HomeMy WebLinkAboutApplication- PermitGarfield County
Building & Sanitation Department
108 8,h Street, Suite #201 Glenwood Springs, Co. 81601
Office- 945-8212 Inspection Line- 384-5003
Job Address 3� �t5�� i ere r 1- r-L,etitptptpRet
NO. c
Nature of Work Building Permit 9 f g/—i) Sy —
Use of Building L?d%lle//(1.-ted5jt/?
Owner E[>LOr iseS
Contractor �(,_\ f)pir J ( / I
Amount of Permit $ D/I• D r Date(5-/P-
Clerk
/P-
Clerk
Permit No:
GARFIELD COUNTY BUILDING PERMIT APPLICATION
108 S° Street, Suite 201, Glenwood Springs, CO 81601
Phone: 970 945-8212/ Fax: 970-384-3470/Inspection Line: 970-384-5003
Parcel/ScheduleNo:. /2/i')St/-t'.(-7
AGREEMENT
PERMISSION IS HEREBY GRANTED TO THE APPLICANT AS OWNER, CONTRACTOR AND/OR THE AGENT OF THE CONTRACTOR OR OWNER TO CONSTRUCT
THE STRUCTURE AS DETAILED ON PLANS AND SPECIFICATIONS SUBMITTED TO AND REVIEWED BY THE BUILDING DEPARTMENT.
IN CONSIDERATION OF THE ISSSUANCE OF THIS PERMIT, THE SIGNER. HEREBY AGREES TO COMPLY WITH ALL BUILDING CODES AND LAND USE
REGULATIONS ADOPTED BY GARFIELD COUNTY PURSUANT TO AUTHORITY GIVEN IN 3028.201 CRS AS AMENDED. THE SIGNER FURTHER AGREES THAT
IF THE ABOVE SAID ORDINANCES ARE NOT FULLY COMPILED WITH IN THE LCOATION, ERECTION, CONSTRUCTION, AND USE OF THE ABOVE DESCRIBED
STRUCTURE, THE PERMIT MAY BE REVOKED BY NOTICE FROM THE COUNTY AND THAT THEN AND THERE IT SHALL BECOME NULL AND VOID.
THE ISSUANCE OF A PERMT BASED UPON PLANS, SPECIFICATIONS AND OTHER DATA SHALL NOT PREVENT THE BUILDING OFFICIAL FROM THEREAFTER
REQUIRING THE CORRECTION OF ERRORS IN SAID PLANS, SPECIFICATIONS AND OTHER DATA OR FROM PREVENTING BUILDING OPERATION BEING
CARRIED ON THEREUNDER WHEN IN VIOLATION OF THS CODE OR ANY OTHER ORDINANCE OR REGULATION OF THIS JURISDICTION.
THE REVIEW OF SUBMITTED PLANS AND SPECIFICATIONS AND INSPECTIONS CONDUCTED THEREAFTER DOES NOT CONSTITUTE AN ACCEPTANCE OF
ANY RESPONSIBILITIES OR LIABLITIES BY GARFIEID COUNTY FOR ERRORS, OMISSIONS OR DISCREPENCIES. THE RESPONSIBILITY FOR THESE ITEMS
AND IMPLEMENTATION DURING CONSTRUCTION RESTS SPECIFICIALLY WITH THE ARTICTECT, DESIGNER, BUILDER, AND OWNER. COMMENTS ARE
INTENDED TO BE CONSERVATIVE AND 1N SUPPORT OF THE OWNERS INTEREST.
Garfom.003
` It gr 1 HEREBY ACKNOWLEDGE THAT I HAVE READ AND UNDERSTAND THE AGREEMENT ABOVE(INITIAL): GLUE
t
Job Address:
38150 Rlt/ER FRavTAGE Ro. 11/6-Wci9Sr4E, CO. 8/S47
1 Lot No: Block No: Subd. / Exemption:
I -or 2 /4GAJR RIPPY ExEmpriON
2
Owner:
SHER/QC EnvreRPRl,3ES
Address 0150 CR /26
GLEmiwoon SPR. co
Ph:
915-Z719
Wk Ph: «EOR. e
379-3223
3
Contractor:
S'ArnE
Address:
SA,n,E
Ph:
SAone
Lic. No.
4
Architect/Engineer:
Address:
Ph:
Lic. No.
5
Sq. Ft. of Building:
9600
Sq. Ft. of Lot:
44.2Z ncgzES
Height:
2372-
No. of Floors:
/
6
Use of Building:
COen s',ERCAiq L. SroAAGE
7
Describe Work:
8
Class of Work: 1.a New o Alteration o Remove
o Addition ❑ Move
9
10
Garage: o Single
o Double
Carport: o Single
❑ Double
ser Driveway Permit we* On -Site Sewage Disposal a Site Plan
GOOT Or 395228 (Septic)
11
Valuation of Work: $
Adjusted Valuations: 5 +3 (/a f �c#,80 •
OCT
12
S ecialCo di v.,/�I-
'
NOTICE
A SEPARATE ELECTRICAL PERMIT IS REQUIRED AND MUST BE
ISSUED BY THE STATE OF COLORADO.
THIS PERMIT BECOMES NULL AND VOID IF WORK OR CONSTRUCTION
AUTHORIZEDTCTI IS NOT ISSUEDSP WITHIN ABANDONED DAYS, OE, IF CONSRA
PERIOD OF 180 DAYS AT ANY TIME AFTER WORK IS COMMENCED.
PERIOD OF DOR WORKAISSUSPENDER OW KIS
I HEREBY CERTIFY THAT 1 HAVE READ AND EXAMINED THIS
APPLICATION AND KNOW THE SAME TO BE TRUE AND CORRECT. ALL
PROVISIONS OF LAWS GOVERNING THIS TYPE OF WORK WILL BE
COMPLETED WITHIN WHETHER SPECIFIED HEREIN OR NOT. THE
GRANTING OF A PERMIT DOES NOT PRESUME TO GIVE AUTHORITY
TO VIOLATE O' CEL THE PROVISIONS OF ANY OTHER STATE OR
LOCAL LAW helot LATING NSTRUCTION OR THE PERFORMANCE
OFCONSTR si
41 // 0 I
Plan Check Fee:
1 //_�r �/
((e
Permit Fee:
^
/�J7�. 1��
Total Fee:
301( 0
�.�/- /
paite{d Permit1itIssued:
OCC Group: Const. Type:
S-/ Vn/
Zoning:
Setbacks:
Manu. Home: ISDS No. &
SD °°c
Fee:
(Tt \3
�J 1l�
:f � iac ji R e �� I DAT /
ASi; -00' iii:. !i At / i
APP': AL/DATE � 9Pyjts'
ATE
�
AGREEMENT
PERMISSION IS HEREBY GRANTED TO THE APPLICANT AS OWNER, CONTRACTOR AND/OR THE AGENT OF THE CONTRACTOR OR OWNER TO CONSTRUCT
THE STRUCTURE AS DETAILED ON PLANS AND SPECIFICATIONS SUBMITTED TO AND REVIEWED BY THE BUILDING DEPARTMENT.
