HomeMy WebLinkAboutHigh Strength Bolt Inspection Report 11.20.19West Slope Testing & Inspection LLC Report #1
3177 Glendam Dr.
Grand Junction, CO 81504 Page 1 of 1
Phone: 970-434-6988
Cell: 970-260-2844
Inspection Report
Date: 11-20-19
Project: Metal Building
Address: 62 County Rd. 113 Glenwood Springs, CO
Building Permit No: BLCO-09-18-5452
Contractor that Performed Work: Tally Ho Construction
Inspection of shop fabrication or field work at job site: Field
Report: Inspected high strength A325 bolting at the main
and portal frame column & rafter connections.
The high strength A325 bolting inspected above appeared to be in substantial
conformance with the plans & the AISC/RCSC Specification for high strength
bolting except as noted below.
1) A325 grade bolts needed installed at some of the portal frame column, end wall,
and center wall column connections where '/2" A307 bolts had been inadvertently
installed.
Inspector/Technician: Douglas E Young
Douglas E. Young
ICC Certification #5102224
tr ctur 1 Welding Special nspector
ctu I Stee(& Bol p ial Inspector
p lied irepr ecial Inspector