HomeMy WebLinkAboutSubsurface Investigation and OWTS Design 04.18.16 April 18, 2016 Project No. C1205 Betty Collins Bettyjocollins@hotmail.com Subsurface Investigation and Onsite Wastewater Treatment System Design 3-Bedroom Residence 5352 CR 233 Garfield County, Colorado Betty, ALL SERVICE septic, LLC performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 5.35-acre property is located outside of Rifle, in an area where OWTSs and wells are necessary. Legal Description: Section: 5 Township: 6 Range: 92 TR IN LOTS 3 & 4 Parcel ID: 217905200359 SITE CONDITIONS The property is currently developed with two residences. The 3-bedroom, single-family residence located on the northern portion of the property is utilizing an OWTS that is experiencing problems and must be replaced. The existing septic tank and soil treatment area (STA) will be abandoned in place. The private well on the property is located on the southeast corner of the residence. The well must be setback a minimum of 50-feet from the new, proposed septic tank and a minimum of 100-feet from the new proposed STA. The proposed STA will be located a minimum of 10 -feet from the west property boundary. The proposed STA location slopes slightly to the east. The proposed beds will run east to west; therefore, the beds may be stepped with the western bed slightly higher than the eastern bed in order to keep both beds as close to native grade as possible. Well location Page 2 SUBSURFACE The subsurface was investigated on April 10, 2016 by digging one soil profile test pit (Test Pit). The Test Pit was hand dug with a shovel to approximately 3.5-feet, and then a post-hole digger was used to excavate an additional foot to a maximum depth explored of 4.5-feet. Visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.1 The materials encountered in the Test Pit consisted of dark brown, moist silty clay loam to a maximum depth explored of 4.5-feet. No bedrock or groundwater was encountered, although the moisture content in the soil increased with depth. No mottling of the soils was observed. The pit was left open and monitored for one week (through April 17, 2016). No groundwater entered the pit during that time. A tactile analysis of the soils was taken from the Test Pit at approximately 1-foot below grade. The soil formed a ball and a ribbon 1 to 2-inches in length before breaking. Soil structure shape was blocky, soil structure grade was moderate, and consistence was firm. The texture of the soil was very smooth. STA sizing is based on Soil Type 3, Silty Clay Loam. For purposes of this design, we assume high groundwater at 4.5-feet below grade. A long term acceptance rate (LTAR) of 0.35 gallons per square foot will be used to design the OWTS, in accordance with Table 10-1 presented in the Garfield County On-Site Wastewater Treatment System Regulations, adopted April 14, 2014. Approximate area of proposed STA Test Pit location Ball and ribbon 1 to 2 inches in length 1 Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page 3 Test Pit hand dug to a max depth of 4.5-feet / no groundwater encountered DESIGN SPECIFICATIONS The existing septic tank and STA will be abandoned in place. The septic tank must be pumped, collapsed and remaining void filled with gravel, sand, or compacted soil. Design Calculations: Average Design Flow = 75 GPD x 2 people/bedroom x 3 Bedrooms = 450 GPD LTAR = 0.35 GPD/SF 450 GPD / 0.35 GPD/SF x 1.0 (pressure dosed beds) x 0.7 (chambers) = 900 SF The existing sewer line from the house to the septic tank must be explored and if found to be in poor condition, the line must be replaced using SDR-35 sewer line. A double-sweep clean out must be installed between the house and the septic tank. We recommend installing the clean out within 5-feet of the house. The new OWTS design is based on 3-bedrooms. An average daily wastewater flow of 450 GPD will be used. The system installation will include a 1250-gallon, two-compartment concrete septic tank with an Orenco® ProPak pumping system and PF5005 pump in the second compartment. Other pumps may be considered. The pump must be able to attain 37 gallons per minute (GPM) and 28 feet of Total Dynamic Head (TDH). The control panel for the pumping system must be installed within line of sight of the septic tank. The control panel must include a manual pump control and alarm on separate breakers. Floats for the pumping system must be set to deliver approximately 75 gallons each dose. Effluent will be pressure dosed through a 1.5-inch diameter pump line from the septic tank to an Orenco® model 6402 automatic distributing valve (ADV), which must be installed at a high point, insulated, and accessible from grade. The pump line must have a minimum 1% grade for proper drain back into the septic tank after each pump cycle. The STA will consist of two beds, each with 4 rows of 10 ‘Quick 4’ Infiltrator® chambers, for a total of 80 chambers and 960 square feet of infiltrative area. Existing vegetation should be scraped from each bed footprint and chambers installed as close to existing grade as possible. Chambers may not be installed more than 0.5-feet below grade. The beds may be set at different elevations to maintain installation as close to existing grade as possible. Chamber rows in each bed will be connected with a level, 1.5-inch diameter manifolds. Effluent will be pressure dosed to 1.5-inch diameter laterals, which must be suspended with zip ties from the underside of the chambers. Laterals will have 5/32-inch diameter orifices facing up, with the exception of the first and last holes facing down for drainage. The orifices must be placed 3-feet on center. Each lateral must end in a 90 degree ell facing up with a ball valve for flushing. Valves may be placed in a valve box, accessible from grade. Inspection ports must be placed at the beginning and end of each trench. Ports may be cut to grade and covered with a valve box for access. Page 4 Backfill over the chambers must be a 3-inch minus material or smaller, well draining and able to support vegetative growth (topsoil is recommended). A 3:1 slope (horizontal:vertical) beyond the bed is required; therefore, the basal area will extend 6-feet beyond the outside perimeter of the bed. The beds must be crowned in a manner to promote drainage off of the mounded area. The component manufacturers are typical of applications used by contractors and engineers in this area. Alternatives may be considered or recommended by contacting our office. Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the absorption area. No heavy equipment, machinery, or materials should be placed on backfilled STAs. