square feet. B. Exposed bottom edge less than 18 inches above the floor. C. Exposed top edge greater than 36 inches above the floor. D. One or more walking surfaces within 36 inches horizontally of the plane of the glazing. 8) Glazing in railings regardless of height above a walking surface. Included are structural baluster panels and nonstructural in -fill panels 9) Glazing in walls and fences used as the barrier for indoor and outdoor swimming pools and spas when the bottom edges is less than 60 inches above the pool side and the glazing is within 5 feet of the pool or spa water's edge. 10) Glazing in walls enclosing stairway landings or within 5 feet of then bottom and top of stairways where the bottom edge is less than 60 inches above the walking surface. • WAYNE RUDD 132 ParkAve. Basalt, CO 81621 970-927-9119 Fax 970-927402 Februaruy 10, 2005 Mr. Andrew Schwaller GARFIELD COUNTY BUILDING DEPARTMENT 108 8th St. - Suite 201 Glenwood Springs, CO 81601 Re: Tenant Finish at 0062 Cattle Creek Rd. Dear Andy: Per you letter dated December 7, 2004, I want to respond to your comments regarding the permit application for the property referenced above: 1. I will be happy to meet an inspector at the property at any time to verify the building location to the property lines as regards to allowable yard increases. 2. We concur that the Loft area is required to have 2 exists per Sec. 1004.2.3.2, and we will construct an additional stairway which will exit to the corridor on the North side of the building, per the enclosed plans. Regarding the existing stairway, section 1004.2.2 provides for an exception to the requirement that both exists directly access the outside or a corridor providing direct access to an exit. Exception 4 should apply to the existing stairway exit, as the stairway provides "...direct access through an adjoining room, which in turn provides access to an exit..." As this room has 9 direct exits, it appears this exit will comply as built. 3. Proper signage and safeguards will be in place in the Container Paint Area prior to the final inspection. 4. Regarding accessibility, we will remove the striker lock sets and put push plates and spring hinges on the entrance to the men's and women's locker rooms. Additionally, we will remove the second door to the front entrance to comply with the code. 5. Please see the revised plans for fire designs for occupancy separations and area separations. Thank you very much for your assistance in this project. Please feel free to contact me if you have any questions. oland Parker Project Manager cc: Bill Gavette, Carbondale Fire Department Herman Aardsma, Waste Management Garfield County BUILDING & PLANNING DEPARTMENT " T Roland Parker Rudd Construction 132 Park Ave. Basalt, CO 81621 December 15, 2004 Re: Tenant Finish at 0062 Cattle Creek Rd. Dear Roland, In follow up to your letter of December 7, 2004 we have the following comments: A site visit would be required to verify the available yard area increases. Based on the site plan submitted an area increase of 25% was figured into the initial allowable area increase. Assuming the loft area is a 2nd floor and a 100% increase in allowable area is correct, the building is code compliant with regards to area. We will need to verify yard sizes to substantiate the 100% increase. The Loft area is required to have 2 exits as per Sec. 1004.2.3.2. The required access to exits from this area will need to be directly to an exit or to a corridor that provides direct access to an exit. Please see the requirements for these exits as outlined in Sec 1004 of the 97 UBC and make the needed corrections to the plans. We concur with the proposed change in occupancy rating for the Container Paint Area. Proper signage and safe guards would need to be in place prior to the final inspection. Regarding accessibility, it would