Loading...
HomeMy WebLinkAboutBuilding Code SectionsRECEIVED JUN Û fi 20Ig GARFIELD COUNTY COMMUNITY DEVELOPMENT708.4 Continuity F¡re pårtii¡ons shall extend from the tûp c'f the founclation or floor/ceiling assembly below to the underside of the floor or roof sheathing, slab or deck above or to the fire-resistance- rated floor/ceiling or roof/ceiling assernbly ah¡ove, and shall be securely attached thereto, tn cornbustible construction where the û¡¡:, ¡sartittols are not required to be contrnuoL¡s to the sheathing, deck or slab, tlre space between the ceiling and the sheathing, deck or slab above shall be fjrebtockecJ or draftstopped irr accordance with Sections'/1f\.2 and /18.3 at the pârtition line. The sLlpporting construct¡on shall be prolected to afford the requirecl fit'e- resistânte rating af the '-vall supportecl, except for r¡¡alls separating tenant spaces in covered and open rn;tli buildÌngs, i.çalls separaling Crweiling ¿"rn¡l-s, w*lls separating s!eeping ¿;nifs and car¡icjo¡-r¡valìs, in buildÌrigs of Type llB, lllB and VB construction. x-Exceptions: w@ 1 . The wall need not he extended into tlre crawl space below where the floor above tlre crawl space has a mininrurn 1-hour firr:-¡'eslstattte ,zttng. 2, Where the roonr-side fire-resistance-rated merïbrane of tlre ¡ oi l¿io¡ is carried through to the underside of the floor or r-oof sheathing, deck or slab of a fire-resistance-rated fioor or roof above, the ceiling af the rurridor shall be perm¡tted to be ¡:rotected by the Llse of ceiling materials as required for a 1-hour fire-resistance-rated floor or roof system. 3. Where the la¡¡¿t|¿.-¡'ceiling is constructed as required for the ..tli'ïíd{-}r v¡alìs, lhe vv¿lls sh¿ll be pernritted tû terrrinale ãt the upper nrembratre of such ceilìrrg .rssenrbly. 4. The íire pat"riticirs separating tenant spaces in a covered or open naii building, complying with Secirflil 4tì.4.2 i, ãre nof required to extend beyond tlre unclerside of a ceiling that is not part of a fire-resistance-rated assembly. A w¡rll is not required in afi'lr. or ceiling spâces above tenânt separation ttt;-+lis. 5. Attir f;reLrlor.i<irrg or draftstopping is not required at the pârtition line in Group R-2 buildìngs that do not exceed four sfories above gratlt: ¡.r/:rrici provitied the r¿1ii spãce is subdivided by draftstopp¡ng into "ìreas not exceeding 3,000 square feet (279 m2¡ or above every two dwelling ¡¡nl¡5 wlrichever is smaller. 6. FireL:loc i';irrg or draftstopping is rrot required at the partition line in f:uildings equipped \¡úith an aírt,JtT)ûui sprinklet :iys{€:¡n installed thror.rghout in accordance with 5r:cttoir 9û3.3.1..i or9ll3.-ì..1 .2,provic.iedthatäuioin;ilie sprinklersareinstallecl incombustible floor/ceiling and roof/ceiling spaces. 7ûo?JfrI ,lv tvt'Ñt Section 714 Penetrations 714.1 Scope The prov¡s¡ons Òf th¡s sect¡on shâll Sovern tlìe mâler¡åls and methods of colrstruction t¡sed to protect I lrt ougll itetìeû ¿ r ¡o ¡ 15 ätld / l)e/ì ¡/, ¿,r/j [rc tÌeb:ìtût )s oÍ l)ot izcnla¡ '1sscL"1bÍ¡15 a^d f ire-resist.ìnce-rated rairl¡ âssemblies. 714.1.1 Ducts and Air Transfer Open¡ngs Perletr.rt¡ons of f¡Iê-resistance.rated \^/¿ils by clucts thal å¡e Dôt Frotected w¡th dárnpe¡s shall comply wirh Sections 7 1 4.2 through 71 4.3 3. Pene$at¡ons of br¡l¡t¡?