Loading...
HomeMy WebLinkAboutState Electrical Inspection 12.01.2015Time Page 1 of 1 COLORADO STATE ELECTRICAL BOARD 1560 Broadway, Suite 1350 Denver, CO 80202 Inspection Report Date Inspected: 12/01/2015 Permit Th 782997 Permit Magnum Electric Company Inc. Jeffrey Anderson Holder: PO Box 2225 Grand Junction 815022225 Phone: (970) 243-6655 Fax: Email: jeffnanderson@magnum-electric.com Site: Sec 28 TO7S R96W Scarrow Rd Travelers Highland Subdivision Parachute, Garfield County, 81635 Owner: PLus 5 LLC Status: Partial Inspection Type: Rough In NEW COMMERCIAL Inspector: Norman Feck 303-869-3442 Corrections: Equipment grounding conductor overlaps where it terminates under J boxes ground screw in most locations at this job. This is seen as a violation for aluminum conductor connections on switches and receptacles. See exhibits 110.3 and 110.4 of NEC Handbook speaking of 110.14 terminations. l do not see this copper conductor overlap as an NEC violation but consider it a wrong practice for wire binding screws. Please terminate like exhibit 110.3 for future installations. Correction can be completed after wall board is in place Comments: 1) Walls ok although note correction item of this report. 2) FYI for upcoming above grid inspection - Bushing required where cable runs wild from phone/data raceways. file:///C:/Users/Jeff/Documents/Plus%205%2OLLC/wall%20rough%20in.htm 12/2/2015