HomeMy WebLinkAboutSoils Report 05.07.2018Engineering, Inc. RECEIVED SEP 2 7.0? GARFIELD TY comotDEEO EN CIVIL/GEOTECHNICAL SOIL AND FOUNDATION INVESTIGATION FOR THE SHANNON GUEST HOUSE 6000 COUNTY ROAD 115 (AKA RED CANYON ROAD) GLENWOOD SPRINGS GARFIELD COUNTY, COLORADO PROJECT NO. 18-3257 MAY 7, 2018 PREPARED FOR: ABEL MONTANEZ 1179 HWY 133 #10 CARBONDALE, CO 81623 P.O. Box 724, Eagle, CO 81631 Tel (970) 390-0307 www.lkpengineering.com 1 TABLE OF CONTENTS EXECUTIVE SUMMARY 2 SCOPE OF STUDY 2 SITE DESCRIPTION 2 PROPOSED CONSTRUCTION 3 FIELD INVESTIGATION 3 SUBSURFACE SOIL AND GROUNDWATER CONDITION 3 FOUNDATION RECOMMENDATIONS 4 SLAB CONSTRUCTION 5 RETAINING WALLS 5 UNDERDRAIN SYSTEM 6 SITE GRADING AND DRAINAGE 6 LAWN IRRIGATION 7 LIMITATION 7 FIGURES LOCATION SKETCH DRAWING NO. 1 SUBSURFACE EXPLORATION LOGS .FIGURE NO's 1 - 3 SWELL/CONSOLIDATION TEST RESULTS FIGURE NO'S 4 - 5 GRAIN SIZE DISTRIBUTION FIGURE NO. 6 PERIMETER DRAIN FIGURE NO. 7 LKP Engineering, Inc. Project: 18-3257 2 EXECUTIVE SUMMARY The proposed guest house should be supported with conventional type spread footings, designed for a maximum allowable soil bearing pressure of 3000 psf and a minimum dead load of 1000 psf. They should construct the footings on the undisturbed whitish, cemented, calcareous sandy clay. See Foundation Recommendations. SCOPE OF STUDY This report presents the results of a subsurface Soil and Foundation Investigation for the proposed Shannon Guest House to be constructed at 6000 County Road 115 (Aka Red Canyon Road), Glenwood Springs, Garfield County, Colorado. The legal description of the property as listed at the assessor's data site is Section 28, T6S, R88W, a parcel in Lot 15 and the SE1/4 of Section 28, aka Lot 1, Simmons (Arnove) Exemption. The purpose of the subsurface soil and foundation investigation was to determine the engineering characteristics of the foundation soil and to provide recommendations for the foundation design, grading, and drainage. Geologic hazard studies are outside of our scope of services. SITE DESCRIPTION Lot 1 is a 30.455 -acre parcel of land, on both sides of Red Canyon Road, at 6000 County Road 115 (Aka Red Canyon Road), Glenwood Springs, Garfield County, Colorado. The proposed building site for the proposed Guest House is located across the road from the existing main house and above and about 80 feet north from the existing chicken coup. The topography LKP Engineering, Inc. Project: 18-3257 3 of the proposed building site is moderate. Drainage is to the south and southwest. Vegetation within the proposed building site consisted of sage brush. PROPOSED CONSTRUCTION At the time of the soils and foundation investigation, building plans were not available for the proposed guest. Based on our conversations, we understand that the proposed guest house will be single story wood frame constriction over a crawl space. The test pits had been already excavated by yourself, prior to our site visit. Loads are anticipated to be light, typical of residential construction. If the finalized plans differ significantly from the above understanding, we should be notified to reevaluate the recommendations of this report. FIELD INVESTIGATION The field investigation, conducted on April 30, 2018 and May 7, 2018, consisted of logging and sampling two test pits and the excavation cut on the back of the chicken coup. Excavation of the test pits was done by you prior to our site visit. The test pits' locations are shown on Drawing No. 1. We show the soil profile of the test pits on the Subsurface Exploration Logs, Figure