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. Page 5 INSTALLATION OBSERVATIONS ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL SERVICE septic, LLC should be notified 48 hours in advance to observe the installation. LIMITS: The design is based on information submitted. If soil conditions encountered are differen t from conditions described in report, ALL SERVICE septic, LLC should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, ALL SERVICE septic, LLC Reviewed By: Carla Ostberg, MPH, REHS Introduction Orenco’s automatic distributing valve assemblies, pressurized with small high-head effluent pumps, are useful for distributing effluent to multiple zones. These zones can be segments of sand filter manifolds, drainfields, or other effluent distribution systems. Distributing valve assemblies can substantially simplify the design and installation of a distribution sys- tem and reduce installation costs. This is particularly true where a distributing valve assem- bly is used instead of multiple pumps and/or electrically operated valves. Additionally, a reduction in long term operation and maintenance costs is realized due to a reduced size and/or number of pumps. More even distribution can be achieved on sloping sites by zoning laterals at equal elevations. This eliminates drainback to lower lines and the unequal distrib- ution of effluent that occurs at the beginning of a cycle. Valve Operation The valve itself has only a few moving parts, requires no electricity, and alternates automati- cally each cycle. Refer to Figure 1 for the following valve operation description. The flow of the incoming effluent forces the rubber flap disk 1 to seat against the valve bottom 2. The opening 3 in the rubber flap disk aligns with an opening in the valve bottom to allow flow to only one valve outlet. The stem 4 houses a stainless steel spring which pushes the rubber flap disk away from the valve bottom after the flow of effluent stops. The stem acts as a cam follower and rotates the rubber flap disk as the stem is raised and lowered through the cam 5. The force from the flow of effluent pushes the stem down through the cam and the stainless steel spring pushes the stem back up through the cam when the flow of effluent stops. Each linear motion of the stem allows the rubber flap disk to rotate half the distance necessary to reach the next outlet. When there is no flow, the rubber flap disk is in the “up” position and is not seated against the valve bottom. 5 4 3 2 1 Inlet Outlets Figure 1: 6000 Series Valve Orenco Automatic Distributing Valve Assemblies NTP-VA-1 Rev. 1.2, © 11/03 Orenco Systems®, Inc. Page 1 of 6 For Wastewater Effluent Systems This article may describe design criteria that was in effect at the time the article was written. FOR CURRENT DESIGN CRITERIA, call Orenco Systems, Inc. at 1-800-348-9843. The Distributing Valve Assembly The Orenco Automatic Distributing Valve Assembly combines the distributing valve itself and sever- al other components to give a complete preassembled unit that is easy to install, monitor, and main- tain. Figure 2 shows a complete assembly. Because distributing valves with several outlets can be difficult to line up and glue together in the field, the discharge lines in the assemblies are glued in place at Orenco. The unions (1) allow removal and maintenance of the valve. The clear PVC pipe sections (2) give a visual check of which discharge line is being pressurized. The inlet ball valve (3) allows a quick, simple method to test for proper valve cycling. The ball valve also stops the flow of effluent in case the pump is activated unexpectedly during maintenance or inspection. Check valves may be necessary on the discharge lines. Use of check valves is discussed in the valve positioning section. Valve Assembly Hydraulics Liquid flowing through the valve assembly must pass through fairly small openings and make several changes in direction. Because of this, headlosses through the valve assembly are fairly high. Table 1 gives the headloss equations for several different assemblies and Figure 3 shows the graphical repre- sentations of these equations. Orenco recommends that high-head turbine pumps be used to pressur- ize the valve assemblies to ensure enough head is available for proper system operation. High-head turbine pumps are also recommended because the use of a distributing valve usually requires more frequent pump cycling. The high-head turbine pumps are designed for high cycling systems and will outlast conventional effluent pumps by a factor of 10 or more in a high cycling mode. Furthermore, the high-head turbine pump intake is 12 inches or more above the bottom of the pump and tends to prevent any settled solids from being pumped into the distribution valve and obstructing its opera- tion. A minimum flow rate through the distributing valve is required to ensure proper seating of the rubber flap disk. Minimum flow rates for the various models are given in Table 1. Figure 2: Orenco Distributing Valve Assembly (6000 Series Valve) NTP-VA-1 Rev. 1.2, © 11/03 Orenco Systems®, Inc. Page 2 of 6 Table 1. Automatic Distributing Valve Assembly Headloss Equations Model Series Equation Operating Range (gpm) V4400A HL = 0.085 x Q1.45 10 - 40 V4600A HL = 0.085 x Q1.58 10 - 25 V6400A HL = 0.0045 x Q2 + 3.5 x (1 - e-0.06Q) 15 - 70 V6600A HL = 0.0049 x Q2 + 5.5 x (1 - e-0.1Q) 15 - 70 NTP-VA-1 Rev. 1.2, © 11/03 Orenco Systems®, Inc. Page 3 of 6 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 Flow (gpm) He a d L o s s T h r o u g h A s s e m b l y ( f t . ) V4600A V4400A V6600A V6400A The Pumping System Although the distributing valve was designed for the irrigation industry, it has started to gain fairly wide acceptance in the effluent pumping industry. However, because of the mechanical movements of the valve, it is necessary to take steps to prevent solids from reaching the distributing valve that may impede the operation of the valve. Orenco Biotube®Pump Vaults — when properly sized and installed — provide the necessary protection to prevent valve malfunction. The Biotube®pump vault accepts effluent only from the clear zone between a tank’s scum and sludge layers and then filters this effluent through a very large surface area screen cartridge. Without this protection in effluent systems, the valve has very little chance of reliable long-term operation. Figure 3: Automatic distributing valve assembly headloss curves Valve Positioning The physical position of the valve in relation to the pump and the discharge point is very important for proper valve operation. The most reliable operation occurs when the valve is placed at the high point in the system and as close to the pump as possible. The transport line between the pump and valve should be kept full if possible. If the line is empty at the beginning of each cycle, pockets of air during filling can cause random rotation of the valve. The valve is particularly vulnerable to this erratic rotation with empty lines that are long and not laid at a constant grade. An ideal valve loca- tion is shown in Figure 4. If the final discharge point is more than about 2 feet above the valve and the system does not drain back into the dosing tank, check valves should be installed on the lines immediately following the valve and a pressure release hole or line should be installed just prior