MAINTENANCE NOTES
Unit #7
(3 Bed)
Unit #8
(1 Bed)
1-1/2"x1-1/4" SCH.40 PVC REDUCER, TYP.
1-1/2"0 SCH.40 PVC DISTRIBUTION LINES & MANIFOLD, TYP.
AUTOMATIC DISTRIBUTION VALVE ASSEMBLY
40 (4x10) ARC36 OR
4x13 QUICK 4 UNITS
(600 SF MIN. PER BED)
V PROFILE
PIT �
SOIL EVALUATION
1. SOIL PERCOLATION TESTS IN THE NATIVE SOILS (SILTY CLAY LOAM) RANGED FROM 43-75
MPI (60 MPI AVERAGE) INDICATING A SOIL TYPE OF 3 AND AN LTAR OF 0.35 GPD/SF.
2. NO GROUNDWATER WAS ENCOUNTERED OR OBSERVED IN THE 8 -FOOT DEEP PROFILE PIT.
SITE EVALUATION
12"
SURFACE
TOPSOIL
1, SITE AND SOIL EVALUATIONS WERE PERFORMED BY:
DER/C J. WALTER, PE
BOUNDARIES UNLIMITED INC.
923 COOPER AVE., STE. 201
GLENWOOD SPRINGS, CO 81601
970.945.5252
ATP#2
R116' MIN, WELL SETBACK
FLUSH VALVE
ASSEMBLY, TYP.
(4 PER BED)
Unit #3
(1 Bed)
INSPECTION PORT,
TYP. (4 PER BED)
SILTY
CLAY
LOAM
(TYPE -3)
1. TO ENCOURAGE THE HEALTH AND LONGEVITY OF THE OWTS SYSTEM,
THE OWNER SHALL CONSIDER THE FOLLOWING:
1.A. MINIMIZE THE AMOUNT OF WATER THAT GOES DOWN THE DRAIN,
THE BETTER YOUR SYSTEM WILL WORK.
1.B. MINIMIZE SOLIDS GOING DOWN THE DRAIN.
1.C. ELIMINATE GARBAGE DISPOSALS OR KEEP THE USE OF GARBAGE
DISPOSALS TO A MINIMUM.
1.D. MINIMIZE GREASE AND OILS THAT GO DOWN THE DRAIN.
1.E. USE LINT FILTERS ON LAUNDRY MACHINE DRAINS.
1.F. KEEP SAND AND DIRT OUT OF THE BUILDING DRAIN.
1.G. AVOID FLUSHING SANITARY NAPKINS OR PAPER PRODUCTS
OTHER THAN TOILET PAPER.
1.H. DO NOT USE LYE -BASED DRAIN UNCLOGGER CHEMICALS SUCH
AS DRAINO, OVEN -OFF, OR OTHER STRONG CLEANING AGENTS.
1.1. DO NOT PUT ANY "ROOT DETERRENTS" DOWN THE DRAIN.
1.J. DO NOT POUR PAINT THINNER, PESTICIDES, PAINTS OR PHOTO
LAB CHEMICALS DOWN THE DRAIN
1.K. MINIMIZE USE OF CHLORINE BLEACH AND TOILET ADDITIVES.