IN CONSIDERATION OF THE ISSSUANCE OF THIS PERMIT, THE SIGNER. HEREBY AGREES TO COMPLY WITH ALL BUILDING CODES AND LAND USE
REGULATIONS ADOPTED BY GARFIELD COUNTY PURSUANT TO AUTHORITY GIVEN IN 3028.201 CRS AS AMENDED. THE SIGNER FURTHER AGREES THAT
IF THE ABOVE SAID ORDINANCES ARE NOT FULLY COMPILED WITH IN THE LCOATION, ERECTION, CONSTRUCTION, AND USE OF THE ABOVE DESCRIBED
STRUCTURE, THE PERMIT MAY BE REVOKED BY NOTICE FROM THE COUNTY AND THAT THEN AND THERE IT SHALL BECOME NULL AND VOID.
THE ISSUANCE OF A PERMT BASED UPON PLANS, SPECIFICATIONS AND OTHER DATA SHALL NOT PREVENT THE BUILDING OFFICIAL FROM THEREAFTER
REQUIRING THE CORRECTION OF ERRORS IN SAID PLANS, SPECIFICATIONS AND OTHER DATA OR FROM PREVENTING BUILDING OPERATION BEING
CARRIED ON THEREUNDER WHEN IN VIOLATION OF THS CODE OR ANY OTHER ORDINANCE OR REGULATION OF THIS JURISDICTION.
THE REVIEW OF SUBMITTED PLANS AND SPECIFICATIONS AND INSPECTIONS CONDUCTED THEREAFTER DOES NOT CONSTITUTE AN ACCEPTANCE OF
ANY RESPONSIBILITIES OR LIABLITIES BY GARFIEID COUNTY FOR ERRORS, OMISSIONS OR DISCREPENCIES. THE RESPONSIBILITY FOR THESE ITEMS
AND IMPLEMENTATION DURING CONSTRUCTION RESTS SPECIFICIALLY WITH THE ARTICTECT, DESIGNER, BUILDER, AND OWNER. COMMENTS ARE
INTENDED TO BE CONSERVATIVE AND 1N SUPPORT OF THE OWNERS INTEREST.
Garfom.003
` It gr 1 HEREBY ACKNOWLEDGE THAT I HAVE READ AND UNDERSTAND THE AGREEMENT ABOVE(INITIAL): GLUE
t
The following items are required by Garfield County for a final inspection:
1. A final Electrical Inspection from the Colorado State Electrical Inspector
2. Permanent address assigned by Garfield County Building Department posted where
readily visible from access road;
3. A finished roof, a lockable house, complete exterior siding, exterior doors and windows
installed, a complete kitchen with cabinets, a sink with hot & cold running water, non-
absorbent kitchen floor coverings, counter tops and finished walls, ready for stove and
refrigerator, all necessary plumbing;
4. A complete bathroom, with washbowl, tub or shower, toilet stool, hot and cold running
water, non-absorbent floors and walls finished and a privacy door;
5. All steps outside or inside over three (3) steps must have handrails, guard rails on
balconies or decks over 30" high constructed to all 1997 UBC requirements;
Outside grading done to where water will detour away from the building;
7. Exceptions to the outside steps, decks and grading may be made upon the demonstration
of extenuating circumstances, i.e. weather, but a Certificate of Occupancy will not be issued until
all the required items are completed and a final inspection made.
A CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL ALL THE ABOVE
ITEMS HAVE BEEN COMPLETED.
****CANNOTOCCUPY OR USE DWELLING UNTIL A CERTIFICATE OF OCCUPANCY
(C.O.) IS ISSUED. OCCUPANCY OR USE OF DWELLING WITHOUT A C.O. WILL BE
CONSIDERED AN ILLEGAL OCCUPANCY AND MAY BE GROUNDS FOR VACATING
PREMISE UNTIL ABOVE CONDITIONS ARE MET.
I understand and agree to abide by the above conditions for occupancy use and the issuance of a
Certificate of Occupancy for the dwelling under building permit# ern .
z///os'
Signa
BpcontO82002
Date
FEF ESTIMATE
FINISHED LIVING SPACE:
UNFINISHED BASEMENT:
CRAWL SPACE: X 9.00 =
X 69.00 =
X 41.00 =
GARAGE: X 18.00 =
UNCOVERED PATIO/DECK:
COVERED PATIO/DECK:
(kenMISC.
X12.00 =
X 14.00 =
TOTAL VALUATION:
PLAN REVIEW FEE: 1)&, V6
PERMIT FEE: 1 7 9(-15c5'
TOTAL: a 96/ D/
MANUFACTURED HOME SET UP FEE:
SEPTIC - PERMIT:
PERK:
GARFIELD COUNTY BUILDING AND PLANNING
970-945-8212
MINIMUM APPLICATION REQUIREMENTS
FOR
CONSTRUCTION OF
COMMERCIAL OR MULTI -FAMILY RESIDENTIAL BUILDINGS
including
NEW CONSTRUCTION
ADDITIONS
ALTERATIONS
and
MOVED BUILDINGS
In order to understand the scope of the work intended under a permit application and expedite
the issuance of a permit it is important that complete information be provided. Adequate and
complete information will prevent delays in the plan review process. Reviewing a plan and the
discovery that required information has not been provided by the applicant may result in the
delay of the permit issuance and in proceeding with building construction. The owner or
contractor may be required to provide this information before the plan review may proceed. This
causes delays because other plans that are in line for review may be given attention before the
new information may be reviewed after it has been provided to the Building Department.
Please review this document to determine if you have enough information to design your
project and provide adequate information to facilitate a plan review. If you do not, it may
be helpful to obtain a book titled "Dwelling Construction Under the Uniform Building
Code". This book is available to you through this department at our cost. Also, please
consider using a design professional for assistance in your design and a construction
professional for construction of your project.
To provide for a more understandable plan in order to determine compliance with the building,
plumbing and mechanical codes, applicants are requested to review the following checklist prior
to and during design.
1
Plans to be included for a Building Permit must be on draft paper at least 18"x 24" and
drawn to scale.
