HomeMy WebLinkAboutOWTS System Design 06.19.201733 Fur Wheel Drive Rd Carbondale, CO 81623 970.309.5259 June 19, 2017 Brad Crawford Crawford Design Build crawforddesignbuild Er.comcast.net Subsurface Investigation and Onsite Wastewater Treatment System Design 5 -Bedroom Residence Lot 2, Wooden Deer Subdivision Garfield County, Colorado Brad, Project No. C1296 ALL SERVICE septic, LLC performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 5.48 -acre property is located outside of Carbondale, in an area where OWTSs are necessary. Legal Description: Lot 2, Wooden Deer Subdivision Parcel ID: 2393-243-04-002 SITE CONDITIONS The property is currently undeveloped. A 5 -bedroom, single-family residence is proposed. The subdivision is served potable water from a community water system. A water tank that stores water for the entire subdivision is located on the property. The proposed soil treatment area (STA) must be located at least 100 -feet from the water tank. Location of water lines was not provided on the site plan. All OWTS components must be located at least 25 -feet from any water line, and if a sewer line crosses a water line, the sewer line must be encased within 10 -feet of the crossing (see Encasement Detail W4.0/2). The proposed STA location has approximately a ten percent slope across the proposed STA to the west. There are no potential future land use changes or bedroom additions planned for the property. SUBSURFACE The subsurface was investigated on June 16, 2017 by exploring the foundation excavation. A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.' The materials encountered in the excavation consisted of topsoil to 6.0 -inches, underlain by tan caliche to a maximum depth explored of 8.0 -feet Large basalt boulders are present below 4 -feet. No bedrock or groundwater was encountered. 1 Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page 2 An additional test pit must be excavated in the proposed STA prior to construction of the OWTS. This office must be called to verify the soils. A tactile analysis of the soils was taken from the excavation at approximately 3 -feet below grade. The soil formed a ball and a weak ribbon. Soil structure shape was blocky, soil structure grade was weak, and consistence was extremely firm to rigid. STA sizing is based on Soil Type 2A, Silt Loam with weak structure grade. A long term acceptance rate (LTAR) of 0.5 gallons per square foot will be used to design the OWTS, in accordance with Table 10-1 Soil Type 2A presented in the Garfield County On -Site Wastewater Treatment System Regulations, adopted April 14, 2014. Foundation excavation Sidewall of excavation Sidewall (weak structure grade) DESIGN SPECIFICATIONS Design Calculations: Average Design Flow = 75 GPD x 2 people/bedroom x 3 bedrooms + 150 GPD (4th and 5th bedrooms) = 600 GPD = 600 GPD LTAR = 0.5 GPD/SF 600 GPD / 0.5 GPD/SF x 1.2 (gravity beds) x 0.7 (chambers) = 1008 SF Page 3 The new OWTS design is based on 5 -bedrooms. An average daily wastewater flow of 600 GPD will be used. The system installation will include a new 1500 -gallon, two-compartment concrete septic tank with an effluent filter installed on the outlet tee of the septic tank. The septic tank may not be buried more than 4 -feet below grade and risers must bring the manhole lids to grade for access. Effluent will gravity flow to a distribution box, and then to three gravelless chamber beds. The distribution box must be accessible from grade and must have flow equalizers, or similar product, installed on each outlet pipe in the distribution box to assure equal flow to each bed. Each bed will consist of 3 rows of 10 'Quick 4' Infiltrator® Low Profile chambers connected with a level manifold, for a total area of 1080 square feet of infiltrative area. The infiltrative area may not exceed 4 - feet below native grade. Inspection ports must be installed in each corner of each bed. Ports may be cut to grade and placed in sprinkler boxes for access. The component manufacturers are typical of applications used by contractors and engineers in this area. Alternatives may be considered or recommended by contacting our office. Construction must be according to Garfield County On -Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo -fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on backfilled STAs. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non -biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. Page 4 ADDITIONAL CONSTRUCTION NOTES If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3 -inch. INSTALLATION OBSERVATIONS ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL SERVICE septic, LLC should be notified 48 hours in advance to observe the installation. LIMITS: The design is based on information submitted. If soil conditions encountered are different from conditions described in report, ALL SERVICE septic, LLC should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, ALL SERVICE septic, LLC ( 0,s-hac,ktg Carla Ostberg, MPH, REHS Reviewed By: 0' Scale: N r 0' 1" = .1 cP 4 D N. D -3 SWRL E 'OM TA K TO .-10 ( (V °Io .LO'E) 15 0- 'LLO T OC 0 C- T• SP8P C 1 S R 0 0 TL.T E 1 • 2S/U S DR 35 E L: -S EE' C 0 • TAN NOUT R EN EF .UEN RINE WI EAN\OUT ( H IN. Building Poi t _TE: POSIT!L V SELECT N BEDS TO TREES DipT B AC GRA IBUTIO ITH SS AT E IN. 6' TWEE BEDS 3C OF 1 CHA CHA AMBE BED 3 'WS 0 'QUI 4' LOW P OFIL BERS EACH : D = 90 BERS 1080 FN INSPECTION COR ROF ®1l L1■ 111 ORT ' T EAC TA 5-BEDR MAN4" D LEV MAN F A SD FOLDL LD 35 PROPOSED OWTS zQ V,4r 4 • coo° 1 4 0 DESIGN 5 -BEDROOM RESIDENCE (75 GPD x 2 PERSONS/BEDROOM x 3 BEDROOMS) +150 GPD (4TH AND 5TH BEDROOMS) = WASTEWATER FLOW = 600 GALLONS TANK: USE 1500 -GALLON, TWO-COMPARTMENT CONCRETE SEPTIC TANK SOIL TREATMENT AREA (STA): LTAR = 0.5 GAL/ SQ FT CALCULATED STA = Q/LTAR = 600 / 0.5 = 1200 SF GRAVITY, BEDS = 1200 SFX 1.2 = 1440 SF CHAMBERS = 1440 SF X 0.7 = 1008 SF 1008/ 12 SF / CHAMBER = 84 CHAMBERS THREE GRAVELLESS CHAMBER BEDS 10 'QUICK 4' LOW PROFILE CHAMBERS IN EACH BED TOTAL 90 'QUICK 4' LOW PROFILE CHAMBERS WINGS MUST BE USED IN CONJUNCTION WITH DESIGN LETTER DATED 06/19/17 ALL SERV1CI 33 Four Wheel Drive Road Carbondale, Colorado 81623 Phone 970.309.5259 carla@allserviceseptic.com Crawford Residence Lot 2, Wooden Deer Subdivision Garfield County, Colorado Project Number: C1296 Date: 06/19/17 Designed By: CBO Reviewed By: RHP Drawn By: ANG W2.0 Sheet 2 of 4 4" DIA MIN. SDRO-35 EFFLUENT PIPE (MIN. 1% FALL FROM TANK) 4" DIA SDR -35 PVC LEVEL MANIFOLD SLIP-ON PVC CAP DO NOT GLUE 4" DIA SDR -35 SEWER LINE TO EACH TRENCH (MIN. 1% SLOPE TO TRENCH) INFILTRATOR END PLATE 40' 30 CHAMBERS PER BED PIPES PLACED IN TOP PORT OF CHAMBER END PLATES INSULATED COPPER TRACER WIRE 4" DIA SDR -35 SEWER LINE 0 STA PLAN FINISHED GRADE CLEAN OUT DETAIL ALL SERYICI 33 Four Wheel Drive Road Carbondale, Colorado 81623 Phone 970.309.5259 carla@allserviceseptic.com Y6 i 1.. SCALE NOT TO SCALE GRAVELLESS 'QUICK -4' CHAMBER (4' x 3') 4" DIA SDR -35 INSPECTION PORT AT EACH CORNER OF STA 4"SDR 35PVC INSPECTION PORT AT EACH CORNER OF STA EXTENT OF EXCAVATION 0 SLOPE FORDRAINAGE BACKFILL MUST BE MINUS 3 -INCH MATERIAL SMALL VALVE COVER BOX OR IRRIGATION VALVE BOX AT GRADE ATTACH CAP OR THREADED CLEANOUT ASSEMBLY COMPACT SOIL BASE TO SUPPORT BOX USE HOLE SAW TO CUT THRU TOP OF END PLATE 4" PVC PIPE CUT TO FIT INSPECTION PORT DETAIL NOT TO SCALE INFILTRATOR(R) QUICK4(TM) LOW PROFILE CHAMBER, 3'X4' SCARIFY SURFACE STA SECTION NOT TO SCALE Crawford Residence Lot 2, Wooden Deer Subdivision Garfield County, Colorado Project Number: C1296 16" 52" 48" (EFFECTIVE LENGTH) 11011 LINES TO ENTER AND EXIT IN TOP PORT