3. SETBACK REQUIREMENTS FOR A TREATMENT LEVEL 1 (TL1) STA TRENCH/BED, UNLINED
SAND FILTER OR SEEPAGE PIT (PER TABLE 7-1) AND AN ADWF=1,199 GPD:
3.A. SPRING OR WELL=100' + 16' = 116'
3.B. POTABLE WATER SUPPLY LINE=25'
3.C. POTABLE WATER SUPPLY CISTERN= 25'
3.D. DWELLING = 20'
3.E. PROPERTY LINE, PIPE OR LINED IRRIGATION DITCH =10'
3.F. INTERMITTENT IRRIGATION LATERAL, INFILTRATION STRUCTURE=25'
3.G. LAKE, WATER COURSE, IRRIGATION DITCH, STREAM OR WETLAND=50' + 16' = 66'
3.H. DRY GULCH, CUT BANK OR FILL AREA=25'
3.1. SEPTIC TANK=5'
3.J. RESTRICTIVE LAYER OR GROUNDWATER (VERTICAL): 4' (TL 1, GRAVITY FEED)
ATP#4
Unit #4a
(1 Bed)
Unit #4b
(1 Bed)
Unit #1
(1 Bed)
3. SETBACK REQUIREMENTS FOR THE SEPTIC TANK SHALL BE (PER TABLE 7-1):
3.A. SPRING OR WELL=50
3.B. POTABLE WATER SUPPLY LINE=10'
3.C. POTABLE WATER SUPPLY CISTERN = 25'
3.D. DWELLING=5'
3.E. PROPERTY LINE, PIPE OR LINED IRRIGATION DITCH=10'
3.F. INTERMITTENT IRRIGATION LATERAL, INFILTRATION STRUCTURE=10'
3.G. LAKE WATER COURSE, IRRIGATION DITCH, STREAM OR WETLAND=50'
3.H. DRY GULCH, CUT BANK OR FILL AREA=10'
3.1. STA TRENCH/BED, UNLINED SAND FILTER OR SEEPAGE PIT=5'
2. THE OWNER SHALL CONTRACT WITH A SEPTIC TANK INSPECTOR TO
INSPECT THE TANK ANNUALLY FOR GREASE AND SEDIMENT
ACCUMULATION. THE INSPECTOR SHALL REMOVED AND PROPERLY
DISPOSED OF ACCUMULATED GREASE AND SEDIMENT AS NEEDED TO
ENSURE PROPER FUNCTION OF THE SYSTEM.
4.56
SYSTEM NOTES
1. ALL CONSTRUCTION SHALL BE IN ACCORD\NCE WITH GARFIELD COUNTY ONSITE WASTEWATER TREATMENT SYSTEMS (OWTS) REGULATIONS, MOST CURRENT EDITION
AND LOCAL AGENCY REQUIREMENTS WHICH MAY OR MAY NOT SPECIFICALLY BE NOTED ON THE DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR KNOWING
AND CONFORMING TO SUCH SPECIFIC DETAILS AS ARE REFERRED TO IN THE ABOVE MENTIONED REGULATIONS, THIS DRAWING DOES NOT CONSTITUTE AN OWTS
PERMIT. A PERMIT MUST BE OBTAINED FRCM APPROPRIATE LOCAL AGENCY. THE ENGINEER MUST OBSERVE THE CONSTRUCTED SYSTEM BEFORE BACKFILL AND
PROVIDE A LETTER OF INSPECTION AS REQJIRED BY THE LOCAL AGENCY. A REQUEST FOR INSPECTION MUST BE MADE BY THE CONTRACTOR AT LEAST 48 -HOURS
PRIOR 10 I HL LXI'LCTLU TIME UF BAUKFIL.ING,
STYROFOAM INSULATED
FIBERGLASS LID WITH
STAINLESS STEEL BOLTS
AND URETHANE GASKET
24"0 PVC
ENCLOSURE
ORENCO 4 ZONE ZONE
1-1/2110 DISTRIBUTING
VALVE ASSEMBLY
(V6404A)
CHECK VALVES
ONE (1) THREE (3) BEDROOM RESIDENCE PLUS SIX (6) ONE (1) BEDROOM RESIDENCES PLUS FOUR (2) RECREATIONAL VEHICLE (RV) SPACES USING DOSING
AND TREATMENT LEVEL 1 (TL1).
2.B. AVERAGE DAILY WASTEWATER FLOW (ADWF):
2.B.1. SINGLE FAMILY DWELLING WITHOUT A LAUNDRY WASHER (NO LAUNDRY FACILITIES ONSITE): 75 gpdc -19.5 gpdc = 55.5 gpdc.
