HomeMy WebLinkAboutSubsurface Investigation & OWTS Design 01.14.15'' 33 Four Wheel Drive Rd Cqrbondole, C0 8lé23 970-309-5259 iri,i!:i January 14,2015 Project No. C1101 Caleb Edelman edelmancm(Ovahoo.com Subsurface lnvestigation and Onsite Wastewater Treatment System Design Proposed Garage with Plumbing TBD Hwy 82 Garfield County, Colorado Caleb, ALL SERVICE septic, LLC performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for a future garage with plumbing on the western portion of the subject 5.63-acre property (Site) with the following legal description: A Parcel of land situated in Lot 1, Section 29, Township 7 South, Range 88 West of the Sixth Principal Meridian, County of Garfield, State of Colorado. ln addition to the garage, the owner desires to have the ability to construct a 4-bedroom residence in the future without further modifications to the OWTS, The Site is located outside of Carbondale, in an area where OWTSs and wells are necessary. SITE CONDITIONS The northern portion of the Site is currently developed with a single-family residence. A recently installed OWTS serves the single-family residence. A driveway also exists on the northern portion of the Site for access to the single-family residence. A garage with plumbing is proposed on the western portion of the Site. A private well also exists on the Site. The well is located greater than 1O0-feet from the proposed OWTS that will serve the proposed garage with plumbing. The proposed soil treatment area (STA) location has approximately a twenty percent slope across the proposed STA. Native vegetation such as sage and scrub oak exists in the area of the proposed STA. SUBSURFACE The subsurface was investigated on August 12,2014 by digging two 8-foot soil profile test pit excavations (Test Pits) and conducting a visual and tactile evaluation of the soils at approximately 3-feet below native grade. The materials encountered in the Test Pit #1 consisted of medium to dark brown, moist, topsoil to 6-inches, underlain by brownish red sandy loam with single grain structure shape, weak structure grade, and loose consistence with flat, platy cobbles 2 to 4-inches in diameter to a maximum depth explored of 7.S-feet. No bedrock or groundwater was encountered. The materials encountered in the Test Pit #2 consisted of medium to dark brown, moist, topsoil to 6-inches, underlain by brownish red sandy loam with single grain structure shape, weak structure grade, and loose consistence with flat, platy cobbles 2 to 4-inches in diameter to a maximum depth explored of 7.O-feet. No bedrock or groundwater was encountered. Page2 Soils are classified as So¡l Type 1. A long term aooeptanoe rate (LTAR) of 0.8 gallons per square foot will be used to design the OWTS, in accordance with Table l0-l presented in the Garfield County On-Site Wastewater Treatment System Regulations, adopted April 14, 2014. Test Pits observed August 12,2014 Test Pit #1 Test Pit#2 DESIGN SPECIFICAT¡ONS The proposed garage will ínclude a shower, toilet, and lavatory for use by one person. Wastewater flow, in accordance with Table 6-2 presented in the Garfield County On-Site Wastewater Treatment System Regulations, adopted April 14, 2014, is calculated at47 .9 gallons per day. Since a future,4-bedroom residence is contemplated, the OWTS design will be based on 4-bedrooms. Desion Calculations: Average Design Flow = 75x2 x 3 