OF CHAMBER END PLATE O'LOW PROFILE' CHAMBER DETAIL NOT TO SCALE [te: 06/19/17 Designed By: CBO 3 . Reviewed By: RHP Drawn By: CBO Sheet 3 of 4 BOX AND COVER BROUGHT TO GRADE CONCRETE LID FINSHED GRADE 7 0000 OUTLETS DISTRIBUTION BOX BAFFLE OR ANGLED PIPE TO BE USED AT INLET 0 DISTRIBUTION BOXo DETAIL SCALE NOT SCHEDULE 40 ENCASEMENT PIPE SCH 40 RIGID END P CAP AT EACH END OF PIPE _____. _________ -4" DIA SDR -35 SEWER LINE. MUST REST ON BOTTOM OF ENCASEMENT PIPE END CAP MUST BE GLUED OR SECURED IN A WATER TIGHT FASHION WITH UNDERGROUND SEALANT HOLE DRILLED IN END CAP MUST ONLY BE LARGE ENOUGH TO ALLOW SEWER LINE TO FIT THROUGH ENCASEMENT DETAIL NOT TO SCALE LL. SERYICE 33 Four Wheel Drive Road Carbondale, Colorado 81623 Phone 970.309.5259 carla@allserviceseptic.com 1— w w u_ H 0 w 0 - 0 --1 -- 2 — 3 -- 4 5 --- 6 — 7 — 8 — 9 - 10 PROFILE EXCAVATION 6" TOPSOIL TAN, DENSE CALICHE WITH WEAK STRUCTURE GRADE AND LARGE BASALT BOULDERS BELOW 4 -FEET NO GROUNDWATER OR BEDROCK ENCOUNTERED DURING EXCAVATION SOILS LOG Nor TO SCALE LEGEND pq topsoil ncaliche Crawford Residence Lot 2, Wooden Deer Subdivision Garfield County, Colorado Project Number: C1296 Date: 06/19/17 Designed By: CBO Reviewed By: Ri-IP Drawn By: CBO W4.0 Sheet 4of4 Item # 1500T4CP 1500 Gallon Top Seam Two Compartment DESIGN NOTES • Design per performance test per ASTM C1227 • Top surface area 62.33 ft2 • f'c ® 28 days; concrete = 6,000 PSI Min. Installation: • Tank to be set on 5" min. sand bed or pea gravel • Tank to be backfilled uniformly on all sides in lifts less than 24" and mechanically compacted • Excavated material may be used for backfill, provided large stones are removed • Excavation should be dewatered and tank filled with water prior to being put in service for installation with water table less than 2' below grade • Meets C1644-06 for resilient connectors • Inlet and Outlet identified above pipe • Delivered complete with internal piping • PVC or concrete risers available • Secondary safety screen available with PVC riser • Option of pump or siphon installed ALLOWABLE BURY (Based on Water Table) WATER TABLE ALLOWABLE EARTH FILL 0'-0" 3'-0" 1'-0" 3'—O" 2'-0" 4'— 0" 3'-0" 4'— 0" DRY 4' — 0" Flexible BOOL 6 63" 32" 56" Top View • Digging Specs Invert Dimensions Net Capacity 129" Net Weight 53• Section View 13' Long x 8' Wide !Inlet Outlet Length Width Height 'Inlet Side Outlet Total Lid Tank t Total 56" below inlet 56" i 53" 132" 68" 68" 11002 gal 507 gal 1509 gal 3600 lbs 11180 lbs 14780 lbs Water & (719) 3954764 28005 Co. Rd. 317 Wastewater P.O. Bcx925 • Systems Fax: (719) 395-3727 Buena Vi CO81211 NFVALLEY . ProductsPRECAST, iac. • Service Website: www.valleyprecast com Email: frontdesk©valleyprecastcom Residential Biotube® Effluent Filters Applications Our patcntcd" 4 -in. (100 -mm) Biotube Effluent Filters, Biotube Jr., Biotube Insert Filters, and Biotube Base Inlet Filters are ideal for residential septic tanks and have a lifetime warranty. They prevent large solids from leaving the tank, dramatically improving wastewater quality and extending the life of residential drainfields. 4 -in. (100-7am) Biotube Effluent Filter 4 -in. (100 -mm) Biotube Jr. (4 -in. Biotube cartridge avail- able separately as Insert Filter) 8 -in. (200 -mm) Base Inlet Filter 4 -in. (100 -mm) Insert Filter r Drenco's superior effluent filters resist clogging better than all other brands. Our stan- dard, fdl-sized 4 -in. (100 -mm) Biotube Effluent Filter provides maximum long-term protection in a complete package, with housing. Our 4 -in. (100 -mm) Biotube fr., at half the size of our standard model, has more filtering capacity than the full-sized filters sold by other manufacturers. For tanks with existing outlet tees, the Biotube Insert Filter is ideal. And for low profile tanks, there's the Base Inlet Filter. Covered