Loading...
HomeMy WebLinkAboutAs-built drawingaln ree ' mg way MAINTENANCE NOTES Unit #7 (3 Bed) Unit #8 (1 Bed) 1-1/2"x1-1/4" SCH.40 PVC REDUCER, TYP. 1-1/2"0 SCH.40 PVC DISTRIBUTION LINES & MANIFOLD, TYP. AUTOMATIC DISTRIBUTION VALVE ASSEMBLY 40 (4x10) ARC36 OR 4x13 QUICK 4 UNITS (600 SF MIN. PER BED) V PROFILE PIT � SOIL EVALUATION 1. SOIL PERCOLATION TESTS IN THE NATIVE SOILS (SILTY CLAY LOAM) RANGED FROM 43-75 MPI (60 MPI AVERAGE) INDICATING A SOIL TYPE OF 3 AND AN LTAR OF 0.35 GPD/SF. 2. NO GROUNDWATER WAS ENCOUNTERED OR OBSERVED IN THE 8 -FOOT DEEP PROFILE PIT. SITE EVALUATION 12" SURFACE TOPSOIL 1, SITE AND SOIL EVALUATIONS WERE PERFORMED BY: DER/C J. WALTER, PE BOUNDARIES UNLIMITED INC. 923 COOPER AVE., STE. 201 GLENWOOD SPRINGS, CO 81601 970.945.5252 ATP#2 R116' MIN, WELL SETBACK FLUSH VALVE ASSEMBLY, TYP. (4 PER BED) Unit #3 (1 Bed) INSPECTION PORT, TYP. (4 PER BED) SILTY CLAY LOAM (TYPE -3) 1. TO ENCOURAGE THE HEALTH AND LONGEVITY OF THE OWTS SYSTEM, THE OWNER SHALL CONSIDER THE FOLLOWING: 1.A. MINIMIZE THE AMOUNT OF WATER THAT GOES DOWN THE DRAIN, THE BETTER YOUR SYSTEM WILL WORK. 1.B. MINIMIZE SOLIDS GOING DOWN THE DRAIN. 1.C. ELIMINATE GARBAGE DISPOSALS OR KEEP THE USE OF GARBAGE DISPOSALS TO A MINIMUM. 1.D. MINIMIZE GREASE AND OILS THAT GO DOWN THE DRAIN. 1.E. USE LINT FILTERS ON LAUNDRY MACHINE DRAINS. 1.F. KEEP SAND AND DIRT OUT OF THE BUILDING DRAIN. 1.G. AVOID FLUSHING SANITARY NAPKINS OR PAPER PRODUCTS OTHER THAN TOILET PAPER. 1.H. DO NOT USE LYE -BASED DRAIN UNCLOGGER CHEMICALS SUCH AS DRAINO, OVEN -OFF, OR OTHER STRONG CLEANING AGENTS. 1.1. DO NOT PUT ANY "ROOT DETERRENTS" DOWN THE DRAIN. 1.J. DO NOT POUR PAINT THINNER, PESTICIDES, PAINTS OR PHOTO LAB CHEMICALS DOWN THE DRAIN 1.K. MINIMIZE USE OF CHLORINE BLEACH AND TOILET ADDITIVES. 3. SETBACK REQUIREMENTS FOR A TREATMENT LEVEL 1 (TL1) STA TRENCH/BED, UNLINED SAND FILTER OR SEEPAGE PIT (PER TABLE 7-1) AND AN ADWF=1,199 GPD: 3.A. SPRING OR WELL=100' + 16' = 116' 3.B. POTABLE WATER SUPPLY LINE=25' 3.C. POTABLE WATER SUPPLY CISTERN= 25' 3.D. DWELLING = 20' 3.E. PROPERTY LINE, PIPE OR LINED IRRIGATION DITCH =10' 3.F. INTERMITTENT IRRIGATION LATERAL, INFILTRATION STRUCTURE=25' 3.G. LAKE, WATER COURSE, IRRIGATION DITCH, STREAM OR WETLAND=50' + 16' = 66' 3.H. DRY GULCH, CUT BANK OR FILL AREA=25' 3.1. SEPTIC TANK=5' 3.J. RESTRICTIVE LAYER OR GROUNDWATER (VERTICAL): 4' (TL 1, GRAVITY FEED) ATP#4 Unit #4a (1 Bed) Unit #4b (1 Bed) Unit #1 (1 Bed) 3. SETBACK REQUIREMENTS FOR THE SEPTIC TANK SHALL BE (PER TABLE 7-1): 3.A. SPRING OR WELL=50 3.B. POTABLE WATER SUPPLY LINE=10' 3.C. POTABLE WATER SUPPLY CISTERN = 25' 3.D. DWELLING=5' 3.E. PROPERTY LINE, PIPE OR LINED IRRIGATION DITCH=10' 3.F. INTERMITTENT IRRIGATION LATERAL, INFILTRATION STRUCTURE=10' 3.G. LAKE WATER COURSE, IRRIGATION DITCH, STREAM OR WETLAND=50' 3.H. DRY GULCH, CUT BANK OR FILL AREA=10' 3.1. STA TRENCH/BED, UNLINED SAND FILTER OR SEEPAGE PIT=5' 2. THE OWNER SHALL CONTRACT WITH A SEPTIC TANK INSPECTOR TO INSPECT THE TANK ANNUALLY FOR GREASE AND SEDIMENT ACCUMULATION. THE INSPECTOR SHALL REMOVED AND PROPERLY DISPOSED OF ACCUMULATED GREASE AND SEDIMENT AS NEEDED TO ENSURE PROPER FUNCTION OF THE SYSTEM. 