2.B.2. TRAVEL TRAILER PARKS (RV) WI1H INDIVIDUAL WATER AND SEWER HOOKUP PER UNIT (NO LAUNDRY FACILITIES ONSITE): 50 gpdc
2.B.3. ADWF = (55.5 gpdc * (3 BEDROOMS * 1 UNIT+1 BEDROOM * 6 UNITS) * 2 PERSONS/BEDROOM )) + (50 gpdc * (2 RVs * 2 PERSONS/R
DOSING IS TO BE USED. THEREFORE 48 HOURS OF DETENTION IS REQUIRED: ADWF*(48/hrs/24hrs) = 1,199 gpd * (48/HRS/24HRS) = 2,398 GALLONS
INSTALL A 2,000 -GALLON SINGLE -COMPARTMENT TANK IN SERIES WITH A 1,000 -GALLON TWO (2) COMPARTMENT TANK WITH A HIGH HEAD DOSING PUMP
SYSTEM IN THE 2nd COMPARTMENT DF THE SMALLER TANK.
3.C. INSTALL AN EFFLUENT FILTER IN THEOUTLET TEE OF THE 2,000 -GALLON SINGLE -COMPARTMENT TANK.
3.D. THE TANK ARE NOT SUBJECT TO BUCYANCY.
3. SEPTIC TANK (SEC.43.9.B.2.a):
3.A.
3.B.
1-1/21'0 SCH.80 PVC
FORCE MAIN W/ 45°
BENDS, TYP, (280± LF)
1-1/2"0 SCH.80
PVC FROM PUMP
Scale: N.T.S.
4. ABSORPTION AREA CALCULATIONS
Unit #9
2 Bed)
Scale: N.T.S.
INTERCEPT THE EXISTING
SEWER MAIN w/ 6" SCH40
PVC (120± LF)
Unit #6
(1 Bed)
CDPHE APPROVED
2,000 -GALLON
SINGLE -COMPARTMENT
PRECAST CONCRETE
SEPTIC TANK
1"0 BALL VALVE
& TREADED
ASSEMBLY
1-1/4" x 1" PVC
REDUCER
1-1/4'0 PVC
ELBOW
1-1/4'10 PVC
DISTRIBUTION PIPE
4.A. GROUNDWATER WAS NOT ENCOUNTIRED AND THE PROPERTY CONTAINS SLOPES LESS THAN 20%. THEREFORE, BUT THE ELEVATION OF THE SYSTEM IS HIGHER
THAN THE ELEVATION OF THE SEPTIC TANKS. THEREFORE, THE SYSTEM SHALL BE A PRESSURE DOSED SHALLOW GRAVELLESS CHAMBER SYSTEM IN A BED
CONFIGURATION.
4.B. SOILS WERE ANALYZED BY BOUNDARES UNLIMITED INC. (SEPTEMBER 24, 2017) TO BE SILTY CLAY LOAM WITH PERCOLATION RATES BETWEEN 43-70 MINUTES
PER INCH (MPI) (AVERAGE = 60 MPI. THEREFORE, THE SOIL TYPE IS CONSIDERED TO BE TYPE -3 WITH A TREATMENT LEVEL 1 LONG TERM ACCEPTANCE RATE
(LTAR) OF 0.35 gpd/SF FOR TL1
4.C. MINIMUM SOIL TREATMENT AREA, A:
A = ADWF = 1199 = 3,425.8 S.F.
LTAR 0.35 gpd/S.F.
4.D. SIZE ADJUSTMENT FACTORS: PRESSURE DOSED BED = 1.0; CHAMBERS IN BED CONFIGURATION= 0.7
4.D.1. A, adj = 3,425.8 SF * 1.0* 0.7 = 2,399 SF
4.E. GRAVELLESS CHAMBER SYSTEM:
4.E.1. INFILTRATOR QUICK4: 2,399 SF /12 SF/UNIT = 200 UNITS IN A MULTIPLE BED CONFIGURATION.
4.E.2. ADS ARC36 (STANDARD): 2,399 F / 15 SF/UNIT = 160 UNITS IN A MULTIPLE BED CONFIGURATION.
