Loading...
HomeMy WebLinkAboutBolt Inspection Report 05.22.2017West Slope Testing & Inspection LLC - Report # 1 3177 Glendam Dr. Grand Junction, CO 81504 Page 1 of 1 Phone: 970-434-6988 Cell: 970-260•-2844 Inspection• Report Date: 5722-17 Project: Metal Shop Automotive Building Address: 3927 County Rd. 154 Garfield County, CO Building Permit No: BLCO-02-17-4594 Contractor that Performed Work: Tally Ho Construction Inspection of shop fabrication or field work at job site: Field Report: Inspected high strength A325 bolting at the main frame, end wall frame, and portal frame column, rafter, and beam connections. Also randomly tested/verified A325 bolts were adequately tightened. The high strength A325 bolting inspected above appeared to be in substantial conformance with the plans, and the AISC/RCSC Specification for high strength bolting except as noted below. 1) It appeared that the top connection seats at the light gauge columns end wall framing grid line 6 were welded on (from the factory) at the wrong slope to match roof rafters. Subsequently there was a gap at one side & the faying/connection surfaces were not in firm contact. Please have structural engineer and/or metal building manufacture review & provide fix if needed. Inspector/Technician: Douglas E Young Douglas E. Young Cer 'Ocatio 951022 # to Wel ing S s r c t & B in ial Inspector �Zpray-applied Fireproof; g Special Inspector