Loading...
HomeMy WebLinkAboutResponse to Ringer Cabin 'Red Lines'rger Cabin "red lines" response - Google Docs RECEIVED Responses to Ringer Cabin "red lines": JUN I 5 20t8 GARFIELD COUNTY COMMUNITY DEVELOPMENT #7- Access to the crawl space is within the room labeled "utility room". The unobstructed access opening exceeds 18"x24" . There is no equipment installed in the crawl space. #25- All exterior walls meet or exceed R-20 insulation values. All roofs are R-38 and the crawl space wall consists of Fox Block ICF system with R-23 insulation value. #28- All floors and sleeping rooms have a minimum of 1 egress window that meets a minimum 5.7 Sq. Ft. Net clear opening. The West window in the loft meets the minimum size at 38x36. The sliding door meets the egress requirement for the downstairs bedroom. #31132- A smoke detector is installed in the downstairs bedroom, the downstairs living area adjacent to the kitchen, upstairs outside of the bathroom in the ceiling, and on the ceiling on the west end of the loft. All smoke detectors are powered from House electric power with battery back-ups. Detectors are audible in all sleeping areas. 33-Carbon Monoxide alarms are installed within 15 feet of all sleeping rooms #35-39, 40a- All stair handrails are within 34'-38" above nosing on treads and are gripabe to meet grip size criteria. All stainruay headroom meet 6' 8" minimum requirement The stainruay riser height, minimum tread depth and width meet all requirements of R311.7.5 The stairs to the second floor has a compliant guardrail. at least 36" in height and meets the picket opening minimum. The second floor has a 42" solid guardrail. The porch steps have compliant handrails The porch does not extend more than 30" above grade All stairs and egress doors have a compliant floor or landing at the top or bottom of each stairway or egress. f//r}b- There is a compliant landing at the exterior of the downstairs bedroom and the front porch. M1- All usable space underneath the stairs has a minimum of 7"" gypsum board to underside of wall and soffit. (Pantry) Page I o ps://docs.google.com/document/d/1-IGv-TyB_vlrDD_fNTPqzG4HYBXibAJDuW6GSJYsdds/edit 6lr512( Uer Cabin oored lines" response - Google Docs H2- All windows or glass doors within 24" to doors and stairways. Window in downstairs bathroom exceeds 60 inches above drain. #55- clothes dryer is vented per manufacturer instructions and section M 1502 #57- Bathrooms have artificial light and exhaust fans connected directly to the exterior and capable of 50 com intermittent or 20cfm continuous ventilation. #58- Gas powered furnace provides heat at a minimum of 68 Fahrenheit for all habitable rooms #59. Gas vent meets the minimum requirement for clearance from combustible material and installation requirements. #62- Gas furnace has required adequate combustion air per IRC Ch. 17 #63- Appliances meet M 1 305.1 .2 for access for service. #65-Heat producing equipment is maintained per M1306 #71-All gas appliances have required shutoff valves. #72-Address numbers secured to structure. Page2 o ps://docs.google.com/document/d/l-IGv-TyB_v1rDD_fNTPqzG4HYBXibAJDuW6GSJYsdds/edit 6lts12(