Loading...
HomeMy WebLinkAboutOWTS Design Report 07.12.2019Design Calculations For Long Residence Onsite Wastewater Treatment System Parachue, Colorado July 12, 2019 CIVCO Engineering Inc Civil Engineering Consultants Vernal, Utah 1256 W. 400 S. Office: 435-789-5448 P.O. Box 1758 Fax: 435-789-4485 Vernal, UT 84078 www.civcoengineering.com CIVCO Engineering, Inc. PO Box 1758, Vernal, UT, 84078 Ph: (435)789-5448 Fx: (435)789-4485 ONSITE WASTEWATER TREATMENT SYSTEM Page 1 LONG RESIDENCE By: WK Date: 07/12/2019 Parachute, Colorado Chk'd: wk Date: 07/12/2019 ONSITE WASTEWATER TREATMENT SYSTEM Referenced Calculations Description Section contains calculations sizing the components of the OWTS to be located near Parachute, Colorado. Design Standards CDPHE On-site Wastewater Treatment System Regulation CCR 01 OWTS.mcdx CIVCO Engineering, Inc. PO Box 1758, Vernal, UT, 84078 Ph: (435)789-5448 Fx: (435)789-4485 Number of Bedrooms Perk Test Results: ONSITE WASTEWATER TREATMENT SYSTEM Page 2 LONG RESIDENCE By: WK Date: 07/12/2019 Parachute, Colorado Chk'd: wk Date: 07/12/2019 Nbed:= 4 Minutes Elapsed Test Hole 1 Test Ho:e 2 Test Hole 3 Water Level Drop (in.) Perk Rate (Min./In.) Inches Measured to Wtr Surf Perk Rate (Min./In.) nches Measured to Wtr Surf Perk Rate (Min./In.) 15.00 2 7.50 2.5 6.00 2 7.50 30.00 1.5 10.00 1.5 10.00 1.5 10.00 45.00 1 15.00 1 15.00 0.75 20.00 60.00 1 15.00 0.75 20.00 0.75 20.00 Hole Perk Rate: 15.00 20.00 20.00 Ave. Perk Rate: 18.33 SEPTIC TANK Required Tank Volume Vtank:= if Nbed<3 1000 . gal) else 11( 1000 • gal+ (Nbed— 3) • 250. gal) [CCR TABLE 9-1] =1250ga/ First Compartment Volume V,st comp:= 01 OWTS.mcdx if Nbed<3 =625 gal 500 • gal) else 11(500.gal+ (Nbed— 3) • 125 • gal) [CCR 43.9.6.4.a] CIVCO Engineering, Inc. PO Box 1758, Vernal, UT, 84078 Ph: (435)789-5448 Fx: (435)789-4485 SOIL TREATMENT AREA Design Flow Q:= ONSITE WASTEWATER TREATMENT SYSTEM Page 3 LONG RESIDENCE By: WK Date: 07/12/2019 Parachute, Colorado Chk'd: wk Date: 07/12/2019 if /V,8,<2 300 gal day else if Nbed= 3 450 gal day else if Nbed> 3 450 gal +(Nbed-3) 75 day Long-term Acceptance Rate (LTAR) gal day = 525 ga/ [CCR Table 6-1] day gal Perk Rate t:= tave— = 18.33 min Type 2 soil.... LTAR:= 0.6 day 1/9 2 [CCR Table 10-1] Unfactored Soil Treatment Area STA:— 0— 875 ft2 LTAR Soil Treatment Area (Factored for Trenched Chambers)... Application Method Size Adjustment Factor.... SAFAM:= I .0 (gravity) [CCR Table 10-2] Distrib. Media Size Adjustment Factor SAFoM:= O.7 (chambers) [CCR Table 10-3] Cumulative Size Adjustment Factor.... SAF:= if 5AFAM. SAFDM> 0.5 = 0.7 5AFAM• SAFoM else 0.5 [CCR 43.10.D.3] Trenched Chambers Soil Treatment Area STArc:= SAF• 57-A=6 12.5 ft2 Chamber Bottom Width 8,:= 34 /n STArc Required Trenched Chamber Length LTC:= = 216. 