HomeMy WebLinkAboutConditions of PermitCONDITIONS OF PERMIT BLRE-03-20-6156 Raquel Mancinas & Angel Vega Shipping Containers Used as Residential Storage 818 County Road 237 — Silt, Colorado Antlers Orchard, Tract 22 1. REFER TO PLAN ATTACHMENTS FOR GARFIELD COUNTY'S BUILDING REQUIREMENTS AND INSPECTIONS POLICIES. 2. WORK SHALL COMPLY WITH ALL REQUIREMENTS OF "RURAL" ZONE DISTRICT AS DEFINED IN GARFIELD COUNTY'S LAND USE & DEVELOPMENT CODE. 3. IF APPLICABLE, ELECTRICAL PERMITTING & INSPECTIONS SHALL BE PERFORMED BY COLORADO STATE ELECTRICAL BOARD. FINAL ELECTRICAL APPROVAL IS REQUIRED PRIOR TO FINAL BUILDING INSPECTION & CERTIFICATE OF OCCUPANCY. 4. INTERMODAL SHIPPING CONTAINERS (2) AS SHOWN ON SITE PLAN ARE APPROVED FOR USE AS A STORAGE SHED FOR RESIDENTIAL ACCESSORY USE. APPROVAL IS SPECIFICALLY NOT GRANTED FOR USE AS HABITABLE SPACE OR FOR COMMERCIAL USE. OTHER CONDITIONS OF APPROVAL INCLUDE THE FOLLOWING: A. INSTALL 12" MINIMUM BASE LEVELING COURSE OF 11 /2" ROAD BASE BELOW SHIPPING CONTAINER. FINISH GRADE SHALL DRAIN AWAY FROM BASE OF CONTAINER IN ALL DIRECTIONS. B. ENGINEERED FOUNDATION SYSTEM OR STRUCTURAL ANCHORAGES REQUIRED TO PROVIDE A CONTINUOUS LOAD PATH FOR ALL APPLICABLE DESIGN AND ENVIRONMENTAL LOADS IN ACCORDANCE WITH I.B.C., CHAPTER 16. IF HELICAL PIER TIE -DOWNS ARE USED (AS SUBMITTED) PROVIDE STRUCTURAL ENGINEER'S LETTER WITH SPECIFIC SIZES, REQUIREMENTS, AND ENGINEER'S WET -SEAL APPROVAL PRIOR TO BUILDING INSPECTION. C. ALTERNATELY, IF CONCRETE PIER FOUNDATION SYSTEM WITH STRUCTURAL STEEL PLATES IS USED, DESIGN MUST COMPLY WITH REQUIREMENTS OF I.B.C., CHAPTER 18, AND STRUCTURAL ENGINEER'S SIGN -OFF IS NOT REQUIRED. D. VERIFY SAFE EGRESS FROM SHIPPING CONTAINER INTERIOR IF A PERSON IS ACCIDENTALLY LOCKED INSIDE.