¡.?/ .rsse/DÒleç not protected with .c 5h¿ft as peÌmitted by Se.Ìion 7 ! 7 fr, ând llot required to be protecterJ with fire r/a/Dpelr by other sectiorls of thit cod€, shal¡ complywith Sect¡ons 714.4 throu8lì 714.5.2. Ducß atld a¡r transfer openings tlìãt ¿re Þrotected with danrpers slrall cotnply with se(l{on 71 ./. 714.2 lnstâllation Detalls Where sleeves ârê used, they shall be securely fastened tÕ the âssembly penetrated. The spâce bet\ryeen the jtem contâined ¡n the gleeve and the sl€eve itsel{ and any sp"rce between the sleeve and the à5sembly penelrated shall be protected ¡n accordance witll this section. lnsulation arlci coveflngs olì ol ìn tlìe Þerretrat¡ng item shål¡ not penetl ate tlìe assembly unless the specific mâter¡al used hâs been tested as ¡:art of rhe assenlllly ¡lì âccorda¡rce with this se(t¡ôn. 71 4.3 Fire-Resistance-Rated Walls Penetrâtions into or thlough fi¡t vt¿lls, ûrc barriers, st¡¡oke t¡arnerwalls and firt pãttiTti,!1s sh¿ll comply w¡th Sect¡o¡ìs 714.1.1 through 71.:.3.3. Perletrâtions ¡Ìr .çnroÅe bán ¡erwâlìs shall also conrply with Se.tion 114.4.4. 714.3.1 Through Penetrations I hroirgh penel¡.rriùds of f¡Ie"l esistance-rated wali: shall conply witl-, 5Èrrìrjr ,'/1.-ì.1.1 or 714.3.1.2. Exc€ption: Where tlìe penetrâtjtìg items are stèÊ|, ferro(rs ol collper Pipes, tubes ol corìduits, the ¿nnulár spâre lletween the penetrâÌing ¡tenl and tiìe fire'resistänce- rated wåll is perm¡ttecl to be Protected by elther of dle fôllolving nleâstlres: 1 . ln ( ûfi.rere or nr¿sonr',, walls where the penetrat¡ng itenr i5 a maximum 6-inch (1 52 mm) nom¡ral diameter and the area of the openilìg through the !'J:lll does nor exceed 1 44 square inches (0.0929 m2), (orcrete. Srotlt or rrûrt¿r is Pernlitted where installed the full thickness of the \t.ril or the th¡ckness requ¡red to måinta¡n thè f¡te'ftlslsÍ¿tt\.' 2.Themater¡âlusedtofilltlìe a¡vtt¡l¿rsp¿tç:shallpreventfhep.lssageofflâmeând hor g¿ses suffic¡erìt to ¡gnite cotton waste when sub.iected to ASIM E1 1 9 Ôr uL 263 time'temper¿ture f¡re cond¡lions under a m¡nimulìl positive pressÙre dlfferentiâl of 0.0 1 inch (2.49 Pa) of water åt the locatio lr of the penetrðtiûn for the t¡me perioc{ equ¡valent to the Iire'rÊsistan.e råtinE ôf the constrr¡ction penetrãted. 7 1 4,3,1,1 Fire-Res¡stance-Rated Assemblies Penetråtions shâll be iDstalle{l âs tested in an ¿pprovefl fir€-resistârlce-råte(i assembly. 71 4.3.1.2 f hrough-Penetration Fir€stop System '!'hroJEh penêaãtrcl¡J shall be protecteddy an dpproved Pe!-lelt¡ljoll llf{Ìlirci) system inst¿lled as tested in âccordânce with ASTM Ê814 or UL 1479'with a m¡ninrum positive pressure diff€rential of 0.01 inch (2.49 Pa) of wåter a¡rd slìall håve an F r ati¡rg of not less tlìan the required li e-¡es,'sl ät1(4 t åltt ,1,ç- of tbe vòll pene$a1ed. 714.3.2 Memþrane Penetrations 714,3.2 Membrane Penetrations tulr:rnilrène oenírtiâtìcns shall co[ìply with Seclron 7 ì 4 3 1. Where italls or pârt¡tions åle fequired to have a iire-t tsisl¿t4 ? ¡ áir/r.q, rece3sed fìxtures shall be ¡nslâlled slrch that the required iirê re:jrsi.r¡cc w¡ll not be reduced Excèptions: 1 . \¡eilìll! ane pe,ìètlatto'rs of maxinìunì 2'houl f¡fe-res¡st¿nce-rated vúàlls and partitions by steel electr¡(ål boxes thät do not exceerl 1 [i sqoare inches (0'0 103 m?) in ôre.