No's 1 through. Soil samples for laboratory soil analysis and observation were taken at selected intervals. SUBSURFACE SOIL AND GROUNDWATER CONDITION The soil profiles encountered in the two test pits were fairly uniform. The soil exposed in the excavation cut on the back of the chicken coup and about 50 feet south from test pit number three was slightly different. Test Pit No. 1 had about one foot of topsoil over 1.5 feet of blocky clay over two feet of reddish -brown calcareous clay over whitish, cemented sandy clay with some basalt rocks to about 8 feet. At the bottom of the test pit there was a layer of whitish - grayish, silty, gravelly sand. The excavation cut behind the chicken coup was used as test pit LKP Engineering, Inc. Project: 18-3257 4 number two. The soil profile exposed in the cut consisted of about one foot of topsoil over five feet of hard, reddish -brown clay over reddish -brown hard clay with cobble size basalt rocks. Test Pit No. 3 was excavated on May 6 and we observed it on May 7, 2017. The soil profile observed in Test Pit Number 3 was similar to the soil in test pit one and it consisted of about one foot of topsoil over 2.5 feet of blocky clay over 2.5 feet of reddish -brown to brown calcareous clay over whitish, cemented sandy clay with some basalt rocks to the maximum depth excavated of 8 feet. Ground water was not encountered in either test pit. We sampled the soil in the test pit at random intervals. The soil samples were brought to our laboratory for observation and analysis. They were tested for natural dry density, natural moisture content, swell/consolidation, and sieve analysis, as shown on the Swell/Consolidation Test Results, Figure No.'s 4 and 5, and the Grain - Size Distribution, Figure No. 6. FOUNDATION RECOMMENDATIONS The on-site clayey soils showed low to high potential for expansion. The proposed guest house should be supported with conventional type spread footings or pads and grade beams, designed for a maximum allowable soil bearing pressure of 3000 psf and a minimum dead load of 1000 psf. They should construct the footings on the undisturbed sandy, reddish -brown calcareous clay or on the whitish cemented sandy clay. We don't recommend constructing the guest house near the site of the new chicken coup (across the road from the main house) where the hard clay with high potential for expansion was encountered. If that site is selected additional testing with a drill rig will be required in order to provided recommendations for the foundation design. The undersigned engineer must observe the foundation excavation to verb that the soil conditions are as anticipated from the two test pits. For a deep foundation system alternatives, like straight shaft piers or micro piles, an additional soils and foundation with a drill rig will be necessary. Continuous foundation walls should be well reinforced, top and bottom, to span an unsupported length of at least 10 feet. A minimum backfill cover as required by the local building department should be provided for frost protection of the footing subsoils. LKP Engineering, Inc. Project: 18-3257 5 The foundation excavation should be free from excavation spoils, frost, organics and standing water. Any overexcavation within the proposed foundation should be backfilled, in 8 inches loose, level lifts and compacted to 98% of the maximum dry density and within 2 percent of the optimum moisture content as determined in a laboratory from a Standard Proctor test (ASTM D-698). Structural fill, placed under footings, should be tested by a