HomeMy WebLinkAboutHigh Strength Bolt Inspection ReportsWEST SLOPE TESTING & INSPECTION LLC
3177 Glendam Dr
Grand Junction, CO 81504
Phone: 970'434'6988
Cell: 970-260-2844
6-26-18
Page 1 of 1
Garfîeld County Building Inspection Dept.
l08 8th St., Suite 4ol
Glenwood Springs, CO 81601
Please find enclosed special inspection progress reports for Ensign
residence & Orchard Creek Ranch project.
Thank You; Doug Young
'West Slope Testing & Inspection LLC
3177 Glendam Dr.
Grand Junction, CO 81504
Phone: 970-434-6988
Cell: 970-260-2844
Report #10
Page 1 of I
Insp ection Report
I)ate: 5-30-18
Project: Orchard Creek Ranch LLC
Address: 156 County Rd. 137 Garfield County, CO
Buitding Permit No: BLRE -10-17 -497 3
General Contractor: Doug Hayes Construction
Contractor that Performed Work: Sopris Steel
of fabrication or fïeld work at ob site: Field
Report:inspected the joint penetration at the steel
beam to column rhoment connections at approximately grid lines 4,6,F-2, and O
@ t1.Above inspections included verification of welder qualifications, use of
ñop.r welding eiectrodes/materials, and the random observations ofjoint
preparation & root pass welds (Note, the completed weld passes should be
inspected atalater date when welds are completed).
The field welding inspected above appeared to be in substantial conformance
with the plans, andthe qualrty requirements of the A\MS Dl.1 Structural V/etrding
Code.
Further inspections will need to be performed on the remainder of the project.
E. Young
#51
Inspector/Technician: Douglas E Young Inspector
Inspector
, ,,r,.,,o Douglas E yoLing
j ..' íiwl 96fl7t l31'i.,.n'' clÕI Ð(P. 71112Ð?-t
,
'West Slope Testing & Inspection LLC
3L77 Glendam Dr.
Grand Junction, CO 81504
Phone: 970-434-6988
Cell: 970-260-2844
Report #9
Page I of 1
Inspectio n Report
Dates:. 5-14-18 & 5-16-1 8
Projecfi Orchard Creek Ranch LLC
Address: 156 County Rd. 137 Garfield County, CO
Building Permit No: BLRE -10-17 -4973
General Contractor: Doug Hayes Construction
Contractor that Performed Work: Sopris Steel
of sho fabrication or field work at site: Field
Report: Vi compl ete joint penetration at the
beam to column rhoment connection grid MJLZ. Above inspections included
verification of welder qualifications, use of proper welding electrodes/materials,
inspection of j oint preparation, inspection of the root pass welds, and inspection of
some of the intermediate weld pass layers.Also visually inspected cap pass welds
at the tube steel beam to column moment connections grids 12 to 20 that were not
completed during the last inspection visit on 4-4-18, field fillet welding at plate
type steel beam to column moment connection grid 116, fieLd welding at LVL
buckelboot to steel column gttdVlz, and inspected high strength A325 bolting at
the steel beam & column connections grids 6 to 12. Onsite welding & high
strength bolting inspected above was at the steel framing roof level.
1.ne net¿ welding & high strength bolting inspected above appeared to be in
substantial conformance with the plans, and the quality requirements of the AWS
D1.1 Structural \Melding Code & the AISCIRCSC Specification for high strength
bolting.
Further inspections will need to be performed on the remainder of the project.
DouglasE. young
#s\0222
Inspector/Technician: Douglas E Young Inspector
Douglas Ë
r:vvl côt7ii131
clcl ËxP. 7t'U2t2ú
..f\
,,/'1,:i:.1'.9r,. ¡..:¡liùrl
'':. ,t/
: ,iìl
Inspector
West Slope Testing & Inspection LLC
3177 Glendam Dr.
Grand Junction, CO 81504
Phone: 970-434-6988
Cell: 970-26A-2844
Report #8
Page 1 of 1
Insp ection Report
I)ate: 4-4-18
Project: Orchard Creek Ranch LLC
Address: 156 County Rd. 137 Garfield County, CO
Buitding Permit No: BLRE-I 0-1 7 -4973
General Contractor: Doug Hayes Construction
Contractor that Performed Work Sopris Steel
of fabrication or field work at ob site: Field
Report: Visually complete j penetration welding at steel
beam to column moment connections. Above inspections included verification of
welder qualifications, use of proper welding electrodes/materials, joint preparation
(at the beginning of the welding), and a visual inspection of the root pass welds.
Note; a final visually inspection of the completed welds should be performed at a
later date, as the welding was not completed when I had to leave the site. Also
visually inspected fietd fillet welding at tube steel beam connections, bracing
connections, and inspected high strength A325 bolting at steel beam & column
connections. Welding & bolting inspected above was at the steel framing
main/upper floor level to roof level grids 12-20.
The field welding & high strength bolting inspected above appeared to be in
substantial confonnance with the plans, ffid the quality requirements of the AWS
Dl.1 Structural Welding Code & the AISC/RCSC Specification for high strength
bolting except as noted below.
1) \Melded steel plate washers had been placed/welded over holes that had to be
slotted/oversized to allow for bolt alignment at two of the steel beam connections
roof framing. Please veriff acceptance with the structural engineer, as the special
inspector is not suppose to approve connection changes.
Further inspections will need to be performed on the remainder ofthe project.
Douglas ^8.Young
#51
Inspector
Inspector
üouglas Ë Yeung
cwt 9Gü70131
ec1 EXP.7n!2424
' t'' a. ':?
'./
Inspector/Technician: Douglas E Young
West Slope Testing & Inspection LLC
3177 Glendam Dr'
Grand Junction, CO 81504
Phone: 970-434'6988
Cell: 970-260-2844
Report #1
Page 1 of 1
I n ort
tes:'I
Project: Ensign Residence
Address: 683 Overlook Dr. Garfield County, CO
Building Permit No: BLRE-08-1 7-4868
General Contractor: Thunder Construction
Contractor that Performed Work: Sopris Steel
fabrication or field work at ob site:
-18
of
Report:Visually inspected at beams & columns plece
lcl,3c2, 5C2, 5:C3, 5C4, 6Cr,6C2, 6C3, 6C4, 7 Cl, 7 C2, 7 C3, 9B 1, 982, 983,
1081, 10F.2,1083, and 1181.
Thewelding inspected above appeared to be in substantial conformance with the
plans, and the quuiity r.q,.rirements of the AWS D1.1 Structural \Melding Code''
Further inspections shóuld be performed, as work progresses on the project'
DouglasE.Young
Certifrcation #sr02224
fnspector/Technician: Douglas E Young &Inspector
lnspector
Ðouglas F Youngcwt 96070131
QCl EXP. 7!1t2t20