HomeMy WebLinkAboutEngineer's Report 10.15.2015RIVERSTONE 1410 S T R U C T I', A. _ CONCEPTS December 15, 2015 Mr. Pete Waararâ–ºiemi 353 Goose Lane Carbondale, CO 81623 Re: Aspen -Glenn Duplex D-38 Mr. Waaraniemi: Me /0/ It is our understanding that the vertical reinforcing in all footings in the above referenced project have been placed at 48" on center in lieu of 24" on center as specified. I have reviewed the project requirements and it appears as though 48" on center vertical reinforcing will be adequate to support the required loads. No additional reinforcing is required provided that the horizontal reinforcing is installed as specified. Please let me know if you have any additional questions. Sincerely, David Fulton Senior Associate Reviewed and approvidc by Patrick Bird, P.E./S.E. 1 a RIVE tWARK f ti - Si11Tl 150. 114tlal 11).1110 0.'116 - 1'EI(E\l ,-04 at 21112 - l \\ 2'i ;41604', Pete Waaraniemi From: David Fulton <david@riverstonesc.com> Sent: Tuesday, December 15, 2015 3:11 PM To: Pete Waaraniemi Subject: RE: D38 Footing Reinforcing Letter.pdf Pete, 14-16" is fine. Best regards, DAVID FULTON SENIOR ASSOCIATE RIVERSTONE PPerfornung Today's Engineering it i h Tomorrow's Technology! 671 E RIVERPARK LN., STE 4150 BOISE, ID 83706 P- 208.343 2092 Q: 208 954.8583 www.rlverstonesc.com CONFIDENTIALITY NOTICE THIS EMAIL CONTAINS PRIVILEGED AND CONFIDENTIAL INFORMATION WHICH I5 THE PROPERTY QF RIVERSTONE STRUCTURAL CONCEPTS, PLLC, AND 15 INTENDED FOR THE USE OF THE RECIPIENT{S} UNAUTHORIZED USE OR DISCLOSURE OF THIS INFORMATION IS STRICTLY PROHIBITED. IF YOU ARE NOT AN INTENDED RECIPIENT, PLEASE NOTIFY US IMMEDIATELY AND DESTROY THIS COMMUNICATION AND ANY COPIES From: Pete Waaraniemi Imailto:pete@janckilaconstruction.com] Sent: Tuesday, December 15, 2015 2:02 PM To: David Fulton <david@riverstonesc.com> Subject: RE: D38 Footing Reinforcing Letter.pdf David, sorry about this. The concrete contractor has 3 horizontals in the wall and they are 14" to 16" apart. The plans call for 12" apart. Is this going to fly or do I need to have him tighten these up and add a bar. Clearly I have to babysit this guy. Thanks, Pete Waaraniemi JANCKILA Cell 970-319-3650 Office 970-927-6714 From: David Fulton[mailto:david@riverstonesc.comj Sent: Tuesday, December 15, 2015 10:02 AM 1 To: Pete Waaraniemi <pete@ianckilaconstruction.com> Subject: D38 Footing Reinforcing Letter.pdf Pete, apologize for not getting back to you yesterday, I was out of the office. Please see attached and let me know if you need anything else. Best regards, DAVID FULTON SENIOR ASSOCIATE RIVERSTONE Performing Today's Engineering otilh Tomorrokti s Technology!" 671 E. RA/MARK LN., SIE 11150 BOI5F, ID 83706 P 208.343 2092 D 208 9S4 8583 www.riverstonesc.com CONFIDENTIALITY NOTICE THIS EMAIL CONTAINS PRIVILEGED AND CONFIDENTIAL INFORMATION WHICH IS THE PROPERTY OF RIVERSTONE STRUCTURAL CONCEPTS. PL LC AND IS INTENDED FOR THE USE OF THE RECIPIENT(SI UNAI,TI IORI?ED USE OR DISCLOSURE OF THIS INFORMATION IS STRICTLY PROHIBITED IF YOU ARE NOT AN INTENDED RECIPIENT, PLEASE NOTIFY US IMMEDIATELY AND DESTROY THIS COMMUNICATION AND ANY COPIES. 2