Plans must include a floor plan, a concrete footing and foundation plan, elevations all sides with
decks, balcony steps, hand rails and guard rails, windows and doors, including the finish grade
line. A section showing in detail, from the bottom of the footing to the top of the roof, including
re -bar, anchor bolts, pressure treated plates, floor joists, wall studs and spacing, insulation,
sheeting, house -rap, (which is required), siding or any approved building material.
A window schedule. A door schedule.
A floor framing plan, a roofing framing plan, roof must be designed to withstand a 40 pound per
square foot. up to 7,000 feet in elevation, an 80 M.P.H. windshear, wind exposure B, windload of
15 pounds per square foot and a 36 inch frost depth.
AH sheets to be identified by number and indexed. All of the above requirements must be met or
your plans will be returned.
All plans submitted must be incompliance with the 1997 UBC, UMC and 1997 UPC.
Applicants are required to indicate appropriately and to submit completed checklist at
time of application for a permit:
1. Is a site plan included that identifies the location of the proposed structure, additions or
other buildings, setback easements, and utility easements showing distances to the
property lines from each corner of the proposed structure prepared by a licensed surveyor
and has the surveyors signature and professional stamp on the drawing? Slopes of 30%
or more on properties must be show on site plan. NOTE: 106.3.1 (7.) Any site plan for
the placement of any portion of a structure within 50 ft. of a property line and not within
a previously surveyed building envelope on a subdivision final plat shall be prepared by a
licensed surveyor and have the surveyors signature and professional stamp on the
drawing. Any structure to be built within a building envelope of a lot shown on a
recorded subdivision plat, shall include a copy of the building envelope as it is shown on
the final plat with the proposed structure located within the envelope.
Yes t/--
2.
2. Does the site plan when applicable include the location of the I.S.115. (Individual
Sewage Disposal System) and distances to the property lines, wells (on subject property
and adjacent properties), streams or water courses? This information must be certified by
a licensed surveyor with their signature and professional stamp on the design.
Yes ✓ No Not necessary for this project
3. Are the plans submitted for application review construction drawings and not drawings
that are stamped or marked identifying them as "Not for construction, for permit issuance
r
only", "Approval drawings only", "For permit issuance only" or similar language?
Yes ✓ No Not necessary for this project
4. Is the I.S.D.S. (Individual Sewage Disposal System) designed, stamped and signed by a
Colorado Registered Engineer?
Yes 1� No Not necessary for this project
5. Does the site plan indicate the location and direction of the State, County or private road
accessing the property?
Yes ✓
6. Do the plans include a foundation plan indicating the size, location and spacing of all
reinforcing steel in accordance with the uniform building code or per stamped engineered
design?
Yes ✓ No Not necessary for this project
7. If the building is a pre-engineered structure, is there a stamped, signed engineered
foundation plan for this building?
Yes ✓ No Not necessary for this project
8. Do the plans indicate the location and size of ventilation openings for under floor crawl
spaces and the clearances required between wood and earth?
Yes No Not necessary for project ✓
9. Do the plans indicate the size and location of the ventilation openings for the attic, roof
joist spaces and soffits?
Yes No Not necessary for this project L/-
10.
10. Do the plans include design loads as required under the Uniform Building Code for roof
snowloads, (a minimum of 40 pounds per square foot in Garfield County)?
Yes ✓ No Not necessary for this project
11. Do the plans include design loads as required for floor loads under the Uniform Building
Code Chapter 16 and Tables 16A, 16B and 16C?
Yes No Not necessary for this project ✓
12. Does the plan include a building section drawing indicating foundation, wall, floor, and
roof construction?
Yes ✓ No Not necessary for this project
13. Is the wind speed and exposure design included in the plan?
Yes ✓ No Not necessary for this project
14. Does the building section drawing include size and spacing of floor joists, wall studs,
ceiling joists, roof rafters or joists or trusses?
Yes ✓ No Not necessary for this project
15. Does the building section drawing or other detail include the method of positive
connection of all columns and beams?
Yes ✓ No Not necessary for this project
16. Does the plan indicate the height of the building or proposed addition from the highest
point of the building or addition measured at mid span between the ridge and the eave
down to existing grade contours?
Yes ✓ No Not necessary for this project
17. Does the plan include any stove or zero clearance fireplace planned for installation
including make and model and Colorado Phase II certifications or Phase II EPA
certi fication?
Yes No Not necessary for this project ✓
18. Does the plan include a masonry fireplace including a fireplace section indicating design
to comply with the Uniform Building Code Chapter 31?
Yes No Not necessary for this project ✓
19. Does the plan include a window schedule or other verification that egress/rescue windows
from sleeping rooms and/or basements comply with the requirements of the Uniform
Building Code?
Yes ✓ No Not necessary for this project
20. Does the plan include a window schedule or other verification that windows provide
natural light and ventilation for all habitable rooms?
Yes No Not necessary for this project
21. Do the plans indicate the location of glazing subject to human impact such as glass doors,
glazing immediately adjacent to such doors; glazing adjacent to any surface normally
used as a walking surface; sliding glass doors; fixed glass panels; shower doors and tub
enclosures and specify safety glazing for these areas?
Yes ✓ No Not necessary for this project
22. Do the plans include a complete design for all mechanical systems planned for
installation in this building?
Yes No Not necessary for this project ✓
23. Have all areas in the building been accurately identified for the intended use?
(Occupancy as identified in the Uniform Building Code Table 5-A)
Yes ✓ No Not necessary for this project
4
24. Does the plan indicate the quantity, form, use and storage of any hazardous materials that
may be in use in this building?
Yes No Not necessary for this project ✓
25. Is the location of all natural and liquid petroleum gas furnaces, boilers and water heaters
indicated on the plan?
Yes ✓ No Not necessary for this project
26. Do the plans indicate the location and dimension of restroom facilities and if more than
four employees and both sexes are employed, facilities for both sexes?
Yes No Not necessary for this project ✓
27. Do the plans indicate that restrooms and access to the building are handicapped
accessible?
Yes No Not necessary for this project ✓
28. Have two (2) complete sets of construction drawings been submitted with the
application?
Yes ✓ No
29. Have you designed or had this plan designed while considering building and other
construction code requirements?
Yes ✓ No Not necessary for this project
30. Does the plan accurately indicate what you intend to construct and what will receive a
final inspection by the Garfield County Building Department?
Yes ✓ No
31. Do your plans comply with all zoning rules and regulations in the County related to your
zone district? For corner lots see supplemental section 5.05.03 in the Garfield County
Zoning Resolution for setbacks.
Yes ✓ No
32. Do you understand that approval for design and/or construction changes are required
prior to the implementation of these changes?