appear from the submitted drawings that the access to both the men's and women's locker rooms do not meet the requirements of Sec 4.13.6 Maneuvering Clearance at Doors of the CABO/ANSI A117.1-1992. This same section applies to the 2 doors in series at the front entrance which are not to code. Please submit the approved and tested fire designs for occupancy separations and area separation for the walls and floor assemblies involved. These involve the separations outlined in your letter and also the occupancy separations between the B occupancy and S occupancies. Also revised plans will need to be submitted to include all changes to the original set of drawings for the permit application. 108 8th Street, Suite 201, Glenwood Springs, Colorado 81601 (970) 945-8212 (970) 285-7972 Fax: (970) 384-3470 Thank you for your time with this matter. Feel free to contact us with any questions that you may have. Building Official rc itvS 111) WAYNE RUDD 132 Park Ave. Basalt, CO 81621 970-927-9119 Fax 927-4027 December 7, 2004 Mr. Andy Schwaller GARFIELD COUNTY BUILDING DEPARTMENT 108 8th St. - Suite 201 Glenwood Springs, CO 81601 Re: Tenant Finish - 0062 Cattle Creek Rd. Dear Andy: In response to your letter dated November 15, 2004, I would like to offer the following information. I am responding to your numbered comments in sequence. 1 & 2. It appears that you did not take into account the yard distances from the property lines, which would allow for area increases. Taking into account that all yards are in excess of 40 feet, the building is in compliance with the 100% area increases allowed. The total area of the B1 and S3 uses in the building is 15,996 Please note that the plan has an error on sheet A2.1 as the container paint area and welding bay are incorrectly labeled as to dimensions. The measurement of these areas as built is 38'6" X 50"6", or a total of 1,944 square feet. 3. The paint room should be classified as F-1, as the latex paint use (MSDS attached) is neither flammable nor combustible. This was the opinion we received after contacting the ICC and meeting with Bill Gavette. The latex paint is the only paint used in the building and signs posted in the area confirm this is the only product in use. We will place an additional layer of 5/8 drywall on each side of these areas creating a 2 -hour separation. The 10 X 10 overhead door has a 3 hour rating, spec sheet attached. We will replace the 1 hour walk door to the area with a 1 '/z hour door. 4. All doors meet the required occupancy separation. (when the door referenced above is installed) 5. Access to the building is compliant with the sections 1103 and 1104 as regards to the physically disabled. 6. Loft floor framing design is shown on page S2.2. 7. Since the spray room is classified F-1, an automatic fire extinguishing system is not required. 8. Addressed below in responses to letter from Bill Gavette. 9. The two exit doors to the outside in the welding bay (11-4) will be reversed to swing out, if necessary. Since the H-4 area is less than 1,000 square feet and there is one exit door that swings out into the spray mom, can we leave the other two doors (which are not required by code) swinging in? Below are the responses to Bill Gavette's letter dated November 5, 2004. 1. Floor areas are in compliance per 1&2 above. 2. Not applicable due to non flammable paint. 3. Not applicable, as spray area is F-1, not H-2. 4. A 2 -hour separation will be constructed between the F -1/H-4 and S-3 occupancies per response #3 above. 5. To the best of our knowledge, no hazardous material is stored in the building. 6. To the best of our knowledge, no flammable or combustible liquids are stored in the building. Spray Room (F-1) 1. No automatic fire extinguishing system required in F-1. 2. Ventilation system is in place ,sized at 7 air changes per hour. 3,4&5. Not applicable due to non flammable material. 