4.56 SYSTEM NOTES 1. ALL CONSTRUCTION SHALL BE IN ACCORD\NCE WITH GARFIELD COUNTY ONSITE WASTEWATER TREATMENT SYSTEMS (OWTS) REGULATIONS, MOST CURRENT EDITION AND LOCAL AGENCY REQUIREMENTS WHICH MAY OR MAY NOT SPECIFICALLY BE NOTED ON THE DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR KNOWING AND CONFORMING TO SUCH SPECIFIC DETAILS AS ARE REFERRED TO IN THE ABOVE MENTIONED REGULATIONS, THIS DRAWING DOES NOT CONSTITUTE AN OWTS PERMIT. A PERMIT MUST BE OBTAINED FRCM APPROPRIATE LOCAL AGENCY. THE ENGINEER MUST OBSERVE THE CONSTRUCTED SYSTEM BEFORE BACKFILL AND PROVIDE A LETTER OF INSPECTION AS REQJIRED BY THE LOCAL AGENCY. A REQUEST FOR INSPECTION MUST BE MADE BY THE CONTRACTOR AT LEAST 48 -HOURS PRIOR 10 I HL LXI'LCTLU TIME UF BAUKFIL.ING, STYROFOAM INSULATED FIBERGLASS LID WITH STAINLESS STEEL BOLTS AND URETHANE GASKET 24"0 PVC ENCLOSURE ORENCO 4 ZONE ZONE 1-1/2110 DISTRIBUTING VALVE ASSEMBLY (V6404A) CHECK VALVES ONE (1) THREE (3) BEDROOM RESIDENCE PLUS SIX (6) ONE (1) BEDROOM RESIDENCES PLUS FOUR (2) RECREATIONAL VEHICLE (RV) SPACES USING DOSING AND TREATMENT LEVEL 1 (TL1). 2.B. AVERAGE DAILY WASTEWATER FLOW (ADWF): 2.B.1. SINGLE FAMILY DWELLING WITHOUT A LAUNDRY WASHER (NO LAUNDRY FACILITIES ONSITE): 75 gpdc -19.5 gpdc = 55.5 gpdc. 2.B.2. TRAVEL TRAILER PARKS (RV) WI1H INDIVIDUAL WATER AND SEWER HOOKUP PER UNIT (NO LAUNDRY FACILITIES ONSITE): 50 gpdc 2.B.3. ADWF = (55.5 gpdc * (3 BEDROOMS * 1 UNIT+1 BEDROOM * 6 UNITS) * 2 PERSONS/BEDROOM )) + (50 gpdc * (2 RVs * 2 PERSONS/R DOSING IS TO BE USED. THEREFORE 48 HOURS OF DETENTION IS REQUIRED: ADWF*(48/hrs/24hrs) = 1,199 gpd * (48/HRS/24HRS) = 2,398 GALLONS INSTALL A 2,000 -GALLON SINGLE -COMPARTMENT TANK IN SERIES WITH A 1,000 -GALLON TWO (2) COMPARTMENT TANK WITH A HIGH HEAD DOSING PUMP SYSTEM IN THE 2nd COMPARTMENT DF THE SMALLER TANK. 3.C. INSTALL AN EFFLUENT FILTER IN THEOUTLET TEE OF THE 2,000 -GALLON SINGLE -COMPARTMENT TANK. 3.D. THE TANK ARE NOT SUBJECT TO BUCYANCY. 3. SEPTIC TANK (SEC.43.9.B.2.a): 3.A. 3.B. 1-1/21'0 SCH.80 PVC FORCE MAIN W/ 45° BENDS, TYP, (280± LF) 1-1/2"0 SCH.80 PVC FROM PUMP Scale: N.T.S. 4. ABSORPTION AREA CALCULATIONS Unit #9 2 Bed) Scale: N.T.S. INTERCEPT THE EXISTING SEWER MAIN w/ 6" SCH40 PVC (120± LF) Unit #6 (1 Bed) CDPHE APPROVED 2,000 -GALLON SINGLE -COMPARTMENT PRECAST CONCRETE SEPTIC TANK 1"0 BALL VALVE & TREADED ASSEMBLY 1-1/4" x 1" PVC REDUCER 1-1/4'0 PVC ELBOW 1-1/4'10 PVC DISTRIBUTION PIPE 4.A. GROUNDWATER WAS NOT ENCOUNTIRED AND THE PROPERTY CONTAINS SLOPES LESS THAN 20%. THEREFORE, BUT THE ELEVATION OF THE SYSTEM IS HIGHER THAN THE ELEVATION OF THE SEPTIC TANKS. THEREFORE, THE SYSTEM SHALL BE A PRESSURE DOSED SHALLOW GRAVELLESS CHAMBER SYSTEM IN A BED CONFIGURATION. 