HomeMy WebLinkAboutState Electrical Inspection 12.01.2015Time Page 1 of 1
COLORADO STATE ELECTRICAL BOARD
1560 Broadway, Suite 1350
Denver, CO 80202
Inspection Report
Date Inspected: 12/01/2015
Permit Th 782997
Permit Magnum Electric Company Inc. Jeffrey Anderson
Holder:
PO Box 2225 Grand Junction 815022225
Phone: (970) 243-6655 Fax: Email: jeffnanderson@magnum-electric.com
Site: Sec 28 TO7S R96W Scarrow Rd Travelers Highland Subdivision
Parachute, Garfield County, 81635
Owner: PLus 5 LLC
Status: Partial
Inspection Type: Rough In
NEW COMMERCIAL
Inspector: Norman Feck 303-869-3442
Corrections:
Equipment grounding conductor overlaps where it terminates under J boxes ground screw in
most locations at this job. This is seen as a violation for aluminum conductor connections on
switches and receptacles. See exhibits 110.3 and 110.4 of NEC Handbook speaking of
110.14 terminations. l do not see this copper conductor overlap as an NEC violation but
consider it a wrong practice for wire binding screws. Please terminate like exhibit 110.3 for
future installations.
Correction can be completed after wall board is in place
Comments:
1) Walls ok although note correction item of this report.
2) FYI for upcoming above grid inspection - Bushing required where cable runs wild from
phone/data raceways.
file:///C:/Users/Jeff/Documents/Plus%205%2OLLC/wall%20rough%20in.htm 12/2/2015