qualified professional. For any additional foundation alternatives, please contact our office. SLAB CONSTRUCTION — CRAWL SPACE The proposed structure will be a structural floor over crawl space. The crawl space must be vented according to the local building code requirements. RETAINING WALLS Foundation walls retaining earth and retaining structures that are laterally supported should be designed to resist an equivalent fluid density of 60 pcf for an "at -rest" condition. Laterally unrestrained structures retaining the on-site earth should be designed to resist an equivalent fluid density of 40 pcf for the "active" case. Passive earth pressure of 360 psf can be used for the lateral pressure against the sides of the footings. Resistance to sliding at the bottom of the footings can be calculated based on a coefficient of friction of 0.45. Undisturbed soil or a structural, non -swelling fill compacted to 100 percent of the maximum dry density and within 2 percent of the optimum moisture content shall be used to resist lateral loads at the sides of the footings. The above design recommendations assume drained backfill conditions and a horizontal backfill surface. Surcharge loading due to adjacent structures, weight of temporary stored construction materials and equipment, inclined backfill and hydrostatic pressure due to undrained backfill should be incorporated in the design. Every attempt should be made to prevent the buildup of hydrostatic pressure behind the retaining wall. LKP Engineering, Inc. Project: 18-3257 6 UNDERDRAIN SYSTEM To reduce the risk of surface water infiltrating the foundation subsoil, installation of a foundation perimeter drain is recommended (see Figure No. 7). The foundation perimeter drain should consist of a 4 -inch diameter perforated pipe sloped to a suitable gravity outlet, or to a sump pump location. The drain should slope at 1/4 inch per foot if flexible or at 1/8 of an inch if rigid pipe is used. The bottom of the trench adjacent to the footing should be lined with a polyethylene moisture barrier glued to the foundation wall. The drain pipe should be placed over the moisture barrier and covered with a minimum of 6 inches of -3/4 inch free -draining granular material. Geotextile (Mirafi 140N or equivalent) should be used to cover the free -draining gravel to prevent siltation and clogging of the drain. The backfill above the drain should be granular material to within 2 feet of the ground surface to prevent a buildup of hydrostatic pressure. The top one foot of the backfill material should consist of a relatively impervious fill. The backfill should be sloping away from the building. SITE GRADING AND DRAINAGE The following recommendations are general in nature. The site surrounding the building structure should slope away from the building in all directions. A minimum of 12 inches in the first 10 feet is recommended in unpaved areas, and three inches in the first 10 feet in paved areas. The top of the granular foundation backfill should be covered with a minimum of one foot of relatively impervious fill to reduce the potential of surface water infiltrating the foundation subsoils. Exterior backfill should be compacted at or near the optimum moisture content to at least 95% of the maximum standard Proctor density under pavement, sidewalk and patio areas and to at least 90% of the maximum standard Proctor density under landscaped areas. Mechanical methods of compaction should be used. Do not puddle the foundation excavation. Surface water naturally draining toward the proposed building site should