to the valve. This pressure release hole or line can go into a return line to the dosing tank or to a “minidrainfield” near the valve. In order for the valve to rotate reliably, no more than about 2 feet of head should remain against the valve to allow the rubber flap disk to return to its up position. In many cases, it may take from one minute to several minutes for the pressure in the valve to be lowered enough for proper rotation to occur. Special care should be taken when installing systems controlled by programmable timers to ensure cycling does not occur too rapidly. Figure 5 illustrates a valve assembly using check valves. Pumping downhill to the valve should be avoided unless the transport line is very short and the ele- vation between the discharge line out of the tank and the valve is less than about 2 feet. If the valve is located many feet below the dosing tank, random cycling may occur while the transport line drains through the valve at the end of the cycle. A pressure sustaining valve located just before the distrib- uting valve may overcome this problem in some instances. Dosing Tank Discharge Laterals Distributing Valve Assembly Transport Line Figure 4: Ideal valve location NTP-VA-1 Rev. 1.2, © 11/03 Orenco Systems®, Inc. Page 4 of 6 System Startup Refer to the Hydrotek Valve booklet that is provided with the distributing valve assembly for the sequencing of the valve outlets. The transport line should always be flushed with clean water before installing the valve. Any sand, gravel, or other foreign objects that may have been in the pipe during installation can easily become lodged in the distributing valve, causing malfunction. With the pump running, alternately close and open the ball valve on the distributing valve assembly to check proper rotation of the valve. (Note: If check valves are used on the lines after the distribut- ing valve, the pump may need to be turned on and off to allow the pressure to be released from the valve.) If visual operation of which zone is operating is not possible, watch the clear pipe on each line for indication of which zone is operating. Maintenance Annually check for proper operation by following procedures listed in the Hydrotek Valve booklet and system startup procedures listed above. Troubleshooting 1. PROBLEM: Valve does not change or cycle to next zone or outlet CAUSE: The stem and disk assembly is not rotating when water flow is turned off and then back on. SOLUTION 1: Ensure that there is no debris inside the cam. Clean and carefully reinstall the cam. SOLUTION 2: If fewer than the maximum number of outlets are being used, check the installation of the cam. Ensure that the stem and disk assembly is not being held down by an improperly installed cam. Refer to the cam replacement instructions. h Check Valves if h>2'-0" Distributing Valve Assembly Transport Line Dosing Tank Pressure Release Line if h>2'-0" Discharge Laterals Figure 5: Valve assembly below final discharge point NTP-VA-1 Rev. 1.2, © 11/03 Orenco Systems®, Inc. Page 5 of 6 SOLUTION 3: Remove the valve top and check for proper movement of stem and disk assembly. Check for and remove any debris or foreign objects that may jam or retard the movement of the disk. SOLUTION 4: Check for freedom of movement of stem and disk assembly up and down over the center pin in bottom of valve. Scale deposits may build up on the pin and hold stem and disk assembly down. Clean pin and again check for freedom of movement. SOLUTION 5: Be sure that all operating outlets are not capped and that the flow to operating zones is not restricted in any manner. This would cause pressure to build up in the valve and lock the stem and disk assembly in the down position. SOLUTION 6: The backflow of water from uphill lines may be preventing the valve from cycling properly. This can happen when the valve is placed too far below an elevated line. If the valve cannot be placed close to the high point of the system, a check valve should be installed near the valve in the outlet line that runs uphill from the valve and a drain line installed just prior to the valve to relieve the pressure. 2. PROBLEM: Water comes out of all the valve outlets CAUSE: Stem and disk assembly not seating properly on valve outlet. SOLUTION 1: Check for sufficient water flow. A minimum flow rate is required to properly seat the disk as shown in Table 1. SOLUTION 2: Remove the valve top and check the inside walls to ensure that nothing is interfering with the up and down movement of the stem and disk assembly inside the valve. SOLUTION 3: Make sure that the operating outlets are not capped and that the flow to the operat- ing zones are not restricted in any manner. 3. PROBLEM: Valve skips outlets or zones CAUSE: Pumping into an empty transport line — especially downhill — may cause the valve to skip outlets from pockets of air allowing the rubber flap disk to raise during a cycle. SOLUTION 1: Keep the transport line full. SOLUTION 2: If the line must remain empty between cycles, use a larger diameter transport line laid at a constant grade to prevent air pockets from forming. CAUSE: The stem and disk assembly is being advanced past the desired outlet. SOLUTION 1: Ensure that the correct cam for the desired number of zones is installed and that the outlet lines are installed to the correct outlet ports of the valve as indicated by the zone numbers on the top of the cam. NTP-VA-1 Rev. 1.2, © 11/03 Orenco Systems®, Inc. Page 6 of 6 Distributing Valves General Orenco’s Automatic Distributing Valve Assemblies are mechanically operated and sequentially redirect the pump’s flow to multiple zones or cells in a distribution field. Valve actuation is accomplished by a combination of pressure and flow. Automatic Distributing Valve Assemblies allow the use of smaller horsepower pumps on large sand filters and drainfields. For example, a large community drainfield requiring 300 gpm can use a six-line Valve Assembly to reduce the pump flow rate requirement to only 50 gpm. Orenco only warrants Automatic Distributing Valves when used in conjunction with High-Head Effluent Pumps with Biotube®Pump Vaults to provide pressure and flow requirements, and to prevent debris from fouling valve operation. An inlet ball valve and a section of clear pipe and union for each outlet are provided for a complete assembly that is easy to maintain and monitor. Ideal valve location is at the high point in the system. Refer to Automatic Distributing Valve Assemblies (NTP-VA-1) for more information. Standard Models V4402A, V4403A, V4404A, V4605A, V4606A, V6402A, V6403A, V6404A, V6605A, V6606A. Nomenclature Submittal Data Sheet Side View ball valve elbow Top View coupling clear pipe distributing valve union Bottom View elbows Specifications Materials of Construction All Fittings: Sch. 40 PVC per ASTMspecification Unions: Sch. 80 PVCper ASTMspecification Ball Valve: Sch. 40 PVCper ASTMspecification Clear Pipe: Sch. 40 PVCper ASTMspecification V4XXX Distributing Valves: High-strength