4.B. SOILS WERE ANALYZED BY BOUNDARES UNLIMITED INC. (SEPTEMBER 24, 2017) TO BE SILTY CLAY LOAM WITH PERCOLATION RATES BETWEEN 43-70 MINUTES PER INCH (MPI) (AVERAGE = 60 MPI. THEREFORE, THE SOIL TYPE IS CONSIDERED TO BE TYPE -3 WITH A TREATMENT LEVEL 1 LONG TERM ACCEPTANCE RATE (LTAR) OF 0.35 gpd/SF FOR TL1 4.C. MINIMUM SOIL TREATMENT AREA, A: A = ADWF = 1199 = 3,425.8 S.F. LTAR 0.35 gpd/S.F. 4.D. SIZE ADJUSTMENT FACTORS: PRESSURE DOSED BED = 1.0; CHAMBERS IN BED CONFIGURATION= 0.7 4.D.1. A, adj = 3,425.8 SF * 1.0* 0.7 = 2,399 SF 4.E. GRAVELLESS CHAMBER SYSTEM: 4.E.1. INFILTRATOR QUICK4: 2,399 SF /12 SF/UNIT = 200 UNITS IN A MULTIPLE BED CONFIGURATION. 4.E.2. ADS ARC36 (STANDARD): 2,399 F / 15 SF/UNIT = 160 UNITS IN A MULTIPLE BED CONFIGURATION. 5. THIS SYSTEM IS SIZED FOR TYPICAL DOMESTIC WASTES ONLY. BACKWASH OR FLUSHING FLOWS FOR REVERSE OSMOSIS UNITES OR WATER SOFTENERS AND/OR FILTERS SHOULD NOT BE INTRODUCED INTO THIS SYSTEM. 6. CLEAN OUTS ARE REQUIRED AT THE HOUSES/RV(s) AND AT ALL BENDS AND AT LEAST EVERY 100 -FEET BETWEEN THE HOUSES AND THE SEPTIC TANK. 7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING ALL WATER TIGHT COMPONENTS THROUGHOUT THE SYSTEM TO PREVENT INFILTRATION. 8. INSTALL RISERS AS NECESSARY TO BRING t\LL ACCESS PORTS TO FINAL GRADE. PORTS SHALL BE MARKED IF CAPS ARE TO BE BURIED. 9. INSTALL 3 -INCHES OF BLUEBOARD INSULAE ION, 3 -FEET WIDE, OVER SEWER AND EFFLUENT PIPE WHEREVER DEPTH IS LESS THAN 3 -FEET. UNDER NO CIRCUMSTANCES SHALL COVER BE LESS 1HAN 2 -FEET. 10. LOCATIONS OF ALL COMPONENTS MAY BEVARIED AS NECESSARY AS LONG AS ALL MINIMUM DISTANCES AND SLOPES MEET THOSE REQUIRED. EXISTING SEPTIC TANKS (2000± GALLONS Existing Septic Field TO SUPPORT: UNITS #6, 9 & 11 RV(s) #5, 10,12,15, & 16) CDPHE APPROVED 1,000 -GALLON Storage Units TWO-COMPARTMENT PRECAST CONCRETE SEPTIC TANK W/ HIGH HEAD DOSING PUMP Item # 2000T-1 CP 2000 Gallon Top Seam One Compartment Item # I 000T2CP-HH Storage Units Union Pacific Railroad GENERAL ABSORPTION AREA NOTES 1. INSTALL CHAMBER UNITS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. 2. ABSORPTION BEDS SHALL NOT EXCEED 12' WIDE BY 100 -FEET IN LENGTH, SHALL PARALLEL THE TOPOGRAPHY AND SHALL BE INSTALLED IN A RECTANGULAR PATTERN WHENEVER POSSIBLE. N:\PROJECTS\2017\17026-3M-Green Diamond\dwg\17026-C-Topo.dwg 9/26/2017 11:29 AM THE BOTTOM OF THE ABSORPTION BED SHALL BE LEVEL AND THE BOTTOM AND SIDEWALLS MUST BE RAKED TO REMOVE ANY SOIL SMEARS INCURRED DURING THE EXCAVATION. FAILURE TO DO SO MAY REQUIRE THE CONTRACTOR TO REPLACE THE ABSORPTION FIELD AT HIS/HER OWN EXPENSE. 4. DRAINAGE SWALES ARE TO BE PROVIDED ABOVE AND AROUND THE FIELD, AS NECESSARY, TO PREVENT SURFACE RUNOFF FROM ENTERING ABSORPTION AREA. 5. NO EXCAVATION OF THE ABSORPTION FIELD IS TO BE DONE DURING WET WEATHER AND USE OF RUBBER TIRE VEHICLES OVER THE ABSORPTION AREA IS STRICTLY PROHIBITED. 