by patent numbers 5,492,635 and 4,439,323 To Order Call your nearest Orenco Systems®, Inc. distributor. For nearest distribu- tor, call Orenco at 800-348-9843 or go to www.orenco.com and click on "Distributor Locator." APS -FT -1 Rev. 3.4 © 11/10 Orenco Systems®, Inc. Standard Features & Benefits • Has 5-10 limes more flow area than other brands, so lasts many times longer between clean- ings, increasing homeowner satisfaction • Installs in min- utes inside new or existing tanks; extendible tee handle for easy removal Optional Features & Benefits • Alarm available, to signal the need for cleaning • Flow modulating discharge orifices available to limit flow rate leaving tank, mitigat- ing surges and increasing retention time • Custom and commercial sizes available • Easy to clean by simply hosing off whenever the tank needs pumping • Removes about two-thirds of sus- pended solids, on average, extending drainfield life • Corrosion -proof construction, to ensure long life • Lifetime warranty Biotube Filtering Process Effluent from the relatively clear zone of the septic tank, between the scum and sludge layers, horizontally enters the Biotube Effluent Filter. Effluent then enters the annular space between the housing and the Biotubes, utilizing the Biotubes' entire surface for filtering. Particles larger than the Biotube's mesh are prevented from leaving the tank. o Orenco Systems' Incorporated Clanging the 1i* the World Does Wastewater° www.arenco.com Nomenclatures 4 -in. Biotube Filter (standard) FTL 04 -juin l Opliw is: Blank = no options M = flow modulation plate installed A = float bracket attached Cartridge height: 28" and 36" are standard Housing height: 36" and 44" are standard Filter diameter (inches) W = fits Type 3034 outlet pipe S = fits Schedule 40 outlet pipe Blank = 1/8" filtration P = 1/16" filtration Riots the effluent filter series 8 -in. Biotube Filter (base inletmodel) FT 0822-14B 1 Options: A = float bracket FS = 2" outlet orifice FSO = 2" outlet orifice and overflow plate* Base inlet model Cartridge height: 14" standard Housing height: 22" standard Hite diameter (inches) 08 = 8" Blank = 1/8" filtration P = 1/16" filtration Biotube effluent filter series • Also available with coupling and sleeve as a "kit": FT-OVERFLOWKIT 4 -in. Biotube Jr. (includes cartridge and housing) FT J 04 18 Options: Blank = no options M = flow modulation plate installed A = float bracket attached Cartridge height (inches) Filte diameter (inches) W fits Type 3034 outlet tee S = fits Schedule 40 outlet tee Blank = 1/8" filtration P r 1/16" filtration Junior series Biotube effluent filter series 4 -in. Biotube Filter Insert (cartridge only) FTi 0418- - —T For customized options (e.g., NC indicates North Carolina regions) \,„, fits Type 3034 outlet tee 5 = fits Schedule 40 outlet tee Cartridge height (inches) Filte diameter (inches) Blank = 1/8" filtration P = 1 /16" filtration Insert Biotube effluent filter series 4 -in. Biotube Effluent Filter Extendible PVC handle 4 -in. Biotube Jr. -Stainless steel set screws=' Top seal plate ----- Air vents ----- Biotube® Biotube° filter cartridge )000( Solid base Filter housing Distributed By: Concrete Distribution Box n9 DBox 8C el inlet, T outlets) & Riser DB 1 Top View End View Riser Section Side View nock Down Baffle 12"" End View Section View 28" 25" 14" 5I + 4 d 28" Lid View 6000 PSI Concrete • 7 Outlet equal flow • Slide -in Baffle • 4" Pipe penetration ports • Connectors cast into the box • 12" Riser available Weight: D -Box with Baffle - 200 lbs D -Box Lid - 75 lbs D -Box Riser -140 lbs Water (P.O. Boar 925719) 3954764 Rd 317 Wastewater WVALLEY • Systems • Produr s Fax: (719) 395-3727BuenaV, CO81211 PRECAST, Inc. • service Website: www.valleyprecastcom Email: frantdesk©valleyprecastcom PR THIS WEIR SHAPE IS SELF