6. Duct filters will be cleaned on a regular basis. 7. Although not required in F-1, all wiring and equipment in the spray room is explosion proof. 8. Portable fire extinguishers are provided in the area. 9. Not applicable as no flammable or combustible liquids stored in the room. Welding Bay (1-1-4) 1. Ventilation is in compliance with UBC 1202.2.3 (1,600 cfm exhaust fan and hood system) 2. Compressed gasses will be handled in accordance UFC Article 74. Thank you in advance for your assistance in this project Please feel to contact me if you have any questions. Project and Property Manager cc: Bill Gavette, Carbondale Fire District Herman Aardsma, Waste Management f I t e, Garfield County BUILDING & PLANNING DEPARTMENT Mr. Wayne Rudd Rudd Construction 132 Park Ave. Basalt, CO 81621 November 15, 2004 Re: Tenant Finish Permit Application 0062 Cattle Creek Dear Mr. Rudd: With the plan review process, the following code deficiencies have been determined. Please see attached print out and referenced code sections. I tried to adjust the type of construction to see if greater allowable areas for mixed use occupancy could be obtained. Regardless of type V -N or type II -N, the areas were over what is allowed. Other changes to the design are required. Also included with this letter are the requirements received from the Carbondale Fire Districts review. Their requirements will be included as conditions to the permit. Please call if you have any questions. Yours truly, Andrew Schwaller Building Official 108 8th Street, Suite 201, Glenwood Springs, Colorado 81601 /970) 945-8212 (970) 285-7972 Fax. 1970)384-3470 f f Gafield County Building and Planning 108 8th Street Ste 201 Glenwood Springs, Colorado 970-945-8212 Plan analysis based on the 1997 Uniform Building Code Project Number: Project Name: Rudd Tenent finish Address: Occupancy: S3,S1,B,H4,H2 Construction: V -N Date: November 12, 2004 Contractor: Designer: Guy Engineer: Report By: A. Schwaller NOTE: The code items listed in this report are not intended to be a complete listing of all possible code requirements in the 1997 UBC. It is a guide to selected sections of the code. # SHEET IDENTIFICATION CORRECTION REQUIRED 1 A2.1 The total area of this building is over the allowed area. -- Sec. 504 and 505. See specifically 504.3. 2 A2.1 S-3 This occupancy is above the maximum floor allowed. -- Table 5-B and Sec. 506. S-3 is over allowed for V -N Construction. Over allowable if Type II -N also. 3 A2.1 This is required to be a 2 hour assembly since it is an occupancy separation S-3 to H-2. Paint room is H-2. -- Table 3-B & Sec. 302.3 4 A.1 Doors must match required occ. seperation 5 Provide access to the building for the physically disabled. -- Sec. 1103.0 & 1104.0 6 Verify loft storage floor framing and design. 7 Spray rooms shall be protected by an approved automatic fire extinguishing system. UFC 4502.8.1 and UBC Sec. 9042.6.1 8 See UFC Sec 4502.8.1 for other spray booth requirement rt i • 1 1 November 5, 2004 Andy Schwaller Building Official 108 8th Street, Suite 201 Glenwood Springs, CO 81601 RE: Waste Management Facility, Cattle Creek Commercial Center I have reviewed the drawings for the Waste Management facility for compliance with the fire and life safety requirements of the Uniform Fire Code and the Uniform Building Code, 1997 editions. The review has based on use of the building with the following occupancies: Use UBC Occupancy Area Shop S-3 12,130 sq. ft. Offices B 4,470 sq. ft. Welding H-4 717 sq. ft. Spray Room 11-2 623 sq. ft. General 1. 