November 22, 2019 Project No. C1229
Simon Bentley
cdbsimon@comcast.net
Onsite Wastewater Treatment System (OWTS) Installation Observations
Lot 2, Roaring Fork Preserve
Garfield County, Colorado
Permit Number SEPT-09-16-4442
Simon,
ALL SERVICE septic, LLC observed the installation of the onsite wastewater treatment system (OWTS)
on March 17, March 30, 2017, and November 19, 2019 for the subject property. Crawford Design Build
installed the system.
The OWTS design is based on 4-bedrooms. An average daily wastewater flow of 525 GPD was used.
The two auxiliary studios will contain plumbing and will be utilized by residents of the property. No
additional design flow has been calculated for the two studios.
The system installation included a 1250-gallon, two-compartment concrete septic tank with an effluent
filter on the outlet tee anchored with deadmen due to high seasonal groundwater to serve the main
house. An additional 1000-gallon, two-compartment concrete septic tank with an effluent filter on the
outlet tee anchored with deadmen due to high seasonal groundwater was installed to serve the studios.
Both septic tanks will gravity flow via 4-inch diameter sewer pipe with a minimum of 1% fall to a 500-
gallon pump chamber with an Orenco® Biotube Pump Vault and an Orenco® PF5005 pump in the pump
chamber. This pump chamber was also anchored with deadmen due to high seasonal groundwater. All
tanks have effluent filters that must be cleaned annually, or as needed. The floats were set to dose
approximately 90 gallons each pump cycle. The control panel for the pump is located within line of sight of
the pump chamber, on the outside north wall of the studio. Hall Construction out of Grand Junction
performed start-up on the pumping system. We recommend Valley Precast out of Buena Vista be
contracted to double check the pumping system. We tested the pumping system on manual during our
last site visit and flushed the laterals. We recommend a handle extension be added to the float tree for
easy removal.
Effluent is pressure dosed through a 1.5-inch diameter pump line to a mounded, 9’ x 59’ unlined sand filter.
The excavation for the sand filter extended 1-foot below grade. The mound consists of a minimum of 3-feet
of sand filter material, placed at native grade.
Pipes used to disperse the effluent was surrounded by washed coarse screened gravel. The manifold was
1.5-inches in diameter. Laterals were 1.5-inches in diameter with 5/32-inch diameter orifice holes facing
down, spaced 3-feet on center. Each 1.5-inch diameter lateral ends in a sweeping ell facing up with a ball
valve for flushing. A soil separation fabric was placed over the gravel layer followed by approximately 1-foot
of topsoil.
We verified during our March 2017 inspections that the mounded, unlined sand filter was greater than 100-
feet to the well.
The OWTS was generally installed according to specifications. This observation is not a guarantee of
workmanship and/or parts and materials. ALL SERVICE septic, LLC should be notified if changes are
made to the OWTS in the future. Any additional OWTS construction must be according to the county
regulations.
LIMITS:
Observations are limited to components that are visible at the time of the inspection. The installer must
have documented and demonstrated knowledge of the requirements and regulations of the county in
which they are working. The quality of the installation is dependent of the expertise of the installer, soil
type, and weather conditions.
Please call with questions.
Sincerely,
ALL SERVICE septic, LLC Reviewed By:
Carla Ostberg, MPH, REHS Richard H. Petz,
Construction of mounded sand filter
Flushing valves
11/22/19
Tank installation (serves studios)
Sewer lines well bedded
Septic tank serving main house
Cover over sand filter flushing valves and inspection ports to grade
Electrical for pump chamber
High groundwater conditions
Pump chamber installation
PERMIT
KEEP AVAILABLE AT PROJECT SITE
Project Address ____________________________________________ Parcel No. ________________________
Subdivision _________________________________ Lot _______ Section-Township-Range ____________
Owner Name ______________________________________________ Owner Phone _____________________
Owner Mailing Address _______________________________________________________________________
Contractor(s) ______________________________________________ Contractor Phone _________________
Work Description:
Valuation _________________________________
Square Feet _______________________________
IMPORTANT: APPLICATION IS HEREBY MADE TO THE BUILDING OFFICIAL FOR A PERMIT SUBJECT TO THE CONDITIONS AND
RESTRICTIONS SET FORTH ON THIS APPLICATION. PLEASE NOTE: Final inspection of the work authorized by this permit is required. A
Certificate of Occupancy must be obtained prior to use and occupancy of new buildings and structures. A Building Permit becomes null and
void if the authorized work is not commenced within 180 days of the date of issuance and if work is suspended or abandoned for a period of
180 days after commencement.
Permit Type ____________________________________
Work Classification _____________________________
Issue Date ___________ Expiration Date ___________
PERMIT #
Community Development Department
108 8th Street, Suite 401
Glenwood Springs, CO 81601
Phone (970) 945-8212
5/6/2017
36-07-88
Septic - New
970-927-5204
Crawford Design Build, LLC
Roaring Fork Preserve
PO Box 1236 Carbondale, CO 81623
970-618-4346
New engineered OWTS for new s/f dwelling
2
SEPT-09-16-4442
239336219002
New
11/7/2016
Jonathan Whitman Revocable Trust
20 Silver Spruce Dr.
832‐R‐13‐002