noncorrosive ABSpolymer and stainless steel V6XXX Distributing Valves: High-strength noncorrosive ABSpolymer, stainless steel, and die cast metal NSU-SF-VA-1 Rev. 3.0, © 4/03 Page 1 of 2 Applications Automatic Distributing Valve Assemblies are used to pressurize multiple zone distribution systems including textile filters, sand filters and drainfields. V Indicates assembly Model series: 44 = 4400 series (2-4 outlets) 46 = 4600 series (5-6 outlets) 64 = 6400 series (2-4 outlets) 66 = 6600 series (5-6 outlets) Distributing valve Number of active outlets A Distributing Valves (continued) Flow (gpm) He a d L o s s T h r o u g h A s s e m b l y ( f t . ) 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 0 5 10 15 20 25 30 35 V4400A V6600A V6400A V4600A NSU-SF-VA-1 Rev. 3.0, © 4/03 Page 2 of 2 Model Inlet Size (in.) Outlets Size (in.) Flow range (gpm) Max Head (ft.) Min. Enclosure V4402A 1.25 1.25 10 - 40 170 VB1217 V4403A 1.25 1.25 10 - 40 170 VB1217 V4404A 1.25 1.25 10 - 40 170 VB1217 V4605A 1.25 1.25 10 - 25 170 RR2418 V4606A 1.25 1.25 10 - 25 170 RR2418 V6402A 1.5 1.5 15 - 100 345 RR2418 V6403A 1.5 1.5 15 - 100 345 RR2418 V6404A 1.5 1.5 15 - 100 345 RR2418 V6605A 1.5 1.5 15 - 100 345 RR2418 V6606A 1.5 1.5 15 - 100 345 RR2418 Pump Selection for a Pressurized System - Single Family Residence Project Collins Residence / 5352 CR 233 Parameters Discharge Assembly Size Transport Length Before Valve Transport Pipe Class Transport Line Size Distributing Valve Model Transport Length After Valve Transport Pipe Class Transport Pipe Size Max Elevation Lift Manifold Length Manifold Pipe Class Manifold Pipe Size Number of Laterals per Cell Lateral Length Lateral Pipe Class Lateral Pipe Size Orifice Size Orifice Spacing Residual Head Flow Meter 'Add-on' Friction Losses 2.00 10 40 1.50 6402 50 40 1.50 5 9 40 1.50 8 40 40 1.50 5/32 3 5 None 0 inches feet inches feet inches feet feet inches feet inches inches feet feet inches feet Calculations Minimum Flow Rate per Orifice Number of Orifices per Zone Total Flow Rate per Zone Number of Laterals per Zone % Flow Differential 1st/Last Orifice Transport Velocity Before Valve Transport Velocity After Valve 0.68 56 37.9 4 0.8 6.0 6.0 gpm gpm % fps fps Frictional Head Losses Loss through Discharge Loss in Transport Before Valve Loss through Valve Loss in Transport after Valve Loss in Manifold Loss in Laterals Loss through Flowmeter 'Add-on' Friction Losses 2.9 0.8 9.6 4.0 0.2 0.1 0.0 0.0 feet feet feet feet feet feet feet feet Pipe Volumes Vol of Transport Line Before Valve Vol of Transport Line After Valve Vol of Manifold Vol of Laterals per Zone Total Vol Before Valve Total Vol After Valve 1.1 5.3 0.9 16.9 1.1 23.2 gals gals gals gals gals gals Minimum Pump Requirements Design Flow Rate Total Dynamic Head 37.9 27.6 gpm feet 0 10 20 30 40 50 60 70 80 0 20 40 60 80 100 120 140 160 Net Discharge (gpm) PumpData PF5005 High Head Effluent Pump 50 GPM, 1/2HP 115/230V 1Ø 60Hz, 200/230V 3Ø 60Hz PF5007 High Head Effluent Pump 50 GPM, 3/4HP 230V 1Ø 60Hz, 200/230/460V 3Ø 60Hz PF5010 High Head Effluent Pump 50 GPM, 1HP 230V 1Ø 60Hz, 200/460V 3Ø 60Hz PF5015 High Head Effluent Pump 50 GPM, 1-1/2HP 230V 1Ø 60Hz, 200V 3Ø 60Hz Legend System Curve: Pump Curve: Pump Optimal Range: Operating Point: Design Point: Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-BPP-1 Rev. 1.2, © 08/14 Page 1 of 4 Biotube® ProPak Pump Package™ Technical Data SheetOrenco® 60-Hz Series Pump Packages General Orenco’s Biotube® ProPak™ is a complete, integrated pump package for filtering and pumping effluent from septic tanks. And its patented pump vault technology eliminates the need for separate dosing tanks. This document provides detailed information on the ProPak pump vault and filter, 4-in. (100-mm) 60-Hz turbine effluent pump, and control panel. For more information on other ProPak components, see the following Orenco technical documents: • Float Switch Assemblies (NSU-MF-MF-1) • Discharge Assemblies (NTD-HV-HV-1) • Splice Boxes (NTD-SB-SB-1) • External Splice Box (NTD-SB-SB-1) Applications The Biotube ProPak is designed to filter and pump effluent to either gravity or pressurized discharge points. It is intended for use in a septic tank (one- or two-compartment) and can also be used in a pump tank. The Biotube ProPak is designed to allow the effluent filter to be removed for cleaning without the need to remove the pump vault or pump, simpli- fying servicing. Complete packages are available for on-demand or timed dosing sys- tems with flow rates of 20, 30, and 50-gpm (1.3, 1.9, and 3.2 L/sec), as well as with 50 Hz and 60 Hz power supplies. Standard Models BPP20DD, BPP20DD-SX, BPP30TDA, BPP30TDD-SX, BBPP50TDA, BPP50TDD-SX Product Code Diagram Biotube® ProPak™ pump package components. 4-in. (100-mm) turbine effluent pump Pump motor Pump liquid end Pump vault Support pipe Discharge assembly Float collar Float stem Floats Float bracket Biotube® filter cartridge Vault inlet holes External splice box (Optional; internal splice box comes standard.) Riser lid (not included) Riser (not included) Control panel BPP Pump flow rate, nominal: 20 = 20 gpm (1.3 L/sec) 30 = 30 gpm (1.9 L/sec) 50 = 50 gpm (3.2 L/sec) Control panel application: DD = demand-dosing TDA = timed-dosing, analog timer TDD = timed dosing, digital timer, elapsed time meter & counters Standard options: Blank = 57-in. (1448-mm) vault height, internal splice box, standard discharge assembly 68 = 68-in. (1727-mm) vault height SX = external splice box CW = cold weather discharge assembly DB = drainback discharge assembly Q = cam lock MFV = non-mercury float - Biotube® ProPak™ pump vault Technical Data SheetOrenco® Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-BPP-1 Rev. 1.2, © 08/14 Page 2 of 4 ProPak™ Pump Vault Materials of Construction Vault body Polyethylene Support pipes PVC Dimensions, in. (mm) A - Overall vault height 57 (1448) or 68 (1727) B - Vault diameter 17.3 (439) C - Inlet hole height 19 (475) D - Inlet hole diameter (eight holes total) 2 (50) E - Vault top to support pipe bracket base 3 (76) F - Vault bottom to filter cartridge base 4 (102) ProPak™ pump vault (shown with Biotube filter and effluent pump) Biotube® Filter Cartridge Materials of Construction Filter tubes Polyethylene Cartridge end plates Polyurethane Handle assembly PVC Dimensions, in. (mm) A - Cartridge height 18 (457) B - Cartridge width 12 (305) Performance Biotube® mesh opening 0.125 in. (3 mm)* Total filter flow area 4.4 ft2 (0.4 m2) Total filter surface area 14.5 ft2 (1.35 m2) Maximum flow rate 140 gpm (8.8 L/sec) *0.062-in. (1.6-mm) filter mesh available Biotube® filter cartridge (shown with float switch assembly) AA D E B B C E Technical Data Sheet Orenco® Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-BPP-1 Rev. 1.2, © 08/14 Page 3 of 4 Pump Curves Pump curves, such as those shown here, can help you determine the best pump for your system. Pump curves show the relationship between flow (gpm or L/sec) and pressure (TDH), providing a graphical representation