1t appears that the allowable floor area for the mixed occupancies is exceeded. (UBC 504.3) 2. Spray application of any quantity of flammable or combustible liquids shall be conducted as set forth in the Fire Code. (UBC Table 3D, footnote 9) 3. Spraying Rooms shall be designed to accommodate spraying operations complying with the Building Code requirements for a Group H, Division 2 Occupancy. (UFC Section 220) 4. A 2 -hour separation is required between a H-2 and a S-3 Occupancy. A l -hour separation is required between a 11-2 and a 1-1-3 occupancy. (UBC Table 3B) 5. Hazardous material shall be stored, used and handled in accordance with UFC Article 80. (UBC 307.1.1) 6. Storage and use and handling of flammable and combustible liquids shall be in accordance with UFC Section 4502.7 and UFC Article 79. (UBC Section 304.8) F Code Review- Waste Management Facility, Cattle Creek Commercial Center, Page 2 Spray Room (11-21 1. Spray booths and spray rooms shall be protected by an approved automatic fire - extinguishing system. (UFC Section 4502.8.1, UBC Section 9042.6.1) 2. Provide ventilation in accordance with UBC 1202.2.3 3. Duct material and termination points shall be in accordance with UFC Section 4502.5.5. 4. Clearance between ducts and combustible construction shall be in accordance with UFC Section 4502.5.6. 5. The ventilation system shall provide air intake ducts extended to pick up flammable vapor within 6 inches of the floor. (UFC Section 4502.5.7) 6. Clean-out openings in the ducts are required at appropriate intervals. (Section 4502.5.9) 7. Electrical wiring and equipment shall be in accordance with Section 4502.4.3. 8. Portable fire extinguishers shall be provided in accordance with Section 4502.8.2 9. Storage and use and handling of flammable and combustible liquids shall be in accordance with UFC Section 4502.7 and UFC Article 79. Welding Bay (11-4) 1. Provide ventilation in accordance with UBC 1202.2.3 2. Compressed gases shall be in accordance with UFC Article 74. (UBC Section 411) Please contact me if you have any questions or 11'! may be of any assistance. Sincerely, Bill Gavette Deputy Chief • .' 4 WAYNE RUDD 132 Park Ave. Basalt, CO 81621 970-927-9119 Fax 927-4027 October 13, 2004 David Mead GARFIELD COUNTY BUILDING & PLANNING 108 8th St. - Suite 201 Glenwood Springs, CO 81601 RE: 0062 CR113 - Bldg.#3 Dear David: Per your request during your site visit on October 6, 2004, enclosed are plans of the interior build out, with occupancy classifications noted, and a site plan of the area. Exits from the office area and shop appear to be visible enough as to not require lightning, as all exterior doors have 1/2 lite glass inserts. Additionally, none of these areas are public, and only used by Waste Management personnel. Tom Zancanella is preparing the documentation on the truck wash and evaporative pond, and will forward copies to you when completed. Waste Management has applied for a state permit for the fuel tank and will forward a copy to you upon receipt. Please feel free to contact me or Wayne Rudd if you have any questions. olanParker Project Manager enclosures er E - +1.70 r �s t 4t) !-4 /017 F-► 9313 / 19/1 oriP r S-1 4tio .� ia tntz, mar rts T geaoo 2'4 tan. 4'lid £.F T7Z0 ,i7.7 $ = O. 995'" ,1 + ,11/, 0t abs a,/L ���; �,.L. [1231 WAYNE RUDD 132 Park Ave. Basalt, CO 81621 970-927-9119 Fax 927-4027 September 27, 2004 Steve Hackett GARFIELD COUNTY BUILDING & PLANNING 108 8th Street - Suite 201 Glenwood Springs, CO 81601 RE: Cattle Creek Building, Code Compliance Letter 9/22/04 Dear Steve: Regarding your letter conceming Cattle Creek Building #3, building permit No. 8238, and Certificate of Occupancy No. 4902, the interior walls and bathrooms were included in and completed under this original building permit. This property is currently leased to Waste Management, and they have relocated from their Red Canyon facility which has the same zoning. This is not a waste transfer station. The majority of the building is an area for inside truck storage, especially on cold nights. The building and outside area required extensive