LEVELING THESE RIBS PROVIDE FRICTION FIT FOR ALL 4" PIPE ID 1.73 .09 C4.4 cm] C.2 cm] L_II-11 � 1 1.05 11 C2.7 cmc I TUL__ zt GEAR AND RACK PROVIDES POSITIVE ONE TIME LEVELING POLYLOK EQUALIZER PART NO. -3049 MATERIAL - FILLED POLYPROPYLENE INFILTRATOR® water technologies Quick4 Plus- Series The Quick4 Plus Standard Low Profile (LP) offers maximum strength through its four center structural columns. This chamber can be installed in a 36 -inch -wide trench. It is shorter in height than Infiltrator's other Standard model chambers, allowing for shallower installation. Like the original line of Quick4 chambers, it offers advanced contouring capability with its Contour Swivel ConnectionTM' which permits turns up to 15°, right or left. The Quick4 Plus All -in -One 8 and Quick4 Plus Endcaps provide increased flexibility in system design and configurations. Maximum Strength Quick4 Plus Standard LP Chamber Specifications Size 34"W x 53"L x 8"H (864 mm x 1346 mm x 203 mm) Effective Length 48" (1219 mm) Louver Height 6.3" (160 mm) Storage Capacity 32 gal (121 L) Invert Height 3.3" (84 mm), 9.6" (244 mm) APPROVED in The Quick4® Plus Standard Low Profile (LP) Chamber Quick4 Plus Standard Low Profile (LP) Chamber Benefits: • Low profile design makes this chamber ideal for shallow applications • Reduces imported fill needed for cap and fill systems • Four center structural columns offer superior strength • Advanced contouring connections • Latching mechanism allows for quick installation • Four -foot chamber lengths are easy to handle and install • Supports wheel loads of 16,000 lbs/axle with 12" of cover Quick4 Plus All -in -One Periscope Benefits: • Allows for raised invert installations • 180° directional inletting • 12" raised invert is ideal for serial applications Quick4 Plus All -in -One 8 Endcap Benefits: • May be used at the end of chamber row for an inlet/outlet or can be installed mid -trench • Mid -trench connection feature allows center feed inletting of chamber rows • Center -feed connection allows for easy installation of serial distribution systems • Variable pipe connection options allow for side, end or top inletting • Piping drill points are set for gravity or pressure pipe Quick4 Plus Endcap Benefits: • Simple, flat design • Allows installation of a pipe from the end only • Piping drill points are set for gravity or pressure pipe • Certified by the International Association of Plumbing and Mechanical ��� Officials (IAPMO) Quick4 Plus- Series Quick4 Plus Standard Low Profile Chamber PI Quick4 Plus All -in -One 8 Endcap 3.3" INVERT 8" 18" --�� Quick4 Plus All -in -One Periscope INVERT 9.6" r -- INFILTRATOR° water technoiog' ies U.S. Patents: 4,759,661; 5,017,041; 5,156,488; 5,336,017; 5,401,116; 5,401,459; 5,511,903; 5,716,163; 5,588,778; 5,839,844 Canadian Patents: 1,329,959; 2,004,564 Other patents pending. Infiltrator, Equalizer, Quick4, and Sidewinder are registered trademarks of Infiltrator Water Technologies. Infiltrator is a registered trademark in France. Infiltrator Water Technologies is a registered trademark in Mexico. Contour, MicroLeaching, PolyTuff, ChamberSpacer, MultiPort, PqsiLock, QuickCut, QuickPlay, SnapLock and StraightLock are trademarks of Infiltrator Water Technologies. PolyLok is a trademark of PolyLok, Inc. TUF-TITE is a registered trademark of TUF-TITE, INC. Ultra -Rib is a trademark of IPD( Inc. © 2016 Infiltrator Water Technologies, LLC. All rights reserved. Printed in U.S.A. 10.4" EFFECTIVE LENGTH* When installed between 2 chambers. 13.3" EFFECTIVE LENGTH* When installed at the end of a trench. 