ì, prôvided the ¡ggregate ârea ol the ùpÊnin8s througll the lnembråne does not exceed 1 0O squôre inches {0.0645 m2) i¡ any 1 00 squôre feet (9 29 m2) of wrll areå. The ¿,1/?uLi¡ 5ll¡?ae lletween the w¡iil nlembfane ancl the box shall not exceed 1,/a inctl (3.2 mm). Such boxes o¡1 opPos¡te s¡des of the w¿li or p¿rtitíorl shall be separâred by one of the f0llowinS: 1 .1. By a horizônt¿l distance of noi less tl)ôn 24 ¡nches (61 0 mm) wlìere the w¡li or partition ìs constructed w¡th ind¡vìdual noncommuni€at¡ng stt¡d.cavìtics; 1 .2. By a horìzontâl cl¡stânce of not less than lhe dePtl', of the v'dll c¿vity where the vù¿rll caviry is filled with cellulose lôôsefill, rockwoôl or slâg tnrncrê! vvool insulation: 1 .3. By sr,lid ffc]bi.ri:k,ng in accorda nce w¡tll Sect¡orì 7 i 8.2 1; 1 .4. By protectint both outlet boxes w¡tlì /6feri putty pacls; or 1 .5. By othèr ,slê./ mâteriâls ând nlêthôds. 2, ¡lerìrbrane perìetlôtii)ns lly ,s{edelectricâl boxes of alìy ìÌateriå1, prov¡ded sucll boxes have beeÌì tested for Llse in firerres¡sta[ce-rateal assembl¡es ¿nd are installed ¡n åccorclan(e wjtll the insiruct¡ons ¡ncltldeil In tlìe l¡sting. lhe .t¡¡lrul¿¡ 5/rá18 belween rhe wâll membrane ând the ttox shâll not exceed 1/s inch (3.2 Ûm) unless lisred otlìerwise. Such boxes on oPposite s¡des c,f the vr'öll or Þartition shall be sep¿râted by one of thê following: 2.1, tsy the hÕrizontal distance sÞecified in the listjng of the electlical boxesi 2.2. By soi¡d fireblocki¡g ¡n accordance witlr Se(t¡orr .i1 8 2. l; 2.3. By protecting both boxes w¡th /6¡edputty Padsj or 2.4. By ôtlìer /6ted rrâterials arìd methods, \. l.l.n 'hr.nr, pe,lel r êt'ot rs by elecllicål tloxes of arly 5¡2e ol type, th¿t have been \das ¡>art of a w¡ll opennl8 protective materislsystem for use in f¡re-Ìe5¡stånce- râtèd assemblies â.d åre ¡nstallèd ¡n âccordance with the instructions ¡ncluded in the listirì9. 4. Menrbr¿ne fienelrati(lfls by boxes other thàn electricâl boxes, provided such penetrating ¡tems ancl the irtLarlár.space between the wall membrane and fhe box' are protected by an approvecl ntenil)!.ttrc peÙekâtion fÌrestop system ¡nstâlled âs testedinaccordancewithASTMESl4orULl4Tg,vJitlìaminimLlmPosit¡vellressure differentìalof0.01inch(2.49Pâ)qfwater,andshalllìaveanFandl¡¿L¡rr¡:ofnotless than the required i!re'teçtstdn{e r,1:¡itg of the vr'¡ll penetrat€d alld bÊ installed ín accórdance with the¡r Itst¡ng. 5.'lhe a¡¡nul¿r s,"â.Ê createcl by the penetrat¡on of ân êutofiìar'rr sprinkler, prôvided ¡t is covered by a metäl escutcheon plate. 6. ¡""'ìemllr.lne pe¡elf êtiq¡rs of mêx¡mun 2-hor¡r fire resstdn[e]atedw¿lq añd Þarür¡ons by ste€l electr¡cal boxes that excee.l 'l 6 squâre ¡nches (0 0 I 03 m2) h area, or steel electrical boxes of alìy size having an ðggrogåte area tlìrou8h the membrane exceêding 'i O0 squäre inches (0.0645 m2) ¡n âny 1 00 square feet (9 29 m2) ot w¿ll area, provided such Þenetråt¡ng items âre protected by listecl putty pads or other l¡sted rÌâteri¿ls and methods, ¿nd installed in accordance with the listilìg 71¿1.3.3 Dissimilar Materials Noncombustible Penetrat¡lì8 items shåll not conrìect to {ombustible items beyon{l the point of f¡restopping unless ¡t can be denìonst¡?ted that tllê f¡re'res¡stånte rntegrity of tlìe w.ll is nìarntâirled 714.4 Hor¡zontal Assembl¡es