HomeMy WebLinkAboutFire District Inspection Report 10.03.2019ROARING FORK FIRE RESCUE AUTHORITY
1089 J W DRIVE
CARBONDALE, CO 81623
INSPECTION REPORT
DATE: 10/2/19 JOB NAME: Jones Residence
TIME: 11:00 CONTRACTOR/OWNER: Flame Out
ROUGH -IN: LOCATION: 7004 County Road 312, New Castle
FINAL: X X COMPLIANT NON-COMPLIANT
PARTIAL: COMPLIANT NON-COMPLIANT
REINSPECT DATE :
Sprinkler
• All valves labeled appropriately? YES
• Hydraulic calculation sticker? YES
• Waterflow test through inspector's test? YES
• All heads trimmed out and correct? YES
• Spare head box? YES
• FDC? N/A
• Control valves supervised (tamper switches)? The breaker switch for pump need secured in the
on position (see picture).
• Outside H/S activated on flow?- YES
INSPECTOR : P>roolee stottt DATE : 10/3/19