4 Business Park Road P.O. Box 768 Old Saybrook, CT 06475 860-577-7000 • Fax 860-577-7001 1-800-221-4436 www.infiltratorwater.com I�� � �► w �w a►rn .w r,■o R>. a7■; Rlru r ti ■ >M 111 r �II7 as WV ;VI VII. ;AV gar ,a• I. 5: Lai. �. .. ,�III .yA Li.io w� co. ra lei wAisa ir,ii.7 ram No 48" (EFFECTIVE LENGTH) Quick4 Plus Endcap 8" 18" 3.3" INVERT 4.5" EFFECTIVE LENGTH* 6' INFILTRATOR WATER TECHNOLOGIES, LLC ("INFILTRATOR") Infiltrator Water Technologies, LLC STANDARD LIMITED Drainfield WARRANTY (a) The structural integrity of each chamber, endcap, EZflow expanded polystyrene and/or other accessory manufactured by Infiltrator ("Units"), when installed and operated in a leachfield of an onsite septic system in accordance with Infiltrator's instructions, is warranted to the original purchaser ("Holder") against defective materials and workmanship for one year from the date that the septic permit is issued for the septic system containing the Units; provided, however, that if a septic permit is not required by applicable law, the warranty period will begin upon the date that installation of the septic system commences. To exercise its warranty rights, Holder must notify Infiltrator in writing at its Corporate Headquarters in Old Saybrook, Connecticut within fifteen (15) days of the alleged defect. Infiltrator will supply replacement Units for Units determined by Infiltrator to be covered by this Limited Warranty. Infiltrator's liability specifically excludes the cost of removal and/or installation of the Units. (b) THE LIMITED WARRANTY AND REMEDIES IN SUBPARAGRAPH (a) ARE EXCLUSIVE. THERE ARE NO OTHER WARRANTIES WITH RESPECT TO THE UNITS, INCLUDING NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE (c) This Limited Warranty shall be void if any part of the chamber system is manufactured by any- one other than Infiltrator. The Limited Warranty does not extend to incidental, consequential, spe- cial or indirect damages. Infiltrator shall not be liable for penalties or liquidated damages, including loss of production and profits, labor and materials, overhead costs, or other losses or expenses incurred by the Holder or any third party. Specifically excluded from Limited Warranty coverage are damage to the Units due to ordinary wear and tear, alteration, accident, misuse, abuse or neglect of the Units; the Units being subjected to vehicle traffic or other conditions which are not permitted by the installation instructions; failure to maintain the minimum ground covers set forth in the installation instructions; the placement of improper materials into the system containing the Units; failure of the Units or the septic system due to improper siting or improper sizing, excessive water usage, improper grease disposal, or improper operation; or any other event not caused by Infiltrator. This Limited Warranty shall be void if the Holder fails to comply with all of the terms set forth in this Limited Warranty. Further, in no event shall Infiltrator be responsible for any loss or damage to the Holder, the Units, or any third party resulting from installation or shipment, or from any product liability claims of Holder or any ihlyd party. For this Limited Warranty to apply, the Units must be installed in accordance with all site conditions required by state. and local codes; all other applicable laws; and Infiltrator's installation instructions. (d) No representative of Infiltrator has the authority to change or extend this Limited Warranty. No warranty applies to any party other than the original Holder. The above represents the Standard Limited Warranty offered by Infiltrator. A limited number of states and counties have different war- ranty requirements. Any purchaser of Units should contact Infiltrator's Corporate Headquarters in Old Saybrook, Connecticut, prior to such purchase, to obtain a copy of the applicable warranty, and should carefully read that warranty prior to the purchase of Units. PLUS01 0816 Contact Infiltrator Water Technologies' Technical Services Department for assistance at 1-800-221-4436