be diverted around and away from it by means of drainage swales or other approved methods. The roof drains and downspouts should extend and discharge beyond the limits of the backfill. LKP Engineering, Inc. Project: 18-3257 7 LAWN IRRIGATION It is not recommended to introduce excess water to the foundation soils by installing sprinkler systems adjacent to the building. The installation of the sprinkler heads should insure that the spray from the heads will not fall within 10 feet of foundation walls, porches or patio slabs. Lawn irrigation must be controlled. LIMITATION This report has been prepared according to locally accepted professional Geotechnical engineering standards for similar methods of testing and soil conditions at this time. The backhoe was selected by Mr. Montanez, the general contractor, as the preferred method for the soil and foundation investigation over a soil and foundation investigation with a drill rig. The findings and recommendations of this report are based on field exploration, laboratory testing of samples obtained at the specific locations shown on the Location Sketch Figure No. 1 and on assumptions stated in the report. Soil conditions at other locations and depths may vary, which may not become evident until the foundation excavation is completed. If soil or water conditions seem different from those described in this report we should be contacted immediately to reevaluate the recommendations of this report. We are not responsible for technical interpretation by others of the data presented in this report. There is no other warranty either expressed or implied. This report has been prepared for the exclusive use of Abel Montanez, for the specific application of the Shannon Guest House to be constructed in the area tested at 6000 County Road 115 (Aka Red Canyon Road), Glenwood Springs, Garfield County, Colorado. Sincerely, LKP ENGINEERING, INC. Luiza Petrovska, PE J:\ WP X4-LKP \_2018 \18-3257SWELDOCX T 'fr IZ)• ■ V • • 2952b C_ q Yee LKP Engineering, Inc. Project: 18-3257 NOTE: THE LOCATION OF THE TEST PITS IS APPROXIMATE IT IS NOT BASED ON A SURVEY CIVIL/GEOTECHNICAL (LKP Engineering, Inc. } P.O. Box 724, Eagle, CO 81631 Tel (970) 390-0307 www.lkpengineering.com LOCATION SKETCH 6000 COUNTY ROAD 115 aka RED CANYON ROAD GLENWOOD SPRINGS GARFIELD COUNTY, COLORADO PROJECT NO 18-3257 SCALE: -1"=50' DRAWING NO.: 1 DATE OBSERVED: April 30. 2018 Test Pit # 1 ELEVATION: S S Y A DEPTH M M DESCR/P770N OF MATERIAL LABORATORY REMARKS FEET B P AND SAMPLE LOCATION TEST RESULTS O L L E Topsoil Brown, blocky Clay Reddish-brown, calcareous �• . Clay DD= 97.6 pcf ❑ MC= 12.9% 5 i/Whitish, cemented sandy Clay .O :; with some basalt rocks '� , (gravel to cobble size) — ?� Whitish-grayish, silty, gravelly DD= 83.0 pcf MC=6.6% ._ i, • Sand at the bottom Mc= 10.9 % -200=6% Bottom of Test Pit @ 8 feet No Ground Water Encountered 10 15 20 - LEGEND: ❑ - 2-inch O.D. California Liner Sample • - Bulk Sample DD - Natural Dry Density (pcf) MC - Natural Moisture Content (%) -200 - Percent Passing No. 200 Sieve LL - Liquid Limit PI - Plasticity Index GW - Ground water PRO„ECT Na.: 18-3257 LKP ENGINEERING, INC. SUBSURFACE EXPLORATION LOG FIGURE NO.: 1 DATE OBSERVED: April 30, 2018 Test Pit # 2 - open excavation cut ELEVATION: behind the chicken coup DEPTH FEET s Y M B O L s A M P L E DESCRIPTION OF MATERIAL AND SAMPLE LOCA 770N LABORATORY TEST RESULTS REMARKS itri Topsoil, silty with fine roots ❑ Reddish brown, hard Clay DD= 107.0 pcf MC= 14 9 5 Reddish-brown, clay with basalt rocks (cobble size) Bottom of Cut ® 8 