6. UNSUITABLE MATERIAL EXISTING WITHIN THE FIELD SHALL BE EXCAVATED AND BACKFILL SHALL CONSIST OF IMPORTED LOAMY SAND OR SANDY GRAVEL. THE ENGINEER SHALL BE CONTACTED IF BEDROCK OR GROUNDWATER IS ENCOUNTERED IN THE EXCAVATION. DESIGN NOTES • Design per performance test per ASTM C1227 • Top surface area 87.75 ft2 • f'c @ 28 days; concrete = 6,000 PSI Min. Installation: • Tank to be set on 5" min. sand bed or pea gravel • Tank to be backfilled uniformly on all sides in lifts less than 24" and mechanically compacted • Excavated material may be used for backfill, provided large stones are removed • Excavation should be dewatered and tank filled with water prior to being put in service for installation with water tahle less than 2' below grade • Meets C1644-06 for resilient connectors • Inlet and Outlet identified above pipe • Delivered complete with internal piping • Secondary safety screen available with PVC riser 20" Clear Access Top View 7. fOPSOIL COVER MAY BE VARIED (1 -FOOT MINIMUM, ?-FOOT MAXIMUM) TO ALLOW FOR LANDSCAPING. SEPTIC TANK & PUMP SYSTEM NOTES: ATTACH REMOVABLE CAP OR THREADED CLEANOUT ASSEMBLY. INSTALL MARKER IF CAP IS TO BE BURIED. 4"0 PVC SOLID PIPE CUT TO FIT 4"0 COUPLING (UNION). USE A HOLE SAW TO CUT OUT CIRCLE OFF THE CENTER OF THE UNIT 4"0 PERFORATED PVC PIPE. EXTEND PIPE TO REST ON BOTTOM OF THE BED GRAVELLESS CHAMBER SYSTEM: ADVANCED DRAINAGE SYSTEMS ARC36 (STANDARD), INFILTRATOR QUICK 4, OR ENGINEER APPROVED EQUAL. Flexible Boot Butyl Rubber Sealant SYSTEM TO BE INSTALLED IN CONFORMANCE WITH MANUFACTURER'S RECOMMENDATIONS. 2. THE DISCHARGE PUMP SYSTEM SHALL BE AN ORENCO BIOTUBE PROPAK WITH 30 GPM, 1/2 HP, 115 V HIGH HEAD VERTICAL TURBINE PUMP AND DEMAND DOSE CONTROLS. FLOATS SHALL BE SET FOR A DOSING VOLUME OF 400 GALLONS (3 DOSES PER DAY). CONTACT SCG ENTERPRISES AT 303.697.9404 OR VALLEY PRECAST, INC. AT 719.395.6764 FOR SYSTEM SPECIFICATIONS AND INSTALLATION PROCEDURES. 1-1/4'0 SCH. 40 PVC PRESSURE DOSING PIPE WITH 3/16"0 HOLES DRILLED EVERY 48"O.C. (FACING UP) 3. THE SYSTEM SUPPLIER SHALL PROVIDE THE OWNER WITH AN OPERATIONS AND MAINTENANCE MANUAL WHICH INCLUDES A MAINTENANCE SCHEDULE, *See installation guide on our website ALLOWABLE BURY (Based on Water Table) WATER TABLE ALLOWABLE EARTH FILL 0' -0" 3'-0" 1'-0" 3'-0" 2'-0" 4'-0" 3'-0, 4'-0, DRY 4'-0" ALLOWABLE BURY (Based on Water Table) WATER TABLE ALLOWABLE EARTH FILL 0' -0 2'-0" 1'-0 3'-0" 2'-0' 3'-0" 3-0' 4'-0" DRY 4'-0" Top View 20" Clear Access DESIGN NOTES • Design per )erformance test per ASTM C1227 • Top surface area 46.25 ft2 • f'c @ 28 dhys; concrete = 6,000 PSI Min. Installation: • Tank to be ;et on 5" min. sand bed or pea gravel • Tank to be backfilled uniformly on all sides in lifts less thin 24" and mechanically compacted • Excavated naterial