Yes ✓ No
33. Do you understand that the Building Department will collect a "Plan Review" fee from
you at the time of application and that you will be required to pay the "Permit" fee as well
as any "Septic System" or "Road Impact" fees required, at the time you pick up your
building permit?
Yes ✓ No
5
34. Are you aware that you are required to call for all inspections required under the Uniform
Building Code including approval on a final inspection prior to receiving a Certificate of
Occupancy and occupancy of the building?
Yes ✓ No
35. Are you aware that the Permit Application must be signed by the Owner or a written
authority be given for an Agent and that the party responsible for the project must comply
with the Uniform Codes?
Yes ✓ No
36. Are you aware that twenty-four (24) hour notice is required for all inspections?
Inspections will be made from Battlement Mesa to West Glenwood in the mornings
and from Glenwood Springs to Carbondale, in the afternoon. All inspections must
be called in by 3:30 p.m. the day before. Failure to give twenty-four (24) hour notice
for inspections will delay your inspection one (1) day. Inspections are to be called in
to 384-5003.
37. Are you aware that requesting inspections on work that is not ready or not accessible
will result in a $47.00 re -inspection fee?
Yes ✓ No
38. Are you aware that prior to issuance of a building permit you are required to show proof
of a driveway access permit or obtain a statement from the Garfield County Road &
Bridge Department stating one is not necessary? You can contact the Road & Bridge
Department at 625-8601.
Yes ✓ No
39. Do you understand that you will be required to hire a State of Colorado Licensed
Electrician and Plumber to perform installations and hookups? The license number will
be required at time of inspection.
Yes ✓ No
40. Are you aware, that on the front of the building permit application you will need to fill in
the Parcel/ Schedule Number for the lot you are applying for this permit on prior to
submittal of the building permit application? Your attention in this is appreciated.
Yes ✓ No
41. Do you know that the local fire district may require you to submit plans for their review
of fire safety issues? Yes ✓ No (Please check with the
building department about this requirement)
7
Signa
I hereby
the best
owledge that I have read, understand, and answered these questions to
y ability
Phone: 9416-2 7/ 9 (days); 941x- 2-7 / 9
(evenings)
Project Name: SNER / C.K EN rE/t PR /5. ES
Project Address: 38/SO RI e/e ,/Zorvrpi QE RD.
NEG/cRSTh. E', CO
Note:
Date
z/i/o #
If you answered "No" on any of these questions you may be required to provide this information
at the request of the Building Official prior to beginning the plan review process. Delays in
issuing the permit are to be expected. Work may not proceed without the issuance of the permit.
*If you have answered "Not necessary for this project" on any of the questions and it is
determined by the Building Official that the information is necessary to review the application
and plans to determine minimum compliance with the adopted codes, please expect the
following:
A. The application may be placed behind more recent applications for building permits in
the review process and not reviewed until required information has been provided and the
application rotates again to first position for review.
B. Delay in issuance of the permit.
C. Delay in proceeding with construction.
*If you answered "No" to this question the circumstances described in the question could result
in a "Stop Work Order" being issued or a "Certificate of Occupancy" not being issued.
Bpcomm
11/2003
Gafield County
Building and Planning
108 8th Street Ste 201
Glenwood Springs, Colorado
970-945-8212
Plan analysis based on
the 1997 Uniform Building Code
Project Number: Date: May 10, 2004
Project Name: Sherick Enter.
Address: 0150 County Rd. 126, New Castle, CO.
Contractor: Sherick Enter
Occupancy: S1 Architect:
Construction: V -N Engineer: Kurtz/Soros
Report By: A. Schwaller
NOTE: The code items listed in this report are not intended to be a
complete listing of all possible code requirements in the 1997 UBC.
It is a guide to selected sections of the code.
Report created using Plan Analyst software by b w & a. (719) 599-5622
Portions of the material contained in this program are reproduced
from the Uniform Building Code with the permission of the
International Conference of Building Officials.
SEPARATION
DIRECTION BOUNDARY AREA INCREASE
NORTH Building 60.0 Feet
EAST Property line 35.0 Feet
SOUTH Building 60.0 Feet
WEST Property line 200.0 Feet
Allowable area increased 100.% for open
- - Sec. 505.1
FL NAME
FIRE PROTECTION
30.0 Feet
35.0 Feet
30.0 Feet
200.0 Feet
area on 3 sides.
OCC MAX FLR AREA ALLOWED RATIO STATUS
1 Storage/Stock Room S1 ok
TOTAL FOR FLOOR
BUILDING TOTAL
- - Sec. 504 and Table 5-B
9600
9600
9600
The actual height of this building is 22. feet.
16000
16000
16000
0.6 ok
0.6 ok
0.6 ok
Code review for:
Project Id.: Sherick
Address: 0150 County
Enter.
Rd. 126, New Castle,
CO.
Page # 2
EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION
Table 5-A
NORTH
For
Occupancy
S1
EAST
For
Occupancy
S1
SOUTH
For
Occupancy
S1
WEST
For
Occupancy
S1
None
3/4 hour
Bearing
Wall
0 hour
Bearing
Wall
0 hour
Bearing
Wall
0 hour
Bearing
Wall
0 hour
Not Allowed
Non -Bearing
Wall
0 hour
Non -Bearing
Wall
0 hour
Non -Bearing
Wall
0 hour
Non -Bearing
Wall
0 hour
Opening
Protection
None
Opening
Protection
None
Opening
Protection
None
Opening
Protection
None
Construction
Material
Any
Construction
Material
Any
Construction
Material
Any
Construction
Material
Any
Parapet
Required
No
Parapet
Required
No
Parapet
Required
No
Parapet
Required
No
No fire protection requirements for openings.
Openings are to be protected with 3/4 hr fire assemblies.
50% of the area of the wall maximum. -- Table 5-A,
Footnote 5 & Sec. 503.2.2
Maximum single window size is 84 sq.ft. with no dimension
greater than 12 feet. -- Sec. 713.8
-- Openings are not permitted in this wall.
OTHER BUILDING ELEMENTS
MATERIAL
Any
Any
Any
Any
Any
Any
Any
ELEMENT
Interior Bearing wall
Interior nonbrg wall
Structural Frame
Exterior Struct Frame
Floor/Ceiling Assembly
Roof/Ceiling Assembly
Stairs
Table 6-A
RATING
0 hr
0 hr
0 hr
0 hr
0 hr
0 hr
None
NOTES
See footnote #1
FOOTNOTES:
1) Elements in an exterior wall located where openings are not permitted
or where protection of openings is required, shall be protected
against external fire exposure as required for exterior bearing walls
or the structural frame, whichever is greater. -- Table 6-A, footnote 1
Page # 3
Code review for:
Project Id.: Sherick Enter.