18 ft B 01 OWTS.mcdx CIVCO Engineering, Inc. PO Box 1758, Vernal, UT, 84078 Ph: (435)789-5448 Fx: (435)789-4485 ONSITE WASTEWATER TREATMENT SYSTEM Page 4 LONG RESIDENCE By: WK Date: 07/12/2019 Parachute, Colorado Chk'd: vvk Date: 07/12/2019 Soil Treatment Area (Factored for Bedded Chambers)... Application Method Size Adjustment Factor..... SAFAM:= 1.2 (gravity) Distrib. Media Size Adjustment Factor 5AF0M:=0.7 (chambers) [CCR Table 10-2] [CCR Table 10-3] Cumulative Size Adjustment Factor.... SAF:= if SAFAM• SAFoM> 0.5 =0.54 II SAFAM• SAFoM else 110.5 [CCR 43.10.D.3] Bedded Chambers Soil Treatment Area STATS:= SAF• STA= 735 ft2 Chamber Bottom Width 5,:= 34 in Required Trenched Chamber Length Lir:— STATS _ 259.41 ft 5, 01 OWTS.mcdx WASTEWATER TREATMENT SYSTEM COMPONENT LIST A. SEWER LINE 4"0 UNPERFORATED PLASTIC ASTM STANDARD D 3034 OR BETTER. GRADE AT 2% OR GREATER (NO MORE THAT 4% WITHIN 5 FEET OF SEPTIC TANK INLET). B. SEPTIC TANK 1250 GALLON CAPACITY w/ 625 GALLON (MIN.) 1st COMPARTMENT. MEET STRUCTURAL CRITERIA OF ASTM C1227-12 FOR PRE -CAST CONCRETE TANKS. MEET STRUCTURAL CRITERIA OF IAPMO/ANSI Z1000-2007 FOR FIBERGLASS, FIBERGLASS -REINFORCED POLYESTER, AND PLASTIC TANKS. SEAL PIPE INLETS & OUTLETS WITH WATER -TIGHT MATERIALS. C. DISTRIBUTION BOX OUTLET INVERTS AT LEAST 1" LOWER THAN INLET INVERT. PROVIDE ACCESS WITH MANHOLE RISER AND LID TO SOIL SURFACE. D. SOIL TREATMENT AREA 216 MINIMUM COMBINED LINEAR FEET OF 34 -INCH WIDE CHAMBER. CHAMBER ROWS MUST BE 100 FEET OR LESS IN LENGTH FROM INLET TO END. E. INSPECTION PORT 4"0 VERTICAL PLASTIC PIPE TO BOTTOM OF TRENCH. PERFORATE BOTTOM 12 INCHES. PROVIDE THREADED CAP AT TOP. - tit if 174 4, WALLACE APPROXIMATE. ..t 5.4 SSP?"94 A $ ;5390 r o▪ rt 1.4 � "y "' r T. 'liti:0141" ***4' *ik+ VICINTIY MAP 1" = 100'-0" PROFILE HOLE PERK TEST LOCATIONS SYSTEM PLAN 1" = 20'-0" T7111111111 I III 111 111 111 111 1 1111 11111111 111_ III III 6'-0" 3'-0" 11 111 111 111 I I I I III 11111111w 1111 I MAX. TYPICAL TRENCH (COMPONENT 'D') 1" = 1'-0" MAX. BACKFILL SUITABLE FOR VEGETATION\ \\\ \ \\� II In 11— E 1• 1 II1 -III- _1111111_ \ \ II III- III=III (IIIIIUJIII:H::LthIIIIIIIIl, RATE: 18.3 MIN. / IN11I1; IIIIIIIIIIIIiiilll ii ii��iiii11I111 1 REVISIONS Rev. # Rev. Date Revision Description U • ammo S. W co W �M 00 00 M LL 00 LlJ 00 M 0 s E O 01 L 01 0 V N H O CLAYTON HOMES rn N DRAWN BY: V H W W co