HomeMy WebLinkAboutOWTS Design Packet 04.18.202033 FOUR WHEEL DRIVE ROAD CARBONDALE, CO 81 623 970.309.5259 CARLA.OSTBERG@GMAI L. COM til?Y'1'I(' ('(>\Ni'I: 1'I • (: April 18, 2020 Michael Hayes mjhayes15@gmail.com Subsurface Investigation and Onsite Wastewater Treatment System Design 3-Bedroom Residence 1188 CR 106 Garfield County, Colorado Michael, Project No. C1519 CBO Inc. performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 9283 square foot property is located outside in Satank, in an area where OWTSs are necessary and the area has both community water and private wells. Legal Description: Section: 28 Township: 7 Range: 88 A PCL OF LAND IN LOTS C, 17, AND 18. BLK 8 Subdivision: COOPERTON TWNSTE. Block: 8 AMENDED 9283 SQ FT Parcel ID: 2393-283-08-015 SITE CONDITIONS A 3-bedroom, single-family residence presently exists on the property. An existing OWTS serves the structure and is experiencing signs of slow draining. B&R Septic was contracted for jetting; however, the system is unable to be repaired. The OWTS consists of a 1000-gallon, two -compartment Copeland Concrete septic tank followed by a 12' x 27' x 3' deep pipe and gravel soil treatment area (STA). The system is documented by Garfield County Individual Sewage Disposal System Permit 1577. The system received final approval on October 7, 1987 (same day as issuance). The system was sized to accommodate 2 bedrooms. A bedroom was added to the residence as recently as 2017 by the previous owner and a permit was obtained from Garfield County Building Department with no required modification to the OWTS. The residence is currently served by a community water system; however, there are two wells on the property. One well will be abandoned and the other well will remain but is not used for drinking water at this time. The existing STA was approximately 37-feet from the well. The proposed STA is approximately 46-feet from this well'. The water line enters the property from the northwest corner. The water line will not come within 25-feet of any OWTS component. An irrigation ditch in a culvert runs underground along the western property boundary. The proposed STA must be at least 10-feet from the ditch. We strongly recommend exploring the condition of the Garfield County OWTS Regulation states as a note under Table 7-1 "For repair or upgrading of existing OWTS where the size of lot precludes adherence to these distances, a repaired OWTS must not be closer to setback features than the existing OWTS, as reviewed and approved by the local public health agency." Page 2 underground culvert to assure there are no breaches in the infrastructure that would allow water from the ditch to impact the proposed STA. The proposed soil treatment area (STA) location is relatively flat. Two large cottonwood trees will be removed to accommodate the STA and proposed septic tank. There should be no traffic or staging of material over the future STA site to avoid compaction of soils prior to construction of the STA. Due to the small size of the property and the existing physical features on the property, the proposed location of the OWTS components are unable to meet minimum regulatory setback distances. Garfield County OWTS Regulation states, "Repairs to failing systems must conform to setbacks identified in Table 7-1 when possible. When this is not possible using all available methods described above, the jurisdiction with authority may permit reductions to setbacks. At no point will a setback reduction be approved by the jurisdiction less than what the existing separation is to existing OWTS. In maximizing this setback distance, all methods available in section 43.10.1.1 must be utilized including but not limited to the use of Higher Level Treatment, wide beds, seepage pits, etc., where allowed. Any setback reduction beyond what the existing failing system presents must be approved by the local board of health as