5. THIS SYSTEM IS SIZED FOR TYPICAL DOMESTIC WASTES ONLY. BACKWASH OR FLUSHING FLOWS FOR REVERSE OSMOSIS UNITES OR WATER SOFTENERS AND/OR
FILTERS SHOULD NOT BE INTRODUCED INTO THIS SYSTEM.
6. CLEAN OUTS ARE REQUIRED AT THE HOUSES/RV(s) AND AT ALL BENDS AND AT LEAST EVERY 100 -FEET BETWEEN THE HOUSES AND THE SEPTIC TANK.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING ALL WATER TIGHT COMPONENTS THROUGHOUT THE SYSTEM TO PREVENT INFILTRATION.
8. INSTALL RISERS AS NECESSARY TO BRING t\LL ACCESS PORTS TO FINAL GRADE. PORTS SHALL BE MARKED IF CAPS ARE TO BE BURIED.
9. INSTALL 3 -INCHES OF BLUEBOARD INSULAE ION, 3 -FEET WIDE, OVER SEWER AND EFFLUENT PIPE WHEREVER DEPTH IS LESS THAN 3 -FEET. UNDER NO
CIRCUMSTANCES SHALL COVER BE LESS 1HAN 2 -FEET.
10. LOCATIONS OF ALL COMPONENTS MAY BEVARIED AS NECESSARY AS LONG AS ALL MINIMUM DISTANCES AND SLOPES MEET THOSE REQUIRED.
EXISTING SEPTIC TANKS
(2000± GALLONS
Existing
Septic Field
TO SUPPORT:
UNITS #6, 9 & 11
RV(s) #5, 10,12,15, & 16)
CDPHE APPROVED 1,000 -GALLON
Storage Units TWO-COMPARTMENT PRECAST
CONCRETE SEPTIC TANK W/ HIGH
HEAD DOSING PUMP
Item #
2000T-1 CP
2000 Gallon Top Seam
One Compartment
Item #
I 000T2CP-HH
Storage Units
Union Pacific Railroad
GENERAL ABSORPTION AREA NOTES
1. INSTALL CHAMBER UNITS IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS.
2. ABSORPTION BEDS SHALL NOT EXCEED 12' WIDE BY
100 -FEET IN LENGTH, SHALL PARALLEL THE
TOPOGRAPHY AND SHALL BE INSTALLED IN A
RECTANGULAR PATTERN WHENEVER POSSIBLE.
N:\PROJECTS\2017\17026-3M-Green Diamond\dwg\17026-C-Topo.dwg 9/26/2017 11:29 AM
THE BOTTOM OF THE ABSORPTION BED SHALL BE
LEVEL AND THE BOTTOM AND SIDEWALLS MUST BE
RAKED TO REMOVE ANY SOIL SMEARS INCURRED
DURING THE EXCAVATION. FAILURE TO DO SO MAY
REQUIRE THE CONTRACTOR TO REPLACE THE
ABSORPTION FIELD AT HIS/HER OWN EXPENSE.
4. DRAINAGE SWALES ARE TO BE PROVIDED ABOVE
AND AROUND THE FIELD, AS NECESSARY, TO
PREVENT SURFACE RUNOFF FROM ENTERING
ABSORPTION AREA.
5. NO EXCAVATION OF THE ABSORPTION FIELD IS TO
BE DONE DURING WET WEATHER AND USE OF
RUBBER TIRE VEHICLES OVER THE ABSORPTION
AREA IS STRICTLY PROHIBITED.
6. UNSUITABLE MATERIAL EXISTING WITHIN THE FIELD
SHALL BE EXCAVATED AND BACKFILL SHALL
CONSIST OF IMPORTED LOAMY SAND OR SANDY
GRAVEL. THE ENGINEER SHALL BE CONTACTED IF
BEDROCK OR GROUNDWATER IS ENCOUNTERED IN
THE EXCAVATION.