electrical work, including venting outlets, exterior truck plug ins, a fuel island, and area lighting. Waste Management has possession of the property. If you would like access, please call Roland Parker at by office 927-4038 ext.4. We will be happy to make arrangements with the tenant to show you the building. Sincerely, Wayn&Rudd A/4 Steve Hackett Subject: Rudd, Wayne Start Date: Wednesday, September 22, 2004 Due Date: Wednesday, October 27, 2004 Status: In Progress Percent Complete: 096 Total Work: 0 hours Actual Work: 0 hours Owner. Steve Hackett Categories: Building Violation 0082 CR 113. Interior finish work, commercial building, no permit. Cited 9/29/04. Ltr from Rudd indicating work done. Referred to Andy for folllowup letter regarding permit requirements. i Page 1 of 2 Andy Schwaller From: Steve Hackett Sent: Wednesday, September 22, 2004 3:54 PM To: Andy Schwaller Cc: Dave Mead; Tim Holliday; Mark Bean Subject: Rudd FYI Code Compliance Office stevehackett@garfield-county.com September 22, 2004 Wayne Rudd C/O Rudd Construction 132 Park Avenue Basalt, CO 81621 Dear Wayne Rudd, This office has received a report from the Colorado State Electrical Inspector which alleges that interior finish work is being done at Midland Exemption, Building #3, property owned by you at 0062 County Road 113 in unincorporated Garfield County. Please be advised that it is a violation of Colorado Revised Statutes 30-28-205 & 210, Uniform Building Code as adopted by Garfield County zoning resolution of 1978, to perform that work without a building permit. Our records indicate that no permit has been issued. You are hereby given notice, pursuant to the above statutes and regulations, that you must completely correct the violations within thirty (30) days of the date this notice is received. Please be advised that violation of the above statues is a misdemeanor crime punishable, upon conviction, by a fine of not more than $100.00 or imprisonment for not more than ten days, or both, and that each day that the violation continues is deemed to be a separate offense. Garfield County Building and Zoning regulations and permit application forms are available at www.garfield- counE.com in the `Building and Planning" directory. If you have any questions regarding what actions are required to achieve compliance, or you wish to report compliance action taken, please contact this office in writing at the address below or by e-mail at the address above. Sincerely, Steve Hackett 9/30/2004 FILE NOTES 10-7-04 met with Wayne Rudd, Roland Parker, and Tim Holliday at Wayne's building, 0062 CR 113. Building was finaled as warehouse, storage building. They have added bathrooms, office space, paint booth, and repair/storage garage facilities inside the building and fuel dispensing, Truck Island, and washing facilities on the exterior of the building. Wayne said he would get as built plans, site plan and documentation of the fuel and wash facilities to us ASAP. He will do permit application at that time also. Did not issue stop -work -order. David Mead FILE NOTES 10-14-04 SPOKE WITH ROLAND PARKER; He will bring in permit application, questionnaire, another set of plans for the fire department, and pay the plan check fee tomorrow or Monday David Ps. Received plans and revised site plan 10-13-04 • . Andy Schwaller From: Bill Gavette [gavette@carbondalefire.org] Sent: Wednesday, June 01, 2005 2:02 PM To: Andy Schwaller Cc: Tim Holliday Subject: Waste Management Facility - Cattle Creek Andy, Today, I met with Jeremy of Rudd Construction and completed an inspection of the Waste Management Facility. Everthing appeared to be acceptable to me. Let me know if you have any questions. Bill Gavette Deputy Chief Carbondale & Rural Fire Protection District www.carbondalefire.org 1 CTION WILL NOT BE MADE UNLESS IS CARD IS POSTED ON THE JOB 24 HOURS ?MICE REQUIRED FOR INSPECTIONS BUILDING PERMIT GARFIELD COUNTY, COLORADO IssitediPi_ZunAn a••••••••••••••••••• Aa ..,tsr.