outlined in section 43.4.0, if the local board of health has opted to allow variances." Variances requested include encroachment on minimum required setbacks to the following: • Well to Septic Tank (40') • WeII to STA (46') • STA to dwelling (11') • STA to Property Line (<1') See Table on W4.0 for reference. SUBSURFACE The subsurface was investigated on April 18, 2020 by digging one soil profile test pit excavation (Test Pit). A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.2 Only one test was excavated due to limited area on the property. The materials encountered in the Test Pit #1 consisted of medium brown topsoil and rootzone to 1.0-foot, underlain by light brown sand and gravels to a maximum depth explored of 7.0-feet. No bedrock or groundwater was encountered. Percentage of rock exceeds 65%. STA sizing is based on Soil Type R-0 and an over -excavated, pressure dosed, unlined sand filter with a minimum of 3-feet of Secondary Sand filter material is proposed. A long term acceptance rate (LTAR) of 0.8 gallons per square foot will be used to design the OWTS, 2 Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page 3 Bottom of test pit View of test pit looking north view of test pit looking west DESIGN SPECIFICATIONS The existing OWTS serving the residence will be abandoned. The septic tank must be pumped and the top, sides, and bottom of the tank crushed and remaining void filled with on -site materials. The existing STA will be abandoned in place. Design Calculations: Average Design Flow = 75 GPD x 2 people/bedroom x 3 Bedrooms = 450 GPD LTAR = 0.8 GPD/SF 450 GPD / 0.8 GPD/SF = 562.5 SF The new OWTS design is based on 3-bedrooms. An average daily wastewater flow of 450 GPD will be used. For the purposes of this OWTS design, Benchmark Elevation has been established as the sewer line exiting the residence as 100'. CBO Inc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. Page 4 OWTS Component Minimum Elevation Primary Tank Inlet Invert Min. 99' 6" (21' w/ min. 2% to septic tank = min. 5.25") Infiltrative Surface Min. 100' (30' w/ min. 1% from pump tank for drain back = min. 3.75" rise) The 4-inch diameter SDR-35 sewer line exiting the residence must have a double -sweep clean out and a minimum 2% grade to the septic tank. The system installation will include a 1250-gallon, two -compartment concrete septic tank with an Orenco® Biotube Pump Vault and an Orenco® PF3005 pump in the second compartment of the septic tank. The floats should be set to dose approximately 90 gallons each pump cycle, allowing approximately 8 gallons of drain back after each pump cycle. A pump curve is enclosed. The pump must be capable of a minimum design flow rate of 34.7 GPM and a minimum total dynamic head of 16.8 feet with 4 feet residual head at last orifice. The control panel for the pump must be located within line of sight of the septic tank. We recommend Valley Precast out of Buena Vista be contracted for start-up of the pumping system. Pump Table Dose Range Max = 115 gal. (450 GPD x 25% + 3 gal drain back) Min. 71 gal. (17 gal x 4) + 3 gal drain back Dose Setting 90 gallons/dose 3 gallons drain back (30' / 1.5" diameter pump line) Float Separation 1250 gallon 2-compartmet Valley Precast concrete septic tank 11" on/off float separation Pump Criteria 34.7 gallons per minute (GPM) 16.8 feet total dynamic head (TDH) Effluent will be pressure dosed through a 1.5-inch diameter pump line to an over -excavated, 10' x 56.25' unlined sand filter with a minimum of 3-feet of sand filter material. Sand filter material must be clean, coarse sand, all passing a screen having four meshes to the inch. The sand must have an effective size between 0.15 and 0.60 mm. The uniformity coefficient must be 7.0 or less. Material meeting ASTM 33, for concrete sand, with three percent or less fines passing 200 mesh sieve may be used. A gradation of the sand media must be provided. Laterals