DESIGN NOTES
• Design per performance test per ASTM C1227
• Top surface area 87.75 ft2
• f'c @ 28 days; concrete = 6,000 PSI Min.
Installation:
• Tank to be set on 5" min. sand bed or pea
gravel
• Tank to be backfilled uniformly on all sides in
lifts less than 24" and mechanically compacted
• Excavated material may be used for backfill,
provided large stones are removed
• Excavation should be dewatered and tank filled
with water prior to being put in service for
installation with water tahle less than 2' below
grade
• Meets C1644-06 for resilient connectors
• Inlet and Outlet identified above pipe
• Delivered complete with internal piping
• Secondary safety screen available with PVC
riser
20" Clear Access
Top View
7. fOPSOIL COVER MAY BE VARIED (1 -FOOT MINIMUM,
?-FOOT MAXIMUM) TO ALLOW FOR LANDSCAPING.
SEPTIC TANK & PUMP SYSTEM NOTES:
ATTACH REMOVABLE CAP OR
THREADED CLEANOUT ASSEMBLY.
INSTALL MARKER IF CAP IS TO
BE BURIED.
4"0 PVC SOLID
PIPE CUT TO FIT
4"0 COUPLING (UNION).
USE A HOLE SAW TO CUT
OUT CIRCLE OFF THE
CENTER OF THE UNIT
4"0 PERFORATED PVC PIPE.
EXTEND PIPE TO REST ON
BOTTOM OF THE BED
GRAVELLESS CHAMBER SYSTEM:
ADVANCED DRAINAGE SYSTEMS
ARC36 (STANDARD),
INFILTRATOR QUICK 4, OR
ENGINEER APPROVED EQUAL.
Flexible
Boot
Butyl Rubber
Sealant
SYSTEM TO BE INSTALLED IN CONFORMANCE WITH
MANUFACTURER'S RECOMMENDATIONS.
2. THE DISCHARGE PUMP SYSTEM SHALL BE AN ORENCO
BIOTUBE PROPAK WITH 30 GPM, 1/2 HP, 115 V HIGH HEAD
VERTICAL TURBINE PUMP AND DEMAND DOSE CONTROLS.
FLOATS SHALL BE SET FOR A DOSING VOLUME OF 400
GALLONS (3 DOSES PER DAY). CONTACT SCG ENTERPRISES
AT 303.697.9404 OR VALLEY PRECAST, INC. AT 719.395.6764
FOR SYSTEM SPECIFICATIONS AND INSTALLATION
PROCEDURES.
1-1/4'0 SCH. 40 PVC
PRESSURE DOSING PIPE WITH
3/16"0 HOLES DRILLED EVERY
48"O.C. (FACING UP)
3. THE SYSTEM SUPPLIER SHALL PROVIDE THE OWNER WITH AN
OPERATIONS AND MAINTENANCE MANUAL WHICH INCLUDES
A MAINTENANCE SCHEDULE,
*See installation guide on our website
ALLOWABLE BURY
(Based on Water Table)
WATER TABLE
ALLOWABLE EARTH
FILL
0' -0"
3'-0"
1'-0"
3'-0"
2'-0"
4'-0"
3'-0,
4'-0,
DRY
4'-0"
ALLOWABLE BURY
(Based on Water Table)
WATER TABLE
ALLOWABLE EARTH
FILL
0' -0
2'-0"
1'-0
3'-0"
2'-0'
3'-0"
3-0'
4'-0"
DRY
4'-0"
Top
View
20" Clear Access
DESIGN NOTES
• Design per )erformance test per ASTM C1227
• Top surface area 46.25 ft2
• f'c @ 28 dhys; concrete = 6,000 PSI Min.