of a pump’s performance range. Pumps perform best at their nominal flow rate, measured in gpm or L/sec. 4-in. (100-mm) Turbine Effluent Pumps Orenco’s 4-in. (100 mm) Turbine Effluent Pumps are constructed of lightweight, corrosion-resistant stainless steel and engineered plastics; all are field-serviceable and repairable with common tools. All 60-Hz PF Series models are CSA certified to the U.S. and Canadian safety standards for effluent pumps, and meet UL requirements. Power cords for Orenco’s 4-in. (100-mm) turbine effluent pumps are Type SOOW 600-V motor cable (suitable for Class 1, Division 1 and 2 applications). Materials of Construction Discharge: Stainless steel or glass-filled polypropylene Discharge bearing: Engineered thermoplastic (PEEK) Diffusers: Glass-filled PPO Impellers: Acetal (20-, 30-gmp), Noryl (50-gpm) Intake screens: Polypropylene Suction connection: Stainless steel Drive shaft: 300 series stainless steel Coupling: Sintered 300 series stainless steel Shell: 300 series stainless steel Lubricant: Deionized water and propylene glycol Specifications Nom. flow, Length Weight Discharge Impellers gpm (L/sec) in. (mm) lb (kg) in., nominal 1 20 (1.3) 22.5 (572) 26 (11) 1.25 4 30 (1.9) 21.3 (541) 25 (11) 1.25 3 50 (3.2) 20.3 (516) 27 (12) 2.00 2 Performance Nom. flow, hp (kW) Design Rated Min liquid gpm (L/sec) flow amps cycles/day level, in. (mm) 2 20 (1.3) 0.5 (0.37) 12.3 300 18 (457) 30 (1.9) 0.5 (0.37) 11.8 300 20 (508) 50 (3.2) 0.5 (0.37) 12.1 300 24 (610) 1 Discharge is female NPT threaded, U.S. nominal size, to accommodate Orenco® discharge hose and valve assemblies. Consult your Orenco Distributor about fittings to connect discharge assemblies to metric-sized piping. 2 Minimum liquid level is for single pumps when installed in an Orenco Biotube® ProPak™ Pump Vault. 10 20 30 40 6050 70 0.63 1.26 1.89 2.52 3.793.15 4.42 140 120 100 80 60 40 20 Flow in gallons per minute (gpm) Flow in liters per second (L/sec) To ta l d y n a m i c h e a d ( T D H ) i n f e e t To ta l d y n a m i c h e a d ( T D H ) i n m e t e r s PF 500511 43 37 30 24 18 12 6 PF 200511 PF 300511 Technical Data SheetOrenco® Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-BPP-1 Rev. 1.2, © 08/14 Page 4 of 4 AUTO OFF MAN NN1 Control Panel (Demand Dose) Orenco’s ProPak™ demand dose control panels are specifically engineered for the ProPak pump package and are ideal for applications such as demand dosing from a septic tank into a conventional gravity drainfield. Materials of Construction Enclosure UV-resistant fiberglass, UL Type 4X Hinges Stainless steel Dimensions, in. (mm) A - Height 11.5 (290) B - Width 9.5 (240) C - Depth 5.4 (135) Specifications Panel ratings 120 V, 3/4 hp (0.56 kW), 14 A, single phase, 60 Hz 1. Motor-start contactor 16 FLA, 1 hp (0.75 kW), 60 Hz; 2.5 million cycles at FLA (10 million at 50% of FLA) 2. Circuit 120 V, 10 A, OFF/ON switch, Single pole breakers 3. Toggle switch Single-pole, double-throw HOA switch, 20 A 4. Audio alarm 95 dB at 24 in. (600 mm), warble-tone sound, UL Type 4X 5. Audio alarm 120 V, automatic reset, DIN rail mount silence relay 6. Visual alarm 7/8-in. (22-mm) diameter red lens, “Push-to-silence,” 120 V LED, UL Type 4X Control Panel (Timed Dose) Orenco’s ProPak timed dose control panels are specifically engineered for the ProPak pump package and are ideal for applications such as timed dosing from a septic tank into a pressurized drainfield or mound. Analog or digital timers are available. Materials of Construction Enclosure UV-resistant fiberglass, UL Type 4X Hinges Stainless steel Dimensions, in. (mm) A - Height 11.5 (290) B - Width 9.5 (240) C - Depth 5.4 (135) Specifications Panel ratings 120 V, 3/4 hp (0.56 kW), 14 A, single phase, 60 Hz Dual-mode Programmable for timed- or demand-dosing (digital timed-dosing panels only) 1a. Analog timer 120 V, repeat cycle from 0.05 seconds to 30 (not shown) hours. Separate variable controls for OFF and ON time periods 1b. Digital timer 120-V programmable logic unit with built-in LCD (shown below) screen and programming keys. Provides control functions and timing for panel operation 2. Motor-start contactor 16 FLA, 1 hp (0.75 kW), 60 Hz; 2.5 million cycles at FLA (10 million at 50% of FLA) 3. Circuit breakers 120 V, 10 A, OFF/ON switch. Single pole 120 V 4. Toggle Switch Single-pole, double-throw HOA switch, 20 A 5. Audio alarm 95 dB at 24 in. (600 mm), warble-tone sound, UL Type 4X 6. Visual alarm 7/8-in. (22-mm) diameter red lens, “Push-to-silence”, 120 V LED, UL Type 4X Control panel, demand-dose Control panel, timed-dose (digital timer model shown) 1b 2 3 4 56 1 2 3 4 5 6 Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 1 of 6 PF Series 4-inch (100-mm) Submersible Effluent Pumps Technical Data SheetOrenco® Applications Our 4-inch (100-mm) Submersible Effluent Pumps are designed to transport screened effluent (with low TSS counts) from septic tanks or separate dosing tanks. All our pumps are constructed of lightweight, corrosion-resistant stainless steel and engineered plastics; all are field- serviceable and repairable with common tools; and all 60-Hz PF Series models are CSA certified to the U.S. and Canadian safety standards for effluent pumps, meeting UL requirements. Orenco’s Effluent Pumps are used in a variety of applications, including pressurized drainfields, packed bed filters, mounds, aerobic units, effluent irrigation, effluent sewers, wetlands, lagoons, and more. These pumps are designed to be used with a Biotube® pump vault or after a secondary treatment system. Features/Specifications To specify this pump for your installation, require the following: • Minimum 24-hour run-dry capability with no deterioration in pump life or performance* • Patented 1⁄8-inch (3-mm) bypass orifice to ensure flow recirculation for motor cooling and to prevent air bind • Liquid end repair kits available for better long-term cost of ownership • TRI-SEAL™ floating impeller design on 10, 15, 20, and 30 gpm (0.6, 1.0, 1.3, and 1.9 L/sec) models; floating stack design on 50 and 75 gpm (3.2 and 4.7 L/sec) models • Franklin Electric Super Stainless motor, rated for continuous use and frequent cycling • Type SOOW 600-V motor cable • Five-year warranty on pump or retrofit liquid end from date of manu- facture against defects in materials or workmanship * Not applicable for 5-hp (3.73 kW) models Standard Models See specifications chart, pages 2-3, for a list of standard pumps. For a complete list of available pumps, call Orenco. Product Code Diagram PF - Nominal flow, gpm (L/sec): 10 = 10 (0.6) 15 = 15 (1.0) 20 = 20 (1.3) 30 = 30 (1.9) 50 = 50 (3.2) 75 = 75 (4.7) Pump, PF Series Frequency: 1 = single-phase 60 Hz 3 = three-phase 60 Hz 5 = single-phase 50 Hz Voltage, nameplate: 1 = 115* 200 = 200 2 = 230† 4 = 460 Horsepower (kW): 03 = 1⁄3 hp (0.25) 05 = ½ hp (0.37) 07 = ¾ hp (0.56) 10 = 1 hp (0.75) 15 = 1-½ hp (1.11) 20 = 2 hp (1.50) 30 = 3 hp (2.24) 50 = 5 hp (3.73) Cord length, ft (m):‡ Blank = 10 (3) 20 = 20 (6) 30 = 30 (9) 50 = 