will be connected with a 1.5-inch diameter level manifold. Laterals used to disperse the effluent must be surrounded by washed coarse screened gravel or crushed stone (minimum 6-inches below and minimum 2-inches above laterals). All of the gravel or stone must pass a 2 '/2-inch screen and must be retained on a 3/4-inch screen. Laterals must be 1.5-inches in diameter with 5/32-inch diameter orifices facing down, spaced 3-feet on center (OC). We recommend Orenco® Orifice Shields be installed on the laterals at each orifice. Laterals will begin 2-feet from the edges of the filter, with 3-feet between each lateral. Each 1.5-inch diameter lateral must end in a sweeping ell facing up with a ball valve for flushing. A soil separation fabric should be placed over the gravel layer followed by approximately 1-foot of topsoil or other suitable soil able to support vegetative growth. Page 5 COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area. CBO Inc. must approve alternative components prior to installation of the OWTS. Requests must be submitted, in writing, to our office for approval prior to installation. Component technical data sheets are available upon request. COMPONENT MANUFACTURER MODEL NO. COMMENTS Septic Tank Valley Precast Item # 1250T-2CP-HH 2-compartment concrete septic tank with high head pump Pump Orenco® PF300511 % HP 120 Volt Biotube ProPak Pump Package Orenco® BPP30DD Vault, Filter, Control Panel (demand dose) Tank Risers and Lids Orenco® Double -walled PVC Risers and Lids (24" diameter) Orifice Shields Orenco® OS150 1.5-inch diameter (54 total) Flushing Assembly Orenco® 1.5" diameter (2) 45° or 90° long sweep only (3 total) The component manufacturers are typical of applications used by contractors and engineers in this area. Alternatives may be considered or recommended by contacting our office. Construction must be according to Garfield County On -Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. INSTALLATION CONTRACTOR CBO Inc. expects that the installer be experienced and qualified to perform the scope of work outlined in this design. The installer must review this design thoroughly and coordinate with our office in advance of installation. Any additional conditions in this design or county permit must be completed and documented prior to final approval of the OWTS installation. Communication between the installer and this office is expected throughout the installation. INSTALLATION OBSERVATIONS CBO Inc. must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. CBO Inc. should be notified 48 hours in advance to observe the installation. In an effort to improve the accuracy of the record drawing, we request that the installer provide a sketch of the installation, including path of the sewer lines, water line installation (if applicable), septic tank location, STA location, and measurements from building corners or another fixed objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design Packet. Photographs of the installation and final cover are also requested to supplement our installation documentation. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with Page 6 successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non -biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. LIMITS: The design is based on information submitted. If soil conditions encountered are different from conditions described in report, CBO Inc. should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Page 7 Please call with questions. Sincerely, CBO Inc. ems, (eL o��s, Reviewed By: Carla Ostberg, MPH, REHS Romeo A. Baylosis, PE Pump Selection for a Pressurized System - Single Family Residence Project Hayes / 1188 CR 106 Parameters Discharge Assembly Size Transport Length Transport Pipe Class Transport Line Size Distributing Valve Model Max Elevation Lift Manifold Length Manifold Pipe Class Manifold Pipe Size Number of Laterals per