Address: 0150 County Rd. 126, New Castle, CO.
PENETRATIONS OF FIRERESISTIVE ASSEMBLIES
WALLS ASSEMBLIES -- Sec. 709.6
Through penetrations:
1) Penetrations shall be installed as tested in the rated assembly.
-- Sec. 709.6.2
2) Penetrations shall be protected by an approved penetration
firestop system and shall have an F rating of not less than the
required rating of the wall penetrated. -- Sec. 709.6.3
Exception: When penetrating items are steel, ferrous or copper
pipes or steel conduits and the wall is concrete or
masonry, the annular space shall be permitted to be
grout or mortar. The minimum thickness is the
thickness required to maintain the fire rating. The
maximum size of the penetrating items is equivalent
to a 6 -inch diameter and the opening is a maximum of
144 square inches. -- Sec. 709.6.1
Membrane penetrations:
The requirements are the same as for through penetrations.
-- Sec. 709.7
Exceptions:
1. Steel electrical outlet boxes that do not exceed 16 square
inches provided that the area of such openings does not exceed
100 square inches for any 100 square feet of wall area.
Boxes on opposite sides of the assembly shall be
separated by a horizontal distance of not less than 24
inches.
2. Sprinklers with metal escutcheon plates.
Noncombustible penetrating items shall not be connected to
combustible materials on both sides of the membrane unless it can
be confirmed that the fire -resistive integrity of wall is
maintained. -- Sec. 709.7
Page # 4
Code review for:
Project Id.: Sherick Enter.
Address: 0150 County Rd. 126, New Castle, CO.
SMOKE and FIRE DAMPERS -- Sec. 713.10 and 713.11
Dampers shall be accessible for inspection and servicing:
1. Penetrations through area separation walls.
Penetrations through occupancy separations.
2. Penetrations of the fire -resistive construction of horizontal
exit walls or corridors serving as a means of egress.
Exception: Openings for steel ducts penetrating the required
fire -resistive construction of corridors are not
required to have smoke dampers when such ducts
are of not less than 0.019 -inch thickness
(26 gage) and have no openings serving the
corridor.
3. Penetrations of shaft enclosures.
Exceptions:
1. Duct penetrations by steel exhaust air subducts
extending vertically upward at least 22 inches above
the top of the opening in a vented shaft where the
airflow is upward.
2. Penetrations of a fire -resistive floor forming the
base of a shaft enclosure may be protected by fire
dampers listed for installation in the horizontal
position.
3. Smoke dampers are not required when shaft is exhaust
only, and is used for continuously operating fans.
4. Penetrations of the ceiling of fire -resistive floor -ceiling
or roof -ceiling assemblies.
Exception: Smoke dampers are not required.
5. Penetrations of an atrium enclosure element.
Exception: Smoke dampers are not required.
6. Penetrations of exterior walls where protection of openings
is required.
Exception: Smoke dampers are not required.
7. Penetrations of areas of refuge.
Exception: Ventilation system designed to supply outside
air during an emergency.
8. Smoke dampers are required in smoke barriers and elevator
lobbies.
EXIT REQUIREMENTS:
FL NAME NUMB MIN MIN PANIC HALLWAY/ DOOR NOTES
OCC EXITS WIDTH HDWR CORRIDOR SWING
1 Storage/Stock Room 32 2 6.4 No N/A N/R
TOTAL 32 2 6.4 No N/A N/R
Page # 5
Code review for:
Project Id.: Sherick Enter.
Address: 0150 County Rd. 126, New Castle, CO.
In areas where 2 exits are required, the minimum separation is 1/2 of
the maximum diagonal of the area or floor. -- Sec. 1004.2.4
When 2 exits are required, exits must be arranged so that it is possible
to go in either direction from any point in a corridor or hallway to a
separate exit, except for dead ends not exceeding 20 feet in length.
- - Sec. 1004.2.6
Exit signs are required from all areas where 2 or exits are required.
- - Sec. 1003.2.8.2, Exception 2
No point to be more than 100 feet from an exit sign.
Main exterior exit doors which obviously and clearly are identifiable
as exits need not be signed when approved. -- Sec. 1003.2.8.2, Exception 1
Door swing is based on Sec. 1003.3.1.5 except as noted.
Occupant load factor is based on Table 10-A.
Number of exits is based on Table 10-A except as noted.
Exit width is in inches and based on Sec. 1003.2.3 and Table 10-B
Exit width is to be divided approximately equally among exits.
- - Sec. 1003.2.3.2
Width shown for all areas is based on other egress components.
Width shown for 1st floor is based on other egress components.
Width shown for other floors & basements is based on stairways.
- - Table 10-B
For the minimum width of doors, see Sec. 1003.3.1.3
For the minimum width of hallways, see Sec. 1004.3.3.2
For the minimum width of corridors, see Sec. 1004.3.4.2
For the minimum width of stairways, see Sec. 1003.3.3.2
FOOTNOTES:
FLUSH AND SURFACE BOLTS:
Manually operated edge- or surface -mounted flush bolts and surface
bolts or any other type of device that may be used to close or
restrain the the door other than by operation of the locking device
shall not be used. When automatic flush bolts are used, the door
leaf having the automatic flush bolt shall not have a door knob or
surface -mounted hardware. The unlatching of any leaf shall not
require more than one operation. -- Sec. 1003.3.1.8
Page # 6
Code review for:
Project Id.: Sherick Enter.
Address: 0150 County Rd. 126, New Castle, CO.
LOCKS AND LATCHES:
Regardless of the occupant load served, exit doors shall be openable
from the inside without the use of a key or any special knowledge or
effort. -- Sec. 1003.3.1.8
Key -locking hardware may be used on the main exit when the main exit
consists of a single door or pair of doors if there is a sign stating
THIS DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS. When unlocked,
door(s) must swing without operation of any latching device. -- exc.
LANDINGS AT DOORS:
1) A floor or landing shall be provided on each side of doors. When
access for persons with disabilities is required. the floor or landing
shall not be more than 1/2 inch lower than the threshold. When access
is not required, the maximum is 1 inch. -- Sec. 1003.3.1.6
2) Landings shall have a width not less than the width of the stairway
or width of the doorway, whichever is the greater. Where a landing
serves an occupant load of 50 or more, doors in any position shall
not reduce the landing dimension to less than one half it required
width. The minimum length in the direction of exit travel is 44 inches.
-- Sec. 1003.3.1.7
TRAVEL DISTANCE: (distance to an exit)
The maximum travel distance in this building is 200 feet. -- Sec. 1004.2.5.2
The travel distance for the major occupancy may be 300 feet.
