HomeMy WebLinkAboutGeotechnical Engineering Consultation 07.19.17tr CTL ITHOMPSON
@
July 19,2017
Phil Vaughan Construction Management, lnc,
1038 County Road 323
Rifle, CO 81650
Attention: Mr.PhilVaughan
Subject: Geotechnical Engineering Consultation
Garage Building
Vaughan Residence
1038 CountY Road 323
Garfield CountY, Colorado
Project No. GS05694.000-1 45
Thís letter provides our geotechnical recommendations for the planned
garage building to be constructed at 1038 County Road 323 in Garfield County,
Óoloiado. Planned buitding construction, anticipated subsurface conditions, and
our foundation recommendations for the building are provided below'
Pla4ned Const-fuction
The garage will have plan dimensions of 30 feet by 86 feet. Walls will be
framed with} x 6 wood studs and the roof system willbe comprised of wood trusses
that span âcross the shorter dimension. The building will have five overhead doors
on the south wall, providing access to four parking bays, The finished floor slab
elevatÍon in the building willbe 5309 feet. Existing ground surfacewithin the building
footprint varies from about 5307 to 5310. The preferred foundation is a concrete
slab-on-ground with turned down edges-
Subsurface Conditions
Subsurface conditions are anticipated to be similar to those observed in
exploratory pits excavated as part of our field ínvestigation for a 2004 addition to the
Vaughan Residence, Subsufface conditions consisted of 2.5 and 6 feet of silty
sanðy clay underlain by clayey to silty gravel with basalt cobbles and boulders to the
total åxplıred depth of 7,5 feet below existing ground surface. Free ground water
was not observed in the exploratory pits.
Site Earthwork
Stripping depth will likely average about 6 incìes to remove topsoil and
organics fiom below the planned building. We believe fillthickness of 2 feet or less
w¡ìi ne required to achieve subgrade for finished floor. Significant overlot grading
cuts and fill are not anticipated for building pad construction.
234 Center Drive I Glenwood Springs' Colorado 81601
Iefephone: 970-945-2809 F ax'. 97Ð'945-7 41 1
îffi
Excavations for utilities and foundation walls can be accomplished using
conventional, heavy-duty construction equipment. Excavation sides will need to be
sloped or braced to meei local, state and federalsafety regulations. We believethe
clay will classify as a Type B soil and the gravel will classify as a Type C soil based
on 'OSH¡ stanáards governing excavations. Temporary slopes deeqerthan 4 feet (if
requíred) should be nã steeperthan 1 to 1 (horizontal to vertical) in Type B soils and
t.S to 1 in Type C soils. Contractors should identify the soils encountered in the
excavations ând refer to OSHA standards to determinê appropriate slopes'
Structural Fill
The silty sandy clay soil at this site possesses the potential for. moderate
consolidation when wêttedunder load. We recommend placement of at least 1 foot
of structural fill below the slab-on-ground foundation. We recommend the granular,
structural fitl consist of an aggregate base course, such as a CDOT Class 6 or
similar soil.
The subgrade surface that witl support structuralfill should be scarified to a
depth of at leas[6 inches, moisture-treated, and compacted. Structuralfill should be
moisture-treated to within 2 percent of optimum moisture content and compacted to
at least g8 percent of maximum standard Proctor (ASTM D 698) dry density' Water
required to increase the structuralfillsoil moisture contentto the specified moisture
content should be uniformly mixed into the fill soil prior to compaclion We
recommend loose fill lífts of i 0 inches or less. The actual thickness of fill lifis that
can be properly compacted will depend on the type of compaction equipment'
Slab-on Ground
In our opinion, a slab-on-ground is a reasonable system for thefoundation
and floor of the proposed garage at this site. We recommend supporting-the
slab on a 1-foot thicknessóf densely-compacted, granular structural fill. Design
criteria for a slab-on-ground foundation/floor system are provided below.
1. The slab-on-ground foundation should be constructed on a
minimum 1 -foot thickness densely-compacted, granular structural
f ill.
Z. The slab should be heavily reinforced and preferably in a single
monolithic configuration tô help maintain its integrity in the event of
ground movement. The slab turned down edges sftot!! be
"
ãesigned for a maximum allowable soil pressure of 1,500 psf.
3, Modulus of subgrade reaction {Ks) is normally used for a slab-on-
ground design. the modulus of subgrade reaction is dependent
upon the coñrpressibility of the foundation soils and the size (or
PHIL VAUSHAN CONSTRUCTION MANAGEMENT
VAUGHAN RESIDENCE ADDITION
PRoJËGT NO. GS05094.000-l 46
c:lus6|,6\cdownlng\EoxtPrcjoctslGlenwood sprlf,gE . PfoJôèt$6506694.0Û0t14613. Lêtters\G805öS',1.000 1¡Í6 Lz'docx
2
4
5.
effective loaded area) of the foundation, lf the entire slab
foundation is uniformiy loaded, then a Ks value of 200 pci' A friction
coefficient of 0.45 can be used for lateral resistant between
concrete and granular structural fill.
Lateral loads can be resolved by evaluating passive resistance
uring an equivalent fluid density o'r 325 pcf for the onsite soils,
piàuioeo the backfill is compacted and is not removed'
soils beneath the foundation must be protected from freezing. The
granular structural fill and natural soils are not significantly
ãusáãpt¡Ue to frost heave. We recommend the perimeter of the
slab bä turned down to extend at least 24 inches below exterior
grà0". The Garfield county building department should be
ıontacted for specific frost depth requirements'
Reviewed by:
ffi
?e.
Surface Drainage
Surface drainage is critical to the performance of building foundations and
slabs. Þrop"r surfacJdrainage can help controlthe amount of surface water
that penetrates anJ wets the ãubgrade soils below the slab. The ground surface
surróunding tne nuìtding should bä sloped to drain away from the building in all
directions. Roof gutterã and downspouts should be provided.
Limitations
This geotechnical engineering consultation was provided in a manner
consistent with that level of ð"t" "nd
skill ordinarily exercised by geote-chnical
;gi;;rr currently practicing under similar conditions in the locality of this
pro]ect. No warranty, express or lmplied, is made. lf we can be of further
i"*i"" in discussing the'contents of this report, please call.
Very truly rS
crllr
f--t,
P-r,,+r
J es D. Kellogg, P.E.
n ManagerPri
cc:
:JDK;cd
Via email to Phil@Pvcmi.com
PHIL VAUGHAN CONSTRUCTION MÀNAGEMENT
VAUGHAN RESIDENCE ADDITION
PROJECT NO. GS05894.000'145