feet No Ground Water Encountered 10 15 20 LEGEND: ❑ - 2—inch O.D. California Liner Sample ■ — Bulk Sample DD — Natural Dry Density (pcf) MC — Natural Moisture Content (9) —200 — Percent Passing No. 200 Sieve LL — Liquid Limit PI — Plasticity Index GW — Ground water LKP ENGINEERING, INC. SUBSURFACE EXPLORATION LOG PRO, ECT NO.: 18-3257 FlCURE NO.: 2 DATE OBSERVED: May 7, 2018 Test Pit # 3 ELEVATION: DEPTH FEET S Y M B O L S A M P L E DESCRIPTION OF MATERIAL AND SAMPLE LOCATION LABORATORY TEST RESULTS REMARKS Topsoil , Brown, blocky Clay V 5 ,�, Reddish—brown, to brown, calcareous Clay 1f'. Whitish, cemented sandy Clay with some basalt rocks (gravel to cobble size) Bottom of Test Pit 0 8 feet No Ground Water Encountered 10 15 20 LEGEND: ❑ - 2—inch 0.D. California Liner Sample ■ — Bulk Sample DD — Natural Dry Density (pcf) MC — Natural Moisture Content (9) —200 — Percent Passing No. 200 Sieve LL — Liquid Limit PI — Plasticity Index GW — Ground water LKP ENGINEERING, INC. SUBSURFACE EXPLORATION LOG PRO..ECT NO.: 18-3257 FIGURE NO.: 3 3 2 1 0 — 1 0 y —2 —3 0) W — 4 3 2 1 0 — 1 — 4 LKP Engineering, Inc. Swell — Consolidation Test Results Aftircr Na: 18-3257 RpARr Na: 4 EXPANSION CONSTANT WHEN PRESSURE WETTED OF UNDER 1000 PSF 0.1 1 0 10 100 APPLIED PRESSURE — ksf Sample of Reddish—whitish, calcareous sandy Clay from: Test Pit No. 1 at 4 feet Natural Dry Unit Weight = 9Z 6 pcf Natural Moisture Content = 12.9 percent 0.7.E SWELL AT 2.6 KSF LKP Engineering, Inc. Swell — Consolidation Test Results Aftircr Na: 18-3257 RpARr Na: 4 0.1 1 0 10 100 APPLIED PRESSURE — ksf Sample of Whitish, clayey Sand From: Test Pit 1 at 8 feet Natural Dry Unit Weight = 83.0 pcf Natural Moisture Content = 10.9 percent LKP Engineering, Inc. Swell — Consolidation Test Results Aftircr Na: 18-3257 RpARr Na: 4 0 0) k W of 3 2 1 0 —1 -4 LKP Engineering, Inc. Swell — Consolidation Test Results PROEM" Na: 18-3257 MORE : 5 1 - EXPANSION CONSTANT 1 1 1 11__11 WI-rEN PRESSURE WETTED UNDER OF 1000 PSF 1 1 1 0.1 1.0 10 100 APPLIED PRESSURE — ksf Sample of Reddish—brown, hard Clay From: Bank cut behind chicken coup at 4 feet Natural Dry Unit Weight = 107.0 pcf Natural Moisture Con ten t = 14.0 percent 2.2X SWELL AT 8.5 KSF LKP Engineering, Inc. Swell — Consolidation Test Results PROEM" Na: 18-3257 MORE : 5 •0u/ 86WO9u/6u3 d)17 NOl1nBIdlSIO 3Z/S-NIV2/O o4 FROM: Test Pit No. 1 at 8 feet U.& STANDARD SIEVE OPENING IN INCHES U.S STANDARD SIEVE NUMBERS HYDROMETER Inn 6 4 3 2 1a 1 4.4v+ y. 3 4 6 810 14 16 20 3040 50 70 100 140 200 II 0 0 0 In* 0 Percent Finer by Weight �i ` i 1 1 1 1 Percent Coarser by Weight N NI * � ccoo n 0 ooi • 500 100 50 10 5 1 0 5 01 0 05 0.005 0.0011 UV Gravel Sand Cobbles coarse fine coarse mediumfine Silt or Clay Gravel: 9X Sand: 85Z Fines 6X Moisture Content: 6.6X Description: Silty, gravelly, Sand e b FGD ZING LOPE AWAY FROM BUILDING OVER BACKFILL WITH A MINIMUM OF ONE FOOT OF RELATIVELY IMPERVIOUS SOIL 6 6 - o- 0 GRANULAR FILL ILTER FABRIC (MIRAFI 140N OR EQUIVALENT) Dp.. •dam .. /� o-. iQ 0� ` • .0.,t1:;.\ Q/` '\ INUS 3/4 -INCH DIAMETER, COARSE, CLEAN CRUSH ROCK 30 MIL MINIMUM THICKNESS, PLASTIC LINER, GLUED TO TH FOUNDATION WALL -INCH DIAMETER PERFORATED PIPE SLOPED TO A DAYLIGHT LOCATION AWAY FROM THE FOUNDATION AT 1/4 -INCH PER FOOT FOR FLEXIBLE AND 1/8 -INCH MINIMUM FOR RIGID PIPE CIVIL/GEOTECHNICAL Engineering, Inc. P.O. Box 724, Eagle, CO 81631 Tel (970) 390-0307 www.lkpengineering.com PERIMETER DRAIN 6000 COUNTY ROAD 115 aka RED CANYON ROAD GLENWOOD SPRINGS GARFIELD COUNTY, COLORADO PROJECT NO.: 18-3257 SCALE: N.T.S. FIGURE NO.: 7