-- Sec. 1004.2.5.2.5
Travel distance shall not be limited within an exit enclosure or exit
passageway. -- Sec. 1005.2.2
Page # 7
Code review for:
Project Id.: Sherick Enter.
Address: 0150 County Rd. 126, New Castle, CO.
BUILDING ACCESSIBILITY:
1) This building including each tenant shall be provided with at least
one entrance which complies with the accessible route provisions of
CABO/ANSI A117.1. At least 50 percent of all entrances shall be
accessible. -- Sec. 1103.2.3
2) When more that one exit is required from any accessible space, each
accessible portion of the space shall be served by not less than two
accessible means of egress. -- Sec. 1104.1.1
3) When an exit stairway is part of an accessible means of egress, the
stairway shall have a clear width of not less than 48 inches between
the handrails. The stairway shall either incorporate an area of refuge
within an enlarged story -level landing or shall be accessed from
an area of refuge. -- Sec. 1104.1.2
The area of refuge shall have direct access to the stairway that serves
it. -- Sec. 1104.2.1
4) Each area of refuge shall be sized to accommodate one wheelchair space
not less than 30 inches by 48 inches for each 200 occupants, or
portion thereof. -- Sec. 1104.2.3
5) If the area of refuge is not within the stairway, it shall be separated
from the rest of the story by a smoke barrier having at least a one-
hour fire -resistance rating. Smoke barriers shall extend to the roof or
floor deck above. Doors shall be smoke and draft control assemblies
with a rating not less than 20 minutes. -- Sec. 1104.2.4
6) Two-way communications are required. -- Sec. 1104.2.5
7) Each area must be identified by a sign stating AREA OF REFUGE and the
international symbol of accessibility. -- Sec. 1104.2.7
8) NOTE: Exit stairways in buildings protected throughout by an approved
automatic sprinkler system are NOT required to incorporate an area of
refuge. -- Sec. 1104.1.2, Exception 2
ROOFING REQUIREMENTS:
1) The roofing on this building is required to be Class C. -- Table 15-A
2) See section 1504 and ICBO research reports for requirements.
VENTILATION:
All areas customarily occupied by humans shall be provided with natural
ventilation by means of openable exterior openings with an area of not
less than 1/20 of the total floor area or shall be provided with a
mechanically operated ventilation system. Such system shall be capable
of supplying a minimum of 15 cubic feet per minute of outside air per
occupant. -- Sec. 1202.2.1
Page # 8
Code review for:
Project Id.: Sherick Enter.
Address: 0150 County Rd. 126, New Castle, CO.
WALL AND CEILING FINISH:
1) Wall and ceiling finish materials are required to comply with
Sec. 804.1 and Table 8-B.
2) Carpeting on the ceiling is required to have a Class I flame
spread rating. -- Sec. 804.2
3) Textile wall coverings shall have Class I flame spread rating.
and shall be protected by automatic sprinklers or meet the
acceptance criteria of U.B.C. Standard No. 8-2 -- Sec. 805
4) Toilet room floors shall have a smooth, hard nonabsorbent surface
that extends upward onto the walls at least 5 inches.
-- Sec. 807.1.1
5) Walls within 2 feet of the front and sides of urinals and water
closets shall have a smooth, hard nonabsorbent surface.
-- Sec. 807.1.2
INSULATION NOTES:
1) All insulation material including facings are required to have a
flame -spread rating of 25 or less and a maximum smoke density of 450
unless it is in a concealed space and the facing is in contact with
a wall or ceiling. -- Sec. 707.3 exc.2
2) Foam plastic insulations are required to be protected. -- Sec. 2602
ACCESSIBLE FACILITIES:
NOTE: Except as noted, section numbers listed below are from
CABO/ANSI A117.1 - 1992
Page # 9
Code review for:
Project Id.: Sherick Enter.
Address: 0150 County Rd. 126, New Castle, CO.
WATER FOUNTAINS AND WATER COOLERS:
At least 50 percent of drinking fountains, but not less than one,
provided on every floor shall be accessible. -- UBC Sec 1105.4.1
Accessible units must comply with the following:
1) Spout is to be within 36 inches of the floor. -- Sec. 4.15.2.1
2) Spout arranged for parallel approach shall be located 3 inches
maximum from the front edge. Spouts of cantilevered units with
knee and toe clearances shall be located 15 inches minimum from
the vertical support and 5 inches maximum from the front edge.
- - Sec. 4.15.2.2
3) Spouts shall provide a flow of water 4 inches height minimum.
- - Sec. 4.15.2.3
4) Operable parts shall be located at or near the front edge of the
unit and shall comply with 4.25.4 -- Sec. 4.15.3
5) A cantilevered unit is required to extend 17 inches minimum from
the vertical support. Clear knee space must provide a clear area
of 8 inches in depth at 27 inches high and 11 inches at 9 inches
minimum above the floor. -- Sec. 4.15.4.1
6) Forward approach units shall comply with 4.2. Units in alcoves
shall comply with 4.2.4.4. Units not having the necessary knee
and toe clearance or clear space under them shall comply with
4.2.4 and have a clear floor space that allows a person in a
wheelchair to make a parallel approach. -- Sec. 4.15.4.2
TOILET FACILITIES:
1) A 60 inch diameter unobstructed turning space is required in
the toilet room. -- Sec. 4.16.3, 4.2.3 & Fig. B4.2.3
2) Water closet shall be mounted adjacent to a side wall or
partition. The distance from the side wall or partition to the
centerline of the water closet shall be 18 in. Sec. 4.17.1
3) When the accessible water closet is not in a stall:
The clear floor space shall be 48 in minimum in front
of the water closet and 42 in from the center line of the
water closet on the side not adjacent to the wall.
-- Sec. 4.17.2 & Fig. B4.17.2
4) When the accessible water closet. is in a stall:
The stall shall be 60 in wide minimum and 56 in deep minimum
for wall hung water closets and 59 in deep minimum for floor
mounted water closets. -- Sec. 4.18.3.1
If the door swings into the stall, the required depth shall
be increased by 36 inches minimum. -- Sec. 4.18.3.2 &
Fig. B4.18.3.1
Page # 10
Code review for:
Project Id.: Sherick Enter.
Address: 0150 County Rd. 126, New Castle, CO.