may be used for backfill, provided large stones are removed • Excavation should be dewatered and tank filled with water prior to being put in service for installation with water table less than 2' below grade • Meets C1644-06 for resilient connectors • Inlet and Outlet identified above pipe 53" • Delivered complete with internal piping • Secondary safety screen available with PVC riser 4. THE PUMP SYSTEMS SHALL BE CONNECTED TO AN ALARM WHICH SHALL BE BOTH AUDIBLE AND VISIBLE, LOCATED NEAR A RESIDENCE AND ON A CIRCUIT SEPARATE FROM THE PUMP. 5. TANK DIMENSIONS ARE BASED ON A VALLEY PRECAST, INC. 2,000 GALLON ONE -COMPARTMENT TANK IN SERIES WITH A 1,000 GALLON TWO-COMPARTMENT TANK WITH A HIGH HEAD PUMP. • 157" "1 Section View Flexible Boot Butyl Rubber Sealant Wires to Panel ----� 24" Minimum Height Ball Valve I *See installation guide on our website Service contracts available for maintenance Digging Specs invert Dimensions Net Capacity Net Weight Lid Tank Total 15' Long x 8' Wide 56" below inlet invert Inlet 56" Outlet 53" Length 162" Width 78" Height 68" 2,142 gallons 5,420 lbs . 15,140 lbs 20,560 lbs Section View I-� 106" Pump: • Lowers TSS and improves effluent quality to field • Easiest pump system to maintain on the market • Complete installation (wiring, panel, mounting and start-up procedures) • Complete warranty Digging Specs Invert Dimensions Net Capacity 11' Long x 7' Wide 561' below inlet invert Inlet 56" Outlet 73" Length 111" Width 60" Height 92" Inlet Side 687 gallons Outlet Side 323 gallons Total 1,010 gallons Net Weight Tank Total 2,620 lbs BOTTOM TO BE LEVEL AND FLAT OVER ENTIRE AREA TO WITHIN 0.1'±. (TYP.). IF NECESSARY TO ACHIEVE THIS SURFACE, IMPORT CONCRETE SAND TO USE AS [[Y[Lffi ¥Tl N9NTERED BOULDERS AND BACKFILL WITH LOAMY SAND OR SANDY GRAVELS. DO NOT USE COMPACTED MATERIALS. Pressure Dosing Chambo Bed tale: N.T.S. PREFABRICATED PIPE SUPPORT OR CHEMICAL RESISTANT ZIP TIE HANGING SYSTEM (PIPE @ 6" MIN. ABOVE BASE ) Water & Wastewater • Systems • Products • Service (719) 395-6764 28005 Co. Rd. 317 P.O. Box 925 Fax: (719) 395-3727 BuenaVista, CO 81211 woitr wmtalleyprecastecom Email: frontdesk@vaileyprecast.com 9,380 lbs 12,200 lbs Water & X719) 395-6764 28005 Co. Rd. 317 Wastewater P.O. Box 925 • Systems Fax: (719) 395-3727 Buena Vista, CO 81211 • Products • Service Website: www.valleyprecasiam Email: frontdesk@vaIleyprecastm /00, (ti Civil Engineering (41"; Surveying & Beyond Inc• 923 Cooker Avenue Suite 201 Glenwood Springs, CO 81601 tele: 970.945.5252 fax: 970.384.2833 Client Information: 3M Investors, LLC 737 Corral Drive Grand Junction, CO 81505 970.618.5244 0 30' NORTH 60' Scale: 1" = 30' GARFIELD COUNTY, COLORADO Green Diamond Rentals & Storage ci4 Onsite Wastewater Treatment Repair/Partial Replacement 0 CC a PROJECT NO, 17026 FILE NAME: 17026-c-topo.dwg DDej igner: Drafter: w Q Date: 9/25/17 ao Sheet C.1