Installation:
• Tank to be ;et on 5" min. sand bed or pea
gravel
• Tank to be backfilled uniformly on all sides in
lifts less thin 24" and mechanically
compacted
• Excavated naterial may be used for backfill,
provided large stones are removed
• Excavation should be dewatered and tank filled
with water prior to being put in service for
installation with water table less than 2' below
grade
• Meets C1644-06 for resilient connectors
• Inlet and Outlet identified above pipe
53" • Delivered complete with internal piping
• Secondary safety screen available with PVC
riser
4. THE PUMP SYSTEMS SHALL BE CONNECTED TO AN ALARM
WHICH SHALL BE BOTH AUDIBLE AND VISIBLE, LOCATED NEAR
A RESIDENCE AND ON A CIRCUIT SEPARATE FROM THE PUMP.
5. TANK DIMENSIONS ARE BASED ON A VALLEY PRECAST, INC.
2,000 GALLON ONE -COMPARTMENT TANK IN SERIES WITH A
1,000 GALLON TWO-COMPARTMENT TANK WITH A HIGH HEAD
PUMP.
• 157" "1
Section View
Flexible
Boot
Butyl Rubber
Sealant Wires to Panel ----�
24" Minimum Height
Ball Valve
I
*See installation guide on our website
Service contracts available for maintenance
Digging Specs
invert
Dimensions
Net Capacity
Net Weight
Lid
Tank
Total
15' Long x 8' Wide
56" below inlet invert
Inlet
56"
Outlet
53"
Length
162"
Width
78"
Height
68"
2,142 gallons
5,420 lbs
.
15,140 lbs
20,560 lbs
Section
View
I-� 106"
Pump:
• Lowers TSS and improves effluent quality to field
• Easiest pump system to maintain on the market
• Complete installation (wiring, panel, mounting and start-up procedures)
• Complete warranty
Digging Specs
Invert
Dimensions
Net Capacity
11' Long x 7' Wide
561' below inlet invert
Inlet
56"
Outlet
73"
Length
111"
Width
60"
Height
92"
Inlet Side
687 gallons
Outlet Side
323 gallons
Total
1,010 gallons
Net Weight
Tank
Total
2,620 lbs
BOTTOM TO BE LEVEL AND FLAT OVER ENTIRE AREA TO
WITHIN 0.1'±. (TYP.). IF NECESSARY TO ACHIEVE THIS
SURFACE, IMPORT CONCRETE SAND TO USE AS
[[Y[Lffi ¥Tl N9NTERED
BOULDERS AND BACKFILL WITH LOAMY SAND OR SANDY
GRAVELS. DO NOT USE COMPACTED MATERIALS.
Pressure Dosing Chambo Bed
tale: N.T.S.
PREFABRICATED PIPE SUPPORT
OR CHEMICAL RESISTANT ZIP
TIE HANGING SYSTEM (PIPE @
6" MIN. ABOVE BASE )
Water &
Wastewater
• Systems
• Products
• Service
(719) 395-6764 28005 Co. Rd. 317
P.O. Box 925
Fax: (719) 395-3727
BuenaVista, CO 81211
woitr wmtalleyprecastecom
Email: frontdesk@vaileyprecast.com
9,380 lbs
12,200 lbs
Water & X719) 395-6764 28005 Co. Rd. 317
Wastewater P.O. Box 925
• Systems Fax: (719) 395-3727 Buena Vista, CO 81211
• Products
• Service Website: www.valleyprecasiam
Email: frontdesk@vaIleyprecastm
/00, (ti
Civil Engineering
(41"; Surveying
& Beyond
Inc•
923 Cooker Avenue
Suite 201
Glenwood Springs, CO 81601
tele: 970.945.5252
fax: 970.384.2833
Client Information:
3M Investors, LLC
737 Corral Drive
Grand Junction, CO 81505
970.618.5244
0
30'
NORTH
60'
Scale: 1" = 30'
GARFIELD COUNTY, COLORADO
Green Diamond Rentals & Storage
ci4
Onsite Wastewater Treatment
Repair/Partial Replacement
0
CC
a
PROJECT NO,
17026
FILE NAME:
17026-c-topo.dwg
DDej igner:
Drafter:
w Q
Date:
9/25/17
ao
Sheet
C.1