5) The bars are to be 33 to 36 inches above the floor and shall
be provided on the rear wall and on the side wall closest to
the water closet. -- Sec. 4.24.2.2 & Figs. B4.17.3, B4.17.4
and B4.18.3.1
a) Side grab bar is required to start within 12 inches of the
back wall and extend to 54 inches from the back wall. (The
minimum length of the bar is 42 in) -- Sec. 4.17.4.1 &
Figs. B4.17.3 and B4.18.3.1
b) The rear bar shall be 24 in long minimum, centered on the
water closet. Where space permits, the bar shall be 36 in
long minimum, with the additional length provided on the
transfer side. -- Sec. 4.17.4.2 & Figs. B4.17.3, B4.17.4
and B4.18.3.1
6) The top of the seat on the water closet is required to be 17
to 19 inches above the floor. -- Sec. 4.17.3 & Fig. B4.17.3
7) Accessible urinals shall be of the stall type or wall hung with
the rim at 17 inches maximum above the floor. -- Sec. 4.19.2
8) A clear area of 30 X 48 inches minimum is required in front
of the urinal. Privacy shields shall not extend beyond the
front edge of the urinal rim, unless they are 30 inches apart
minimum. -- Sec. 4.19.3
9) Accessible lavatories shall be mounted with the rim 34 inches
maximum above the floor and a clearance of 29 inches minimum
from the floor to the bottom of the front edge of the apron.
-- Sec. 4.20.2.1 & Fig. B4.20.3.1
10) It shall extend 17 inches minimum from the wall. The clear knee
space shall be 8 inches in depth minimum at 27 inches minimum
above the floor and 11 inches in depth minimum at 9 in minimum
above the floor. The dip of the overflow shall be ignored when
checking the clearances. -- Sec. 4.20.3.1 & Fig. B4.20.3.1
11) A clear floor space of 30 X 48 inches minimum shall be provided
in front of the lavatory and shall extend 19 inches maximum
under the lavatory. -- Sec. 4.20.3.2 & Fig. B4.20.3.2
12) Water supply and drain pipes under lavatories shall be
insulated or otherwise treated to protect against contact.
-- Sec. 4.20.4
13) The bottom of mirror is required to be within 38 inches of
the floor. -- Sec. 4 16.6 & Fig. B4.20.3.1
Page # 11
Code review for:
Project Id.: Sherick Enter.
Address: 0150 County Rd. 126, New Castle, CO.
GLAZING REQUIREMENTS
All glazing in hazardous locations is required to be of safety
glazing material. -- Sec. 2406.3 & 2406.4
Locations:
1) Glazing in ingress and egress doors except jalousies.
2) Glazing in fixed and sliding panels of sliding door assemblies
and panels in swinging doors other than wardrobe doors.
3) Glazing in storm doors.
4) Glazing in all unframed swinging doors.
5) Glazing in doors and enclosures for hot tubs, whirlpools, saunas,
steam rooms, bathtubs and showers. Glazing in any portion of a
building wall enclosing these compartments where the bottom exposed
edge of the glazing is less than 60 inches above a standing surface
and drain inlet.
6) Glazing in fixed or operable panels adjacent to a door where the
nearest exposed edge of the glazing is within a 24 -inch arc of
either vertical edge of the door in a closed position and where the
bottom exposed edge of the glazing is less than 60 inches above the
walking surface.
7) Glazing in an individual fixed or operable panel, other than those
locations described in items 5 and 6 above, than meets all of the
following conditions:
A. Exposed area of an individual pane greater than 9 square feet.
B. Exposed bottom edge less than 18 inches above the floor.
C. Exposed top edge greater than 36 inches above the floor.
D. One or more walking surfaces within 36 inches horizontally of
the plane of the glazing.
8) Glazing in railings regardless of height above a walking surface.
Included are structural baluster panels and nonstructural in -fill
panels.
9) Glazing in walls and fences used as the barrier for indoor and
outdoor swimming pools and spas when the bottom edges is less than
60 inches above the pool side and the glazing is within 5 feet
of the pool or spa water's edge.
10) Glazing in walls enclosing stairway landings or within 5 feet of
then bottom and top of stairways where the bottom edge is less
than 60 inches above the walking surface.
PLAN REVIEW CHECKLIST
Applicant`s ICi( Date i o e4
Building
`-/ Engineered Foundation ((��
Driveway Permit tftW rid J' ti
Lurveyed Site Plan
`/Septic Permit and Setbacks
✓ Grade/Topography 30%
giLAttach Residential Plan Review List
✓Minimum Application Questionnaire
<Li. Subdivision Plat Notes
goi Fire Department Review
,/Galuation Determination/Fees
✓Red Line Plans/Stamps/Sticker
YAttach Conditions
✓ Application Signed
if n Reviewer To Sign Application
cel/Schedule No.
40# Snowload Letter- Manf. Hms.
GENERAL NOTES:
Planning/Zoning
Property Line tbacks
30ft Stream setbacks
Flood Pl. n
Buildi ' g Height
Zo ' g Sign -off
ad Impact Fees
OA/DRC Approval
Grade/Topography 40%
Planning Issues
Subdivision Plat Notes
Date Rec. ; r) V PERMIT # ,S J 7 S /
Contractor/Home Owner: 2.e 1.0,' Pu
Address:
1(". Ir go Al
TYPE OF INSPECTION:
Partial Rough in Underground
ACTION: Accepted i Rejected
REINSPECTION FEE
Comments or Corrections: � ' i
Final L --
Remarks
(J J2, ✓1 �G,Y v�X/�per✓
(7) 1 1-7 c� c ILS_ i a1
1!/
t
Inspector's Name
Phone # Date h' - le 01/
FORMS: EBINSP NOTICE. DOC
WEST SLOPE TESTING & INSPECTION
3177 Glendam Dr
RECEInd Junction, CO 81504
Phone: 970-434-6988
JUL 1 9 2004
GARFIELD COUNTY Cell: 970-260-2844
BUILDING & PLANNING
7-14-04 Page 1 of 1
Andrew Schwaller
Building Official
108 8th st., suite 201
Glenwood Springs, CO 81601
Please find enclosed special inspection report for the metal
building @ 32150 River Frontage Rd.
Thank You; Doug Young
West Slope Testing & Inspection
3177 Glendam Dr.
Grand Junction, CO 81504
Phone: 970-434-6988
Cell: 970-260-2844
Inspection Report
Report #1
Page 1 of 1
Date: 7-13-04
Project: Building # 2
Address: 32150 River Frontage Rd. New Castle CO
Building Permit No: 9097
General Contractor: Sherick Enterprises LLC
Contractor that Performed Work: TPI Metal Buildings
Inspection of shop fabrication or field work at job site: Field
Report: Tested some sample bolts in a Skidmore -Wilhelm bolt tension
testing device to determine the testing torque required for the 3/4" &
5/8" diameter A325 bolts used in the main frame & end wall
connections. After the testing torque was determined I proceeded to test
& inspect the high strength bolting at the main frame & end wall
connections. After testing a few connections it was determined that the
bolts had not been fully tightened at some of the connections, so the steel
erector went back over all of the connections using the testing torque
determined above with the calibrated torque wrench while I observed the
tightening in process. After the bolts were retightened the bolting
inspected above was found to be in compliance with the UBC, IBC, and
the AISC Specification for Structural Joints Using ASTM A325 or A490
Bolts. To the best of my knowledge this completes the special inspection
of the high strength bolting at the structural steel frame for this project.
