MEMORANDUM
To: County of Garfield
Attn: Building Department
Date: Nov. Ol,2Ol7
Re: Darren Gallegos Residence,
394 Silver King Court, Garfield County, CO.
Our office is the structural engineer of record for the noted proposed residence, and as
such, has issued construction documents for the residence dated March A7,2017 .
Mr. Gallegos requested that we review a series of plumbing penetrations in the main floor
framing. All of the penetrations affected ll.718" deep wood manufactured "I" joists.
In (3) locations the plumber drilled vertical holes which cut the top flange of a "I" joist:
l. At the powder room floor (toilet) he cut ll2" into the top chord at a point 22.1/2"
from the south bearing wall.
2. At the master bathroom floor (toilet) he cut he cut 1/4" into the top chord at 6'-10"
from the north bearing wall.
3. At the master bathroom floor (shower) he cut 3/8" into the top chord at l0'*0" from
the north bearing wall.
These cuts are small enough to be structurally acceptable without remediation.
In the master bathroom I understand that the OSB webs of three (3) "I" joists were drilled
with 2.1/2" diameter holes above 2.1/2" x3,l/2" oval holes. These holes are located 18"
from the north bearing wall. Our office provided a repair detail for this condition.
A final "I" joist of concern has a cluster of holes near the joist mid-span: the group is
located 6'-10" from the near bearing wall. A 2.112" to 3" diameter hole is located in the
lower half of the web, a | .112" diameter knock-out hole is approximately l.ll2" clear of
the larger hole (to its left), and two (2')- 3/4" diameter holes are to the right. The (2)-314"
diameter holes are approximately 2.1/2" center-to-center, and the hole neare'st the large
hole is approximately l.l/2" clear of the larger hole. I recommend that the plumbing lines
occupying the (2)-314" diameter holes be relocated and a 2'-4" long x 8" high OSB web
reinforcement, center on and notched around the large hole be installed. This
reinforcement should be glued and screwed as specifìed in the noted repaft detail. The
wiring in the knock-out hole should be putled and re-installed in a l" diameter hole at the
same location. The (2) plumbing lines should be relocated so that they are clear of the
reinforcement and placed at least 3" clear of one another.
Kurtz &" Associates, Inc.
Brian J. Kurtz, P.E.
ê^
'*+ Vf..RT
.,G.. lo o. c...
®
~rwi;nrli cfi ~~~@ceo~v!J~ Job Codo &.Jiff,,~ 14/.ll'Kt, ;1J I( Om If oli7
CONSULTING f:t-J<;JrJEERS Subject '3'14 S ;/vcr ~tJ ct. Checked Sheet _j_ 01 ___g
c7 a~ ·~~ow>
MAI/\} fLoo I< Jo,s,.'TS (MJ.$1£~ BAIH RooM Flo of2.)
"FR~\J lt>~ 7;(ro 1
' ()~ s PATCH
?"NG' S-117C:. o F ~ t w/
(-.1,) Ro1'J~ * 6 ~t:RE"W7
G 3'' CJ.c,..
FIT ~$ ~ 1i~HI
lo &olfow"'t F LA NG,(;
l I• L '2 .~ q>
f-lvL~ 1o
RErtA 1tJ
~, I $1 \ '• / • 1 1 ~ TFLoof{
"
• • • -... . . . Yz"
ClfMZ..
.·
r ' I I .. . . \ .. .,...,, .. . . .
I -., .
1·6 'Y-. I •' '•i? MtN•M ~fl
u.•10··
&GI
Gil..UE. 4 scJZEw o.sg ~
PQo\/ ID~ ·FU LL. co"11AGI
CA RPE:N le.R.' s WJ.l((ft ~ illf
~
~~ L <~ PouR"[
/! rn~~·iz.]
'J '> • • I • t -... :> --:J;
k> , -2
e ~Te:t.Jv _;;'/
kor<J :z.
w w...L (l~1rJF
TH~U J ottJT A> 5tlowtJ
I~" [if\f1~lt0€_)
24" C.ONTAC.T
LAP
PLAN VIE~: VERTICAL CONSTRUCTION JOINT
I"= 1'-0"
C/ 4'..r~.e/l G,Jj j 0 > Res.i·J~-4~
'3 '14 <5.-f11er-Ki Aj Ci.
6; ~J -0e2J C-fv Co I J .
04-/2s/17
.·
Kw~1Z ~
A ~soc. 11\lC-
J
q4t;· 6:?05