50 (15) * ½-hp (0.37kW) only †220 volts for 50 Hz pumps ‡Note: 20-foot cords are available only for single-phase pumps through 1-½ hp Franklin Super Stainless Motor Franklin Liquid End Discharge Connection Bypass Orifice Suction Connection LR80980 LR2053896 Powered by Technical Data SheetOrenco® Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 2 of 6 Specifications, 60 Hz Pump Model PF100511 10 (0.6) 0.50 (0.37) 1 115 120 12.7 12.7 6 1 ¼ in. GFP 23.0 (660) 16 (406) 26 (12) 300 PF100512 10 (0.6) 0.50 (0.37) 1 230 240 6.3 6.3 6 1 ¼ in. GFP 23.0 (660) 16 (406) 26 (12) 300 PF10053200 10 (0.6) 0.50 (0.37) 3 200 208 3.8 3.8 6 1 ¼ in. GFP 23.0 (660) 16 (406) 26 (12) 300 PF100712 4, 5 10 (0.6) 0.75 (0.56) 1 230 240 8.3 8.3 8 1 ¼ in. GFP 25.9 (658) 17 (432) 30 (14) 300 PF10073200 4, 5 10 (0.6) 0.75 (0.56) 3 200 208 5.1 5.2 8 1 ¼ in. GFP 25.4 (645) 17 (432) 31 (14) 300 PF101012 5, 6 10 (0.6) 1.00 (0.75) 1 230 240 9.6 9.6 9 1 ¼ in. GFP 27.9 (709) 18 (457) 33 (15) 100 PF10103200 5, 6 10 (0.6) 1.00 (0.75) 3 200 208 5.5 5.5 9 1 ¼ in. GFP 27.3 (693) 18 (457) 37 (17) 300 PF102012 5, 6, 7, 8 10 (0.6) 2.00 (1.49) 1 230 240 12.1 12.1 18 1 ¼ in. SS 39.5 (1003) 22 (559) 48 (22) 100 PF102032 5, 6, 8 10 (0.6) 2.00 (1.49) 3 230 240 7.5 7.6 18 1 ¼ in. SS 37.9 (963) 20 (508) 44 (20) 300 PF10203200 5, 6, 8 10 (0.6) 2.00 (1.49) 3 200 208 8.7 8.7 18 1 ¼ in. SS 37.9 (963) 20 (508) 44 (20) 300 PF150311 15 (1.0) 0.33 (0.25) 1 115 120 8.7 8.8 3 1 ¼ in. GFP 19.5 (495) 15 (380) 23 (10) 300 PF150312 15 (1.0) 0.33 (0.25) 1 230 240 4.4 4.5 3 1 ¼ in. GFP 19.5 (495) 15 (380) 23 (10) 300 PF200511 20 (1.3) 0.50 (0.37) 1 115 120 12.3 12.5 4 1 ¼ in. GFP 22.3 (566) 18 (457) 25 (11) 300 PF200512 20 (1.3) 0.50 (0.37) 1 230 240 6.4 6.5 4 1 ¼ in. GFP 22.5 (572) 18 (457) 26 (12) 300 PF20053200 20 (1.3) 0.50 (0.37) 3 200 208 3.7 3.8 4 1 ¼ in. GFP 22.3 (566) 18 (457) 26 (12) 300 PF201012 4, 5 20 (1.3) 1.00 (0.75) 1 230 240 10.5 10.5 7 1 ¼ in. GFP 28.4 (721) 20 (508) 33 (15) 100 PF20103200 4, 5 20 (1.3) 1.00 (0.75) 3 200 208 5.8 5.9 7 1 ¼ in. GFP 27.8 (706) 20 (508) 33 (15) 300 PF201512 4, 5 20 (1.3) 1.50 (1.11) 1 230 240 12.4 12.6 9 1 ¼ in. GFP 34.0 (864) 24 (610) 41 (19) 100 PF20153200 4, 5 20 (1.3) 1.50 (1.11) 3 200 208 7.1 7.2 9 1 ¼ in. GFP 30.7 (780) 20 (508) 35 (16) 300 PF300511 30 (1.9) 0.50 (0.37) 1 115 120 11.8 11.8 3 1 ¼ in. GFP 21.3 (541) 20 (508) 28 (13) 300 PF300512 30 (1.9) 0.50 (0.37) 1 230 240 6.2 6.2 3 1 ¼ in. GFP 21.3 (541) 20 (508) 25 (11) 300 PF30053200 30 (1.9) 0.50 (0.37) 3 200 208 3.6 3.6 3 1 ¼ in. GFP 21.3 (541) 20 (508) 25 (11) 300 PF300712 30 (1.9) 0.75 (0.56) 1 230 240 8.5 8.5 5 1 ¼ in. GFP 24.8 (630) 21 (533) 29 (13) 300 PF30073200 30 (1.9) 0.75 (0.56) 3 200 208 4.9 4.9 5 1 ¼ in. GFP 24.6 (625) 21 (533) 30 (14) 300 PF301012 4 30 (1.9) 1.00 (0.75) 1 230 240 10.4 10.4 6 1 ¼ in. GFP 27.0 (686) 22 (559) 32 (15) 100 PF30103200 4 30 (1.9) 1.00 (0.75) 3 200 208 5.8 5.8 6 1 ¼ in. GFP 26.4 (671) 22 (559) 33 (15) 300 PF301512 4, 5 30 (1.9) 1.50 (1.11) 1 230 240 12.6 12.6 8 1 ¼ in. GFP 32.8 (833) 24 (610) 40 (18) 100 PF30153200 4, 5 30 (1.9) 1.50 (1.11) 3 200 208 6.9 6.9 8 1 ¼ in. GFP 29.8 (757) 22 (559) 34 (15) 300 PF301534 4, 5 30 (1.9) 1.50 (1.11) 3 460 480 2.8 2.8 8 1 ¼ in. GFP 29.5 (685) 22 (559) 34 (15) 300 PF302012 5, 6, 7 30 (1.9) 2.00 (1.49) 1 230 240 11.0 11.0 10 1 ¼ in. SS 35.5 (902) 26 (660) 44 (20) 100 PF30203200 5, 6 30 (1.9) 2.00 (1.49) 3 200 208 9.3 9.3 10 1 ¼ in. SS 34.0 (864) 24 (610) 41 (19) 300 PF303012 5, 6, 7, 8 30 (1.9) 3.00 (2.23) 1 230 240 16.8 16.8 14 1 ¼ in. SS 44.5 (1130) 33 (838) 54 (24) 100 PF303032 5, 6, 8 30 (1.9) 3.00 (2.23) 3 230 240 10.0 10.1 14 1 ¼ in. SS 44.3 (1125) 27 (686) 52 (24) 300 PF305012 5, 6, 7, 8 30 (1.9) 5.00 (3.73) 1 230 240 25.6 25.8 23 1 ¼ in. SS 66.5 (1689) 53 (1346) 82 (37) 100 PF305032 5, 6, 8 30 (1.9) 5.00 (3.73) 3 230 240 16.6 16.6 23 1 ¼ in. SS 60.8 (1544) 48 (1219) 66 (30) 300 PF30503200 5, 6, 8 30 (1.9) 5.00 (3.73) 3 200 208 18.7 18.7 23 1 ¼ in. SS 60.8 (1544) 48 (1219) 66 (30) 300 PF500511 50 (3.2) 0.50 (0.37) 1 115 120 12.1 12.1 2 2 in. SS 20.3 (516) 24 (610) 27 (12) 300 PF500512 50 (3.2) 0.50 (0.37) 1 230 240 6.2 6.2 2 2 in. SS 20.3 (516) 24 (610) 27 (12) 300 PF500532 50 (3.2) 0.50 (0.37) 3 230 240 3.0 3.0 2 2 in. SS 20.3 (516) 24 (610) 28 (13) 300 PF50053200 50 (3.2) 0.50 (0.37) 3 200 208 3.7 3.7 2 2 in. SS 20.3 (516) 24 (610) 28 (13) 300 PF500534 50 (3.2) 0.50 (0.37) 3 460 480 1.5 1.5 2 2 in. SS 20.3 (516) 24 (610) 28 (13) 300 PF500712 50 (3.2) 0.75 (0.56) 1 230 240 8.5 8.5 3 2 in. SS 23.7 (602) 25 (635) 31 (14) 300 PF500732 50 (3.2) 0.75 (0.56) 3 230 240 3.9 3.9 3 2 in. SS 23.7 (602) 25 (635) 32 (15) 300 PF50073200 50 (3.2) 0.75 (0.56) 3 200 208 4.9 4.9 3 2 in. SS 23.1 (587) 26 (660) 32 (15) 300 De s i g n g p m (L / s e c ) Ho r s e p o w e r (k W ) Ph a s e Na m e p l a t e vo l t a g e Ac t u a l v o l t a g e De s i g n f l o w am p s Ma x a m p s Im p e l l e r s Di s c h a r g e s i z e an d m a t e r i a l 1 Le n g t h , i n . ( m m ) Mi n . l i q u i d l e v e l , 2 in . ( m m ) We i g h t , 3 l b ( k g ) Ra t e d c y c l e s / d a y Technical Data Sheet Orenco® Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 3 of 6 Specifications, 60 Hz (continued) Pump Model PF500734 50 (3.2) 0.75 (0.56) 3 460 480 1.8 1.8 3 2 in. SS 34.8 (884) 25 (635) 31 (14) 300 PF501012 50 (3.2) 1.00 (0.75) 1 230 240 10.1 10.1 4 2 in. SS 27.0 (686) 26 (660) 35 (16) 100 PF50103200 50 (3.2) 1.00 (0.75) 3 200 208 5.7 5.7 4 2 in. SS 26.4 (671) 26 (660) 39 (18) 300 PF501034 50 (3.2) 1.00 (0.75) 3 460 480 2.2 2.2 4 2 in. SS 26.4 (671) 26 (660) 39 (18) 300 PF5015124 50 (3.2) 1.50 (1.11) 1 230 240 12.5 12.6 5 2 in. SS 32.5 (826) 30 (762) 41 (19) 100 PF501532004 50 (3.2) 1.50 (1.11) 3 200 208 7.0 7.0 5 2 in. SS 29.3 (744) 26 (660) 35 (16) 300 PF503012 4, 5, 7, 8 50 (3.2) 3.00 (2.23) 1 230 240 17.7 17.7 8 2 in. SS 43.0 (1092) 37 (940) 55 (25) 100 PF50303200 4, 5, 8 50 (3.2) 3.00 (2.23) 3 200 208 13.1 13.1 8 2 in. SS 43.4 (1102) 30 (762) 55 (25) 300 PF503034 4, 5, 8 50 (3.2) 3.00 (2.23) 3 460 480 5.3 5.3 8 2 in. SS 40.0 (1016) 31 (787) 55 (25) 300 PF505012 5,6,7,8 50 (3.2) 5.00 (3.73) 1 230 240 26.2 26.4 13 2 in. SS 65.4 (1661) 55 (1397) 64 (29) 300 PF505032 5,6,7,8 50 (3.2) 5.00 (3.73) 3 230 240 16.5 16.5 13 2 in. SS 59.3 (1506) 49 (1245) 64 (29) 300 PF751012 75 (4.7) 1.00 (0.75) 1 230 240 9.9 10.0 3 2 in. SS 27.0 (686) 27 (686) 34 (15) 100 PF751512 75 (4.7) 1.50 (1.11) 1 230 240 12.1 12.3 4 2 in. SS 33.4 (848) 30 (762) 44 (20) 100 Specifications, 50 Hz Pump Model PF100552 10 (0.6) 0.50 (0.37) 1 220 230 3.9 4.1 6 1 ¼ in. GFP 23.0 (584) 17 (432) 26 (12) 300 PF100752 4, 5 10 (0.6) 0.75 (0.56) 1 220 230 6.2 6.2 9 1 ¼ in. GFP 26.8 (658) 17 (432) 30 (14) 300 PF101552 5, 6 10 (0.6) 1.50 (1.11) 1 220 230 10.5 11.4 18 1 ¼ in. SS 39.5 (1003) 22 (559) 46 (21) 300 PF300552 30 (1.9) 0.50 (0.37) 1 220 230 4.1 4.1 4 1 ¼ in. GFP 22.5 (572) 19 (483) 26 (12) 300 PF300752 30 (1.9) 0.75 (0.56) 1 220 230 6.1 6.1 5 1 ¼ in. GFP 24.8 (630) 19 (483) 29 (13) 300 PF301052 30 (1.9) 1.00 (0.75) 1 220 230 7.4 7.4 7 1 ¼ in. GFP 28.4 (721) 20 (508) 32 (15) 100 PF301552 4, 5 30 (1.9) 1.50 (1.11) 1 220 230 9.3 9.3 8 1 ¼ in. GFP 35.4 (899) 24 (610) 40 (18) 100 PF500552 50 (3.2) 0.50 (0.37) 1 220 230 4.0 4.0 2 2 in. SS 20.3 (516) 25 (635) 29 (13) 300 PF500752 50 (3.2) 0.75 (0.56) 1 220 230 6.3 6.4 3 2 in. SS 23.7 (602) 25 (635) 31 (14) 300 PF501052 50 (3.2) 1.00 (0.75) 1 220 230 7.3 7.4 4 2 in. SS 27.0 (686) 26 (660) 35 (16) 100 PF501552 50 (3.2) 1.50 (1.11) 1 220 230 9.1 9.1 5 2 in. SS 32.5 (826) 30 (762) 42 (19) 100 PF751052 75 (3.2) 1.00 (0.75) 1 220 230 7.3 7.3 4 2 in. SS 30.0 (762) 27 (686) 34 (15) 100 1 GFP = glass-filled polypropylene; SS = stainless steel. The 1 ¼-in. NPT GFP discharge is 2 7⁄8 in. octagonal across flats; the 1 ¼-in. NPT SS discharge is 2 1⁄8 in. octagonal across flats; and the 2-in. NPT SS discharge is 2 7⁄8 in. hexagonal across flats. Discharge is female NPT threaded, U.S. nominal size, to accommodate Orenco® discharge hose and valve assemblies. Consult your Orenco Distributor about fittings to connect hose and valve assemblies to metric-sized piping. 2 Minimum liquid level is for single pumps when installed in an Orenco Biotube® Pump Vault or Universal Flow Inducer. In other applications, minimum liquid level should be top of pump. Consult Orenco for more information. 3 Weight includes carton and 10-ft (3-m) cord. 4 High-pressure discharge assembly required. 5 Do not use cam-lock option (Q) on discharge assembly. 6 Custom discharge assembly required for these pumps. Contact Orenco. 7 Capacitor pack (sold separately or installed in a custom control panel) required for this pump. Contact Orenco. 8 Torque locks are available for all pumps, and are supplied with 3-hp and 5-hp pumps. De s i g n g p m (L / s e c ) Ho r s e p o w e r (k W ) Ph a s e Na m e p l a t e vo l t a g e Ac t u a l v o l t a g e De s i g n f l o w am p s Ma x a m p s Im p e l l e r s Di s c h a r g e s i z e an d m a t e r i a l 1 Le n g t h , i n . ( m m ) Mi n . l i q u i d l e v e l , 2 in . ( m m ) We i g h t , 3 l b ( k g ) Ra t e d c y c l e s / d a y Technical Data SheetOrenco® Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 4 of 6 Materials of Construction Discharge Glass-filled polypropylene or stainless steel Discharge bearing Engineered thermoplastic (PEEK) Diffusers Glass-filled PPO (Noryl GFN3) Impellers Celcon® acetal copolymer on 10-, 20, and 30-gpm models; 50-gpm impellers are Noryl GFN3 Intake screen Polypropylene Suction connection Stainless steel Drive shaft 7/16 inch hexagonal stainless steel, 300 series Coupling Sintered stainless steel, 300 series Shell Stainless steel, 300 series Motor Franklin motor exterior constructed of stainless steel. Motor filled with deionized water and propylene glycol for constant lubrication. Hermetically sealed motor housing ensures moisture-free windings. All thrust absorbed by Kingsbury-type thrust bearing. Rated for continuous duty. Single- phase motors and 200 and 230 V 3-phase motors equipped with surge arrestors for added security. Single-phase motors through 1.5 hp (1.11 kW) have built-in thermal overload protection, which trips at 203-221˚ F (95-105˚ C). Using a Pump Curve A pump curve helps you determine the best pump for your system. Pump curves show the relationship between flow (gpm or L/sec) and pressure (total dynamic head, or TDH), providing a graphical representation of a pump’s optimal performance range. Pumps perform best at their nominal flow rate — the value, measured in gpm, expressed by the first two numerals in an Orenco pump nomenclature. The graphs in this section show optimal pump operation ranges with a solid line. Flow flow rates outside of these ranges are shown with a dashed line. For the most accurate pump specification, use Orenco’s PumpSelect™ software. Pump Curves, 60 Hz Models T ot a l d y n a m i c h e a d ( T D H ) i n f e e t Flow in gallons per minute (gpm) 24 81012141660 800 700 600 500 400 300 200 100 PF1005-FC w/ ¼" flow controller PF10 Series, 60 Hz, 0.5 - 2.0 hp PF1007 PF1010 PF1020 PF1005 T ot a l d y n a m i c h e a d ( T D H ) i n f e e t Flow in gallons per minute (gpm) 36 12 15 18 21 2490 160 140 120 100 80 60 40 20 0 PF1503 PF15 Series, 60 Hz, 0.3 hp Technical Data Sheet Orenco® Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 5 of 6 T ot a l d y n a m i c h e a d ( T D H ) i n f e e t Flow in gallons per minute (gpm) 5102025303540150 400 350 300 250 200 150 100 50 0 PF2005 PF2010 PF2015 PF20 Series, 60 Hz, 0.5 - 1.5 hp T ot a l d y n a m i c h e a d ( T D H ) i n f e e t Flow in gallons per minute (gpm) 510202530354045150 800 900 700 600 500 400 300 200 100 0 PF3005 PF3007 PF3010 PF3015 PF3020 PF3030 PF3050 PF30 Series, 60 Hz, 0.5 - 5.0 hp T ot a l d y n a m i c h e a d ( T D H ) i n f e e t Flow in gallons per minute (gpm) 450 400 350 300 250 200 150 100 50 0 10 02040506070809030 PF5050 PF5030 PF5015 PF5010 PF5007 PF5005 PF50 Series, 60 Hz, 0.5 - 5.0 hp T ot a l d y n a m i c h e a d ( T D H ) i n f e e t Flow in gallons per minute (gpm) 10 20 40 50 60 70 80 90 100300 80 90 100 70 60 50 40 30 20 10 0 PF75 Series, 60 Hz, 1.0 - 1.5 hpPF7515 PF7510 60 Hz Models (continued) Technical Data SheetOrenco® Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 6 of 6 To ta l d y n a m i c h e a d ( T D H ) i n m e t e r s To ta l d y n a m i c h e a d ( T D H ) i n f e e t , n o m i n a l Flow in liters per second (L/sec) Flow in gallons per minute (gpm), nominal 0.90.80.70.60.50.40.30.20.10 13119.57.96.34.83.21.6 120 100 80 60 40 20 0 160 180 140 394 328 262 197 131 66 525 459 PF100552 PF100752 PF101552 PF1005-FC w/ 6mm flow controller PF10 Series, 50 Hz, 0.37 - 1.11 kW To ta l d y n a m i c h e a d ( T D H ) i n m e t e r s To ta l d y n a m i c h e a d ( T D H ) i n f e e t , n o m i n a l Flow in liters per second (L/sec) Flow in gallons per minute (gpm), nominal 0.8 1.2 1.6 2.0 2.40.40 13 19 25 326.3 60 80 100 120 40 20 0 197 262 328 131 66 PF301552 PF301052 PF300752 PF300552 PF30 Series, 50 Hz, 0.37 - 1.11 kW T ot a l d y n a m i c h e a d ( T D H ) i n m e t e r s T ot a l d y n a m i c h e a d ( T D H ) i n f e e t , n o m i n a l Flow in liters per second (L/sec) Flow in gallons per minute (gpm), nominal 0.5 1.0 2.0 2.5 3.0 3.5 4.0 4.51.50 7.9 16 32 40 48 56 6324 40 45 35 30 25 20 15 10 5 0 131 115 98 82 66 49 33 16 PF501552 PF501052 PF500752 PF500552 PF50 Series, 50 Hz, 0.37 - 1.11 kW T ot a l d y n a m i c h e a d ( T D H ) i n m e t e r s T ot a l d y n a m i c h e a d ( T D H ) i n f e e t , n o m i n a l Flow in liters per second (L/sec) Flow in gallons per minute (gpm), nominal 0.6 1.2 2.4 3.0 3.6 4.2 5.44.8 6.01.80 10 19 4838 57 67 76 8629 27 30 24 21 18 15 12 9 6 3 0 89 79 69 59 49 39 30 20 PF751052 PF75 Series, 50 Hz, 0.75 kW Pump Curves, 50 Hz Models The Quick4® Plus Standard Chamber The Quick4 Plus Standard Chamber offers maximum strength through its two center structural columns. This chamber can be installed in a 36-inch-wide trench. Like the original line of Quick4 chambers, it offers advanced contouring