Subject: Fwd: Inspection Report for Permit: 818803
Good morning Jim
Please see the inspection report for 700 Deer Run Trail.
Let us know if you have any questions.
We have kept your daughter in our thoughts and truly hope she is doing well.
Best, Kandy and Kevin Herrman
Sent from my iPhone
Begin forwarded message:
From: Robert Crawford<crawfordbrotherselectric�)a,gmail.com>
Date: May 26, 2017 at 8:34:26 AM MDT
To: Advantage Builders<kherrman@advantagebuildersco.com>
Subject: Fwd: Inspection Report for Permit: 818803
Forwarded message
From: <dora electricalboard@state.co_us>
Date: Fri, Apr 14, 2017 at 12:00 AM
Subject: Inspection Report for Permit: 818803
To:<CRAWFORDBROTHERSELECTRIC@gmail.com>
COLORADO STATE ELECTRICAL BOARD
1560 Broadway, Suite 1350
Denver, Colorado 80202
Automatic email - Do not reply to this email.
Inspection Report
Permit #: 818803 Date Inspected: 13 -APR -17
Permit Richard Crawford
Holder:
PO BOX 4262 BASALT 81621
Phone: (970) 618-4548 Fax:
Email: CRAWFORDBROTHERSELECTRIC@GMAIL.COM
1
Site: 700 Deer Run Rifle County: Garfield
Owner: Kevin Herman Phone: (970) 618-4548
Herman
Status: PARTIAL
Inspection Type: Rough In Trim Permit: N
Constuction Type: NEW Building Type: RESIDENTIAL
Inspector: Norman Feck 303-869-3442
Corrections: 250.50, 250.53G Two ground rods are installed as the grounding electrode system. The ground
rods are not driven flush with grade. There is no ufer electrode and there must be. Establish
concrete encased electrode for this new construction. With that, the ground rods would not be
necessary. The grounding electrode system can be checked next rough inspection.
Comments: 1) Temporary heat meter release ok 2) Typically a rough on the shop or house would take plac
at the same time as these temporary heat meter releases. That saves a trip charge... For future
reference. 3) Shop and house rough needed yet 4) Inspector, check GE system next vist.