HomeMy WebLinkAboutEngineer's Report 12.10.2018CIVCO Engineering, Inc. Civil Engineering Consultants P.O. Box 1758 1256 West 400 South Vernal, Utah 84078 �v(�►� -b e, Citcyoc December 10, 2018 Kate Schwerin 345 Colorado Avenue, Unit 207 Carbondale, CO 86123 Dear Kate: Subject: Carport - TBD, CR 100, Carbondale, Colorado Please find enclosed with this letter, the sizing calculations for the carport at TBD, County Road 100, near Carbondale, Colorado. Also enclosed is a copy of David Rasmussen's email requesting that these components be sized. The calculated component sizes are as follows: • Roof Purlins - W6x8.4 wide -flange sections spaced 48" on -center. • Roof Beams - W 12x14 wide -flange sections • Columns - W4x13 wide -flange sections • Corner Column Footings - 2'-0" x 2'-0" x 0'-10" (WxLxD) with three #4 reinforcing bars each way. • Middle Column Footings - 3'-6" x 3'-6" x 0'-10" (WxLxD) with four #4 reinforcing bars each way. Bottoms of footings should be 3'-0" or more below grade. An 8 -inch diameter (or larger) pier with three #4 vertical reinforcing bars should extend from the top of the footing to 6" or more above grade. Sincerely, Vance V. King, PE Structural Engineer CIVCO Engineering, Inc. VVK/vvk Enclosure Cc: Project File Phone (435)789-5448 * Fax (435)789-4485 Email: vanceking@civcoengineering.com