capability with its Contour Swivel Connection™ which permits turns up to 15-degrees, right or left. It is also available in four-foot lengths to provide optimal installation flexibility. The Quick4 Plus All-in-One 12 Endcap, and the Quick4 Periscope are available with this chamber, providing increased flexibility in system configurations. Maximum Strength APPROVED in _____________________________________________ Quick4 Plus™ Series Quick4 Plus All-in-One 12 Endcap Benefits: • May be used at the end of chamber row for an inlet/outlet or can be installed mid-trench • Mid-trench connection feature allows construction of chamber rows with center feed, as an alternative to inletting at the ends of chamber rows • Center-feed connection allows for easy installation of serial distribution systems • Pipe connection options include sides, ends or top Quick4 Plus All-in-One Periscope Benefits: • Allows for raised invert installations • 180° directional inletting • 12” raised invert is ideal for serial applications Certified by the International Association of Plumbing and Mechanical Officials (IAPMO) Quick4 Plus Standard Chamber Specifications Size 34”W x 53”L x 12”H (864 mm x 1346 mm x 305 mm) Effective Length 48” (1219 mm) Louver Height 8” (203 mm) Storage Capacity 47 gal (178 L) Invert Height 0.6” (15 mm), 5.3” (135 mm), 8.0” (203 mm), 12.7” (323 mm) Quick4 Plus Standard Chamber Benefits: • Two center structural columns offer increased stability and superior strength • Advanced contouring connections • Latching mechanism allows for quick installation • Four-foot chamber lengths are easy to handle and install • Supports wheel loads of 16,000 lbs/axle with 12” of cover Contact Infiltrator Water Technologies’ Technical Services Department for assistance at 1-800-221-4436 4 Business Park Road P.O. Box 768 Old Saybrook, CT 06475 860-577-7000 • Fax 860-577-7001 1-800-221-4436 www.infiltratorwater.com U.S. Patents: 4,759,661; 5,017,041; 5,156,488; 5,336,017; 5,401,116; 5,401,459; 5,511,903; 5,716,163; 5,588,778; 5,839,844 Canadian Patents: 1,329,959; 2,004,564 Other patents pending. Infiltrator, Equalizer, Quick4, and SideWinder are registered trademarks of Infiltrator Water Technologies. Infiltrator is a registered trademark in France. Infiltrator Water Technologies is a registered trademark in Mexico. Contour, MicroLeaching, PolyTuff, ChamberSpacer, MultiPort, PosiLock, QuickCut, QuickPlay, SnapLock and StraightLock are trademarks of Infiltrator Water Technologies. PolyLok is a trademark of PolyLok, Inc. TUF-TITE is a registered trademark of TUF-TITE, INC. Ultra-Rib is a trademark of IPEX Inc. © 2013 Infiltrator Water Technologies, LLC. All rights reserved. Printed in U.S.A.PLUS05 0713 Quick4 Plus™ Series INFILTRATOR WATER TECHNOLOGIES STANDARD LIMITED WARRANTY (a) The structural integrity of each chamber, endcap and other accessory manufactured by Infiltrator (“Units”), when installed and operated in a leachfield of an onsite septic system in accordance with Infiltrator’s instructions, is warranted to the original purchaser (“Holder”) against defective materials and workmanship for one year from the date that the septic permit is issued for the septic system containing the Units; provided, however, that if a septic permit is not required by applicable law, the warranty period will begin upon the date that installation of the septic system commences. To exercise its warranty rights, Holder must notify Infiltrator in writing at its Corporate Headquarters in Old Saybrook, Connecticut within fifteen (15) days of the alleged defect. Infiltrator will supply replacement Units for Units determined by Infiltrator to be covered by this Limited Warranty. Infiltrator’s liability specifically excludes the cost of removal and/or installation of the Units. (b) THE LIMITED WARRANTY AND REMEDIES IN SUBPARAGRAPH (a) ARE EXCLUSIVE. THERE ARE NO OTHER WARRANTIES WITH RESPECT TO THE UNITS, INCLUDING NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE (c) This Limited Warranty shall be void if any part of the chamber system is manufactured by anyone other than Infiltrator. The Limited Warranty does not extend to incidental, consequential, special or indirect damages. Infiltrator shall not be liable for penalties or liquidated damages, including loss of production and profits, labor and materials, overhead costs, or other losses or expenses incurred by the Holder or any third party. Specifically excluded from Limited Warranty coverage are damage to the Units due to ordinary wear and tear, alteration, accident, misuse, abuse or neglect of the Units; the Units being subjected to vehicle traffic or other conditions which are not permitted by the installation instructions; failure to maintain the minimum ground covers set forth in the installation instructions; the placement of improper materials into the system containing the Units; failure of the Units or the septic system due to improper siting or improper sizing, excessive water usage, improper grease disposal, or improper operation; or any other event not caused by Infiltrator. This Limited Warranty shall be void if the Holder fails to comply with all of the terms set forth in this Limited Warranty. Further, in no event shall Infiltrator be responsible for any loss or damage to the Holder, the Units, or any third party resulting from installation or shipment, or from any product liability claims of Holder or any third party. For this Limited Warranty to apply, the Units must be installed in accordance with all site conditions required by state and local codes; all other applicable laws; and Infiltrator’s installation instructions. (d) No representative of Infiltrator has the authority to change or extend this Limited Warranty. No warranty applies to any party other than the original Holder. The above represents the Standard Limited Warranty offered by Infiltrator. A limited number of states and counties have different warranty requirements. Any purchaser of Units should contact Infiltrator’s Corporate Headquarters in Old Saybrook, Connecticut, prior to such purchase, to obtain a copy of the applicable warranty, and should carefully read that warranty prior to the purchase of Units. Quick4 Plus Standard Chamber ___________________________________________________________________________________ Quick4 Plus All-in-One 12 Endcap ________________________________________________________________________________ Quick4 Plus All-in-One Periscope ________________________ EFFECTIVE LENGTH48" 12" 34" QUICK4 PLUS ALL-IN-ONE PERISCOPE (360° SWIVEL) 12.7" INVERT PRESSURIZED PIPE DRILL POINTS LOCATIONS (2 PLACES) 33" 18" 8" INVERT 13" EFFECTIVE LENGTH48" 12" 34" QUICK4 PLUS ALL-IN-ONE PERISCOPE (360° SWIVEL) 12.7" INVERT PRESSURIZED PIPE DRILL POINTS LOCATIONS (2 PLACES) 33" 18" 8" INVERT 13" FRONT VIEW SIDE VIEW EFFECTIVE LENGTH48" 12" 34" QUICK4 PLUS ALL-IN-ONE PERISCOPE (360° SWIVEL) 12.7" INVERT PRESSURIZED PIPE DRILL POINTS LOCATIONS (2 PLACES) 33" 18" 8" INVERT 13" 6" 5"9" feet meters 600 100