Bedrooms + 75 PGD = 525 GPD = Q Q / LTAR = 525 gallons/day / 0.8 gallons/SF = 656 SF 656 GPD x 1.2 (gravity, bed) x 0.7 (chambêrs) = 551 SF Page 3 The system installation will include a new 125O-gallon, two-compartment concrete septic tank an effluent filter on the outlet tee. Effluent will gravity flow to a distribution box which must be made accessible from grade. The STA will consist of three rows of 11 'Quick 4' lnfiltrator@ chambers and one row of 13 'Quick 4' lnfiltrator@ chambers for a total of 46 'Quick 4' lnfiltrator@ chambers and 552 square feet of infiltrative area. lnspection ports must be placed at the beginning and end of each row of chambers. The component manufacturers are typical of applications used by contractors and engineers in this area. Alternatives may be considered or recommended by contacting our office. Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed are of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be plated over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property ownêr shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the absorption area. No heavy equipment, machinery, or materials should be placed on backfilled STAs. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solíds in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES lf design includes a pump, air release valves and weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other controlsystem circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil Extensions should be placed on all septic tank components to allow access to them from existing grade Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. Page 4 INSTALLATION OBSERVATIONS ALL SERVICE septic, LLC mu*t v¡iw th¡ OVVTS ùring aonstruation. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL SERVICE septic, LLC should be notified 48 hours in advance to observe the installation. LIMITS: The design is based on information submitted. lf soil conditions encountered are different from conditions described ín report, ALL SERVICE septic, LLC should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions Sincerely, ALL SERVICE septic, LLC Reviewed By: (a'q {* ("f itótr 6 .N\ Richard H. Carla Ostberg, MPH, REHS Liability Cfause: Under no circumstances whatsoever shattthe tiability of ALL SERVTCE septic, LLC, in connection with any contract, directly or indirectly, exceed the total amount paid by the clientto ALL SERyTCE septic, LLC forthe services and/or goods which are the subject of the contract in connection with which the tiabitity anses. 88668 E&o'li1¿flls IIoec{¡nøey: ceol W1 .0,Rwlet'y€d BF RHPIDrfli BEANG I Shæt I of 4Mushrcom Rock Partnership, LLCTBD Highurayg2Garfeld County, CdcadoProject Numbec Cll0lNiiJi'ealk)*¡t .,ltis(t u2øt Mec úb.É b gdc)-92g'(/ 50' t(x)'Scâlð: 'l'= lB-ü^5þx{z*'n.*,1"I'e*ir:itpt¡ .l¿Ê8¿/Y(t)oêA tu ø¡tØdtuWhþt t, *tu 4 toúþ 7tuh @ øtu¿dû. *û h#W turrúW tuaèddùáh húgãøPMt@d@tu&ttuh1 ¿t ø tud tu Ø LS 2t h tu b b. ttut tu dtu ã, tomúþ 7 W tu@ I t,&d, tu6. M BU Mtucq b pl@ tu tu E6t t ù b d Wb A b@ wfrT c@ .t â728 & tu d bebø. øtM hù ñg &d.hø WZUT et tu d h. ú & tub â o a@ d 7ø.21H b.