HomeMy WebLinkAboutLetter from Engineer 06.22.2017S K PEIGHTAL ENGINEERS Ltd STRUCT1IRAT, CONSULTANTS MEMORANDUM To: Brad Zanin From: Stephen Peightal, PE Date: June 22, 2017 Re: Partition Wall Observation Horse Barn County Road 102 Garfield County, Colorado On site 6-22-17 to observe interior partition wall framing in-place. The intent of visit and Memo is to observe framing conditions, and to present any construction concerns with recommendations. No warranty or guarantee is expressed or implied in this report with respect to the structural components or the integrity of the building. This report is limited to the observed and described construction conditions only. Our services do not include determining the presence, prevention,, or the possibility of mold or other biological contaminants to develop. The building is a new pre-engineered steel building. The observed interior partition walls are assembled of 2 x 4 and 2 x 6 wood studs spaced 16" on center. These 8 -feet tall walls are independent of the primary building shell, and considered as non-structural. The lid over these walls are comprised of I -joists 11 7/8" BCI / 6000 series spaced 16" on center, span 14 -feet, and sheathed with 3/4" plywood. The 2 x 4 and 2 x 6 wall bottom plates are observed as treated, bearing on a concrete slab on grade_ Most bottom plates are observed to be anchored to the concrete with bolts spaced 4 -feet on center. Conclusions Framing workmanship appears very good, with clean lines. Top plates are doubled with proper laps. Joists and studs appear to properly align. Door headers are adequately sized and framed properly with king studs and trimmers. Wall studs are braced with sheathing by plywood at some areas, and gypsum board at the rest. The Boise Cascade specifier guide indicates a Live Load capacity of this lid framing at 80 psf. Slab on grade concrete appears in very good condition. Recommendation Where wall bottom plate is not anchored to the slab, provide connection system spaced at 4 -feet on center. This connection can be accomplished with concrete screw anchors, power activated pins, expansion bolts, or deformed driven pins. Summary With attention to the recommendation above, I find no partition framing concerns. 17031 M SKPE • 298 Park Avenue • #301 • Basalt, CO 9 81621 • (970) 927-9510 • skpeesopris.net