Inspector/Technician: Douglas E Young I r
or\ bkrAws"
GARFIELD COUNTY B LDING AND SANITATION DEPARTMENTPermit Nr 3 9 41
109 8th Street Suite 303
Glenwood Springs, Colorado 81601
Phone (303) 945-8212
INDIVIDUAL SEWAGE DISPOSAL PERMIT
PROPERTY
Owner's Name, U.'1' (C k ent
I AddresaLt Phone -2" ti5_ a:71
Q
System Location Rwor fr-nir 'e_QA�. La -1St&
Legal Description of Assessor's Parcel No j//— Cc' CJ-0J4/Q
Assessor's Parcel No.
This does not constitute
a building or use permit.
SYSTEM DESIGN
Septic Tank Capacity (gallon) Other
Percolation Rate (minutes/inch) Number of Bedrooms (or other)
Required Absorption Area - See Attached % �, (,',
Special Setback Requirements: 1
Date Inspector
FINAL SYSTEM INSPECTION AND APPROVAL (as installed)
Call for Inspection (24 hours notice) Before Covering Installation
System Installer
Septic Tank Capacity
Septic Tank Manufacturer or Trade Name -
Septic Tank Access within 8" of surface
Absorption Area
Absorption Area Type and/or Manufacturer or Trade Name
Adequate compliance with County and State regulations/requirements
Other
Date 1) Inspector -' /t" .D! A- CYnA030-6.. 141....ft . (16 (-2Wr I"Z L
RETAIN WITH RECEIPT RECORdS AT CONSTRUCTION SITE
•CONDITIONS:
1. All installation must comply with all requirements of the Colorado State Board of Health Individual Sewage Disposal Systems Chapter
25, Article 10 C.R.S. 1973, Revised 1984.
2. This permit is valid only for connection to structures which have fully complied with County zoning and building requirements. Con-
nection to or use with any dwelling or structures not approved by the Building and Zoning office shall automatically be a violation or a
requirement of the permit and cause for both legal action and revocation of the permit.
3. Any person who constructs,alters, or installs an individual sewage disposal system in a manner which involves a knowing and material
variation from the terms or specifications contained in the application of permit commits a Class I, Petty Offense ($500.00 fine — 6
months in jail or both).
White - APPLICANT Yellow - DEPARTMENT
•
COUNTY OF GARFIELD - BUILDING DEPARTMENT
CORRECTION NOTICE
108 8th St., Suite 201 Glenwood Springs, Colorado
Phone (970) 945-8212
Job located at J O/gb 7��D /� �► ,
Permit No. 9Qt 1
I have this day inspected this structure and these
premises and found the following corrections needed:
(QUO 944zCr
691 ALA-ee
d4)
is &a-
�, io 4
;et_
You are hereby notified that the above correction must be inspected
before covering.
When correction(s) have been made, call for ins ection at 970-384-5003.
Date /- / — 20 0
Building Inspector
Phone (970) 945-8212
No. 1ngi
Assessor's Parcel No CRIB(' DS4 a -
Date c )g_
c� (} [n1,ER AD /I
Job Addrre�s?) RV 2 iR L?FSI BUILDIG PL1 CAR
/•J
Owner
curt oK RA423-pelSeS Ad ress6t, t2&
Contractor Ot-crier
Setbacks:iron
O11C
Rear
Soils Test
Footing 5=2ti-6y
Foundationlir7-007
Grout
Underground Plu bin
Rough Plumb�in��
Framing 7-1-�-O
Insulation ��
Address
94/5'-;77/
Phone #rimi7_'-3__
Phone #
RH LH
&ft a� Zoning-$
INSP'ECTIONO f
Roofing
Drywall 7 -%-0/01U*//50¢
Gas Piping G 1'°'/fU-
/2 dib
54, 24'16
Weatherproofing
Mechanical k! 6/
2 S -9 -0e -a --
Electrical Rough (Sta )
Electrical mal tat
Fina'�jl,ecklist Completed?
Certificate Occupancy #
Date
Septic System #
Date &I8-
Final/7 13'
Other
(continue on back)
INSPECTION WILL NOT BE MADE UNLESS
• -THIS CARD IS POSTED ON THE JOB
24 HOURS NOTICE REQUIRED FOR INSPECTIONS
Date Issue
BUILDING PERMIT
GARFIELD COUNTY, COLORADO
Zoned Area Permit No CtZ...AqR
1
AGREEMENT
In consideration of the issuance of this permit, the applicant hereby agrees to comply with all
laws and regulations related to the zoning, location; construction and erection of the proposed
structure for which this permit is granted, and further agrees that if the above said regulations
are not fully complied with in the zoning, location,. erection and construction of the above
described structure, the permit may then be revoked by notice from the County Building
Inspector and IMMEDIATELLBECOME NULL AND VOID.
Setbacks Front Side Side Rear
This Card Must Be Posted So It is Plainly Visibk From The Street Until Final Inspection.
INSPECTION RECORD
Footing
S_ off_
Y
Foundation iry— Z -e ./ '
Underground Plumbing, - fu
-p
Insulation /j--il o•fQnw-
Rough Plumbing ?4$41)6 '- j»
Drywall 1-3o-tV, 1( gg66. -0q #
Chimney & Vent a-13-oElectric
Final (by State Inspectori/14 y° , °IC
Gas Piping gei a T
Final f2 43-p jam -
Electric Rough (By State Inspector)
Septic Final R , frac � .-/ate(`
�"
Framing? -2S1 t 4- y'-OV.Ofw-
(To include Roof in place and Windows
and Doors installed).
#UI2tefi D
ALL LISTED ITEMS MUST BE INSPECTED AND APPROVED BEFORE COVERING -
WHETHER INTERIOR OR EXTERIOR, UNDERGROUND OR ABOVE GROUND.
Phone 384-5003
THIS PERMIT IS NOT TRANSFERABLE
109 8th Street County Courthouse Glenwood Springs, Colorado.
APPROVEDDO NOT DESTROY THIS CARD
Dat N:/.►; By
I PLACED OUTSIDE'- CbVER WITH CLEAR PLASTIC