ñt ù tuwt4àFeñrtu&&gd.wwh&tu@tuMñy&I+ñthatueñ'tubMryhæ|tuM5@U Æt bt eg b ú ú o ñ ffi6 b h tuttua h@e øtud wtØ M d tu úd bñ ilw$To &tñ úâil"A?daø¿øtØtuMtuù&cÞtÐ6æ2ßDRNWNGS MUST BE USËD INCONJUNCTION WITH DESIGNLETTER DATED 1I14l1512.0I e.es .4cres */-"fec&içti ,8:irñFLS lWfi.Lellilfit'c#,3g FourwËl Dri\re RædCarbodals, CO E1623s70.309.525S Sho€t 2 d4w2.0Ha:01/1¡ll15DesþnedBy CBORwlewrdBSEdelman ResidenceTBD H¡ghr/ay8zGarfr€ld County, CdffidoProject Numb€Ê l73lNDESIGNPROPOSED GARAGE WITH TOILET, I.AVATORY, AND SHOWERFOR USE BY ONE PERSOIII = 47.9 GALLONSSIZING FOR ¡I€EDRqil RÉSIDEÍICE(75 GAI/FERSON/DAY x 2 PER9OITT|SBEDROOM x 3 BEDROOMS)(75 GAL/PERSON/DAY x I PERSOìIS/BEDROOM x I BEDROOMS)WASTEWATER FLOW Ê 525 GALLONS=-ot0'mScale: 1' = 2û{'TANKMIN. I25OGALLONSUSE 12sGGALLON, TWGCOMPARIMENT TANK WITH EFRUENTFILTEROF552SOIL TREATMENT AREA (STA):LONG TERM ACCEPIANCE RATE (LTAR) - 0.8 AALTSQ FrSïA = Q/LTAIì = 5t5 cAL / 0.8 cAU SF = 056 SFGRAVIW, BED = 856 SF X 12 = 788 SFCHAMBERS = 788 X 0.7 = 552 SF552 SF / 12 SF / 04 CHAMBER = 40 A4 GHAMERSDISTRIBUTION BOXGRADE'evotion/ÀPROPOSED SITE PLAN\t--rE?melflllff **gì FourW¡e€l Drlvo RoodCarbondals, CO 81823970.309.5259 Sh€d3d¡lw3.0Æ.,¡Gh:01/'l/U15DeelgnedBf CBORa,lewraSEdelman Resid€nceTBDHigfnrryS?Gailèld County, CdaadoPrq€ct Number: 1731IYPICAL PI¡T VIEW. f{.T-S.Pl/CINSPECTION PORTOBERVATIol,IPIPECHAMBEREND CAPAT BEGINNING ANDEND OF EACTI ROì'II52'4'ryCHEÆ)ERS(1% FAT.TTOCHAMBERS)QUTCKÍCnú) END CÂPSDISTRB[Mq{BOX WTH BAFFLE,TOGRAÐEt2'INFILTRATOR(R)L[..IESTO ENTERAÀÞ EXT IN TOPPORÍ OF,CHATIãERCHAMBERÍ¡,3 X4'EÑD111'BED - 46 C}IAIIBERSSMAII-VALVE COI/ERBOXOR lRRlCrA'flONVAII'E BOXAÎGRADE4'DIA SDR€s EFFLUENTINLETLIT€C,AP ORÍHRÊAOEDCLEAÀ¡q'T ASSEMBLYCBOSS SECTION OF IYPICAL CHA}IBER BEDcoilPAgr4'SDR35 PVCOBSERì/ATON /VENTINFILTRATOR(R)ourcK4(nt)cHArßER,3Xl'BÂSE IOSI,FPORTBOXPl/CPIPECUTTOFfTPIPEWTH(MUST BE MINUS }INCH MATERIAL)I'SÊ HOLESAWTOCUT TTRUTOPOFEND4.5'MINNOTES:BED MAY BE AIIGLED TO FIT TC'POGRAPHY AND TO MINIMIZE REMO/AL OF ÐOSTII{G VEGETATION.EXTENT OFEXCAVATf)NSURFACELlMlrATloNs - fiEsE PLÆ.¡s MUsr BE usED tN coNJu¡ìETIoN wrH LETTER AND solts o¡TA Fon*tPROVIDED. THE DESIGN IS BASED UFON INFORMATION SUBMITTED. IF SOIL CONDMOi¡S ENCOUNTËREDARE DIFFERENT FROM OONDITIONS DESCRIBED IN REPORT, ALL SEFIVICE SEPTIC LL.C. SHCXJI.D BENOTIRED. ALL OWS C,oNSTRT'CTION MUST BE ACCORDING TO CO{'NTY RËGUI.ATIONS. THE INSTALLERsHouLD l'l¡AVE DËMONSTRATED KNowLEDcE oF THE REeUtREMEtìÍTt¡ AND REGUIâTtoNs oF THECOTJNTY IN WHICH THEY ARE WOR(ING. THE COI'NTY AI\¡D ALL SERVICE SEPTTC L.L.C.MIJST VIEWINSTALLATION.BED MUST gE LB/EI-. TJSE ONSITE SOILSBR¡NG GRADE UP FOR LEVEL INSTALIáTION,solL MusT BE FREE OF OOBALES (MTNUS$INCH iIATERTAL, AT{O MUST BE COàIPACTEDWTTH UBRATORY MACHINERY. BACKFILLSLOPE MUST ÐfiENDAT3:1II12i i".:'iBED3Í¡ Fourwh€€l ûlì,BRodcröofdalo, co u6at970.3æ.5259ilr$rffiAtü I3SUPON P\¡CBOXAND Colr'ER BROTJGI{T TO GRADEDO NOT GI.UEINSULATEDcoNcnerE LD1TRACERWREFINISHEDGRADEGRADE4'DIASEWERLINETOTAñIKHOUSEINLETBAFFLE ORPIPE AI,¡GLÊDDISTRIBUTION BCXTOVì/ARD BO.rfO[tOF BOX,ACLEANOUT DETAIL\:/¡5ffinr@AD-BOX DETAIL\y584Septic Tank with the Addition of an Effluent Filter - 1250 Gallon, 2-Comp,GromdAülyFrom frmæFilte¡ Corhidoe llold¿(fdd c{t to-dcsifld h¿ight)Top of t€ê to conel'from top d tonktoTof ådoptd (cost or boltcd)Vcnt ùifiæE ff¡eût DilchorgclnLt fæYoddoting Díschcgs OÍTrcÊoVault hlet M¡FìltËr CorbidgêElllumt fìltff/ÀTANK DETAIL\s,/-...-._TEOTJTLETSooooUqridtIw4.0DsteOlñ¡Yls I**o*lAovraræ¿ ey rorPlùerñ BvAl{c IShs€t ¡[ cf ¡[Edelrnan ResidenceTBÐ Higt¡way82Gedold County, OdcadoPrcjCNumben l?31flÍ¡ Fourwh€d ülv€ RoadCaÉondale,CO 81ıts97û309.5258ilttatffitüwJ