�. Permit No nn�� t_........ AGREEMENT consideration of the issuance of flit permit, the applicant hereby agrees to comply with all cm and regulation rented to tie --..ine location; consenting and creedal of the proposed trucbue for which this permit is granted, and further agrees that if the above said regnhtion re not tally complied with in the mmHg, location, erection and coatruedon of the above lmcribed structure, the permit may then be revoked by nodce from the County Building nectar and IMMEDIATELY /EDDIATELY BECOME NULL AND VOID. i In Lt4aju Stj /.Z !'P, tams or id , - .. - #3 SOt, i., ► ` treat Eu3tt.0 ask Wheels Frost Side Side Bar This Cod Mat Be Posted So 11 is Moly Viulde Front The Street Hall Elft Ingssetion. INSPECTION RECORD Footog Patcl-12-e04/ j -IS- - Fontlatioa 2 - o Z J,�/ Underground Plumbing/0-2 -nob-- In&atiun Roagb Plumbing 14 n svil Drywall Chimney & Vent Electric Final (by Stoll Rector) Gat Piping ' Pial S- ovine-- vi Electric Elechic Rough (By Stole Inspector) p ,wc Septic Find Erecting Roof Windows Nody sad and ane ALL LISTED ITEMS MUST BE 1 NSPF-CTED AND APPROVED BEFORE COVERING - WHETHER INTERIOR OR EXTERIOR, UNDERGROUND OR ABOVE GROUND. THIS PERMIT IS NOT TRANSFERABLE Phone 384-5003 109 Sflr Street County Courthouse Glenwood Springs, Colorado. APPROVED DO NOT DESTROY TATS CARD Date liter IFPLA DBS OUTSIDE - COVER WITH CLEAR PLASTIC No Assessor's Parcel No"�39-3 — /S%—OD -358 Date 3/// S /� BUILDING PERMIT CARD 7 Job Address or./6)- C «3 l.Ca76-3 'd�J K r Owner !<&4°t i L Address f3i?Pcctic.C4,e &oaf SPone # x°17-9119 Contractor i + ' ' Address'?a 4 ae-e }shoe # 7 "5/15 Setbacks: Front Rear RH Test rF(q ' t� �f� INSPECTIONS Soils Test ' ..k.�a t�� Weatherproofing Footing Mechanical Electrical Rough (State) S« Electric Fin (State) 416- $9,355 Final - Checklist Completed? Certificate Occupancy # Date Septic System # N/(9 Roofing Date Drywall`' Final Gas Piping tQ4f4 /a wn k)ku.S S -JO -cc LH Zoning Foundation Grout Underground Plumbing Rough Plumbing Framing 5--2-q— Insulation 5 VImtl li ' Other NOTES (continue on back) 4• •a INSPECTION WILL NOT BE MADE UNLESS THIS CARD IS POSTED ON THE JOB 24 HOURS NOTICE REQUIRED FOR INSPECTIONS BUILDING PERMIT GARFIELD COUNTY, COLORADO Date Issued -31 5 Zoned Area Permit No `4o5 AGREEMENT In consideration of the issuance of this permit, the applicant hereby agrees to comply with all laws and regulations related to the zoning, location; construction and erection of the proposed structure for which this permit is granted, and further agrees that if the above said regulations are not fully complied with in the zoning, location, erection and construction of the above described structure, the permit may then be revoked by notice from the County Building StGi& rand I TELY BECOME NULL AND VO �,�j IMMED �Zeir • ct 4lhicK WIt `uctvQ Address or Legal Description )• • .n •1 Owner t\ -Contractor iZ�& CO N. Setbacks Front Side Side Rear This Card Must Be Posted So It is Plainly Visible From The Street Until Final Inspection. INSPECTION RECORD Footingti*J Foundation I Underground Plumbing.l Insulations oteria Rough Plumbing i' Drywalck Chimney & Vent t Electric Final (by State Inspector) nJA- Gas Piping ti Final 6_ g.45 -,g',. - Electric Rough (By State Inspector) i' Septic Final Framing 5 -2V -°SW-- (To include Roof in place and Windows and Doors installed). Notes:1 krn f t¢at°oo,. Weeks a . 5-Io-as7N— ALL LISTED ITEMS MUST BE INSPECTED AND APPROVED BEFORE COVERING - WHETHER INTERIOR OR EXTERIOR, UNDERGROUND OR ABOVE GROUND. THIS PERMIT IS NOT TRANSFERABLE Phone 384-504)3 10t 8th Street County Courthouse Glenwood Springs, Colorado. APPROVEDDO NOT DESTROY TTTHIS CARD Date ` IF PLACEDBOUTSIDECO VdIt wiFH CLEAR PLASTIC