Cell Lateral Length Lateral Pipe Class Lateral Pipe Size Orifice Size Orifice Spacing Residual Head Flow Meter 'Add -on' Friction Losses Calculations 1.25 inches 30 feet 40 1.50 inches None 2 feet 6 feet 40 1.50 inches 3 54 feet 40 1.50 inches 5/32 inches 3 feet 4 feet None inches 0 feet Minimum Flow Rate per Orifice Number of Orifices per Zone Total Flow Rate per Zone Number of Laterals per Zone Flow Differential 1st/Last Orifice Transport Velocity Frictional Head Losses 0.61 gpm 57 34.7 gpm 3 2.0 5.5 fps Loss through Discharge Loss in Transport Loss through Valve Loss in Manifold Loss in Laterals Loss through Flowmeter 'Add -on' Friction Losses Pipe Volumes 8.4 feet 2.1 feet 0.0 feet 0.1 feet 0.2 feet 0.0 feet 0.0 feet Vol of Transport Line Vol of Manifold Vol of Laterals per Zone Total Volume Minimum Pump Requirements 3.2 0.6 17.1 20.9 gals gals gals gals Design Flow Rate Total Dynamic Head * 9 * E. 14 a 34.7 gpm 16.8 feet 300 250 100 50 00 i1=a!1■1■1■111■1■1■1■111■1■1■1■111■11 11111111111111111111111111111 111111111 11111111111■11111111111111111 111111111 1111111111111111111111111111111111111111 1111111111111111111111111111111111111111 1 ■ 11111111111111111111111111111111111111 'i11111111111111111111111111111111111111 11111I1111111I11111111i11111111111111111 1111111■1■1■1111111111111111111111111111 !1111■1■1■1■11111■1■1■111■1■1■1■111■11 :1111iii1■1111111■111111111■1■1■1■111111 1111111■111111111111111■11111■1■1■111111 1111111111111111111111111111011111111111 11111111111I1■1111111111111111111I111■11 1■1■111■1■1■11111■1■111■131■1■111■111■11 �11111111111111111111:11111■1111111111 111111111■11111111111111111■111■1I111111 11111111111111!11111111111111■IIY111111 1111111111111111111111111111111111101111 1111111111111111111111111111111111111111 1111111111111111111111111111111111111111 1111111■1■1■1■111111111111111■1■1■111M11 1111111111111111111111111111111111111111 1■1■111■1■1■1■111■111■1■111■1■1■1111M 111111111111111111111111111111111111i11i 11111111111 11111111111111!1111g WISE; MIMI PumpData 5 10 15 20 25 Net Discharge (gpm) PF3005 High Head Effluent Pump 30 GPM, 1/2HP 115/230V 10 60Hz, 200V 30 60Hz PF3007 High Head Effluent Pump 30 GPM, 3/4HP 230V 10 60Hz, 200/460V 30 60Hz PF3010 High Head Effluent Pump 30 GPM, 1 HP 230V 10 60Hz, 200/460V 30 60Hz PF3015 High Head Effluent Pump 30 GPM, 1-1/2HP 230V 10 60Hz, 200/230/460V 30 60Hz Legend 30 35 Systei urve: Punlp,Curve: Pump Optimalaange: Operati0Point: DesiPPoint: 40 peon{ anud IaagM anozl EE 0 co 0 5 C) 64940 :JagwnN pafoad a ‘.G m • CD o co o = 0TI /(/D� VI 0rn a o CD o 0Q o CD 0i0 0 Etj c cu Cr CD CD (QQ Cr 0 `< pin O W 0 17 dO 4 4001-1S O r0 m0 z me ,Jz > -1 mO mz p 0 00 o0 m co z NI a3sn 381Sf1W SJNIMVIO NV1d 311S .HAdVd ill. X .31. NO ONI±NNd HOd dD1VOS .NOLLVAVOX3 01 ?:1OIHd aDWNIHNOO AND IMPROVEMENTS LOCATIONS ARE ACCURATE. PROPERTY LINES AND SETBACK DISTANCES SHOULD BE CD c < M0 <0 _ — r O 0 • m Dm — x Z - > m D D z -oT� 0 V 73 7J O 0 x O > - m mo cn 0 < =m m� Cm cn z0 m� • z ocm � z 0 - 1_1 0 m= zm cn� c (,) me D-1 0 O m zD m 71O cm nm _1 z o c L" - co Z 0 0 0 _ ° z c m f z � m 90 aVOH ,k1N fl00 N 00'38'00'E 7 „o-,oz = „4 :31VOS O 0 z boc? 0) 0 2 mW com mO 00 2'22 X • S 00'07/(20"E 74.01'X X X o to`° n W n 0.) co sa) CT 0 N (0Q-0 S V a) (D fD C0 W 0 co • cn 0 cn CO n 0 • 0 • co o rn n W :JegwnN 1oafoad 9062108814 03Uep!So SeAeH 0 x 0 @ < � c. o. � 0- 1 a0 0 .< '< CO pin N.) WCCI 0 17 dO Z 3aa4S N O 0 2J 0 0 r1 0 0 =D- o Z x m 0 cn m m rn 0 73 70 • o D m 0 r 0 p — iW0 Dom conm 3:Jx m 0 m< D z m 0 0 *z = r 2 Z m 0 0 000 79) D m 0 r 0 2 D 713 0 m N m D r r 0 z 7 0 D 0) 713 W w 38'00"E m m — -- m m 0 r m D z 0 — 1 ZD m CO mD m0 00 z m 0 0 m 0 m 0 D 0) 01 38 01 HIS 4NH )INH± ONIISIX3 „0-,01• = ..I. :31H0S O 01 0 901, avoH )1Nl0O 74.00' z 73 co m� m O 0 ZO O 0 m� 12i3A1f10 NI H01I4 NOI1H912i21 3N112131HM 2103 d01S 82Jf10 Z'bl .2 3NI1.11213dO2Id I0.0• 73ON mmo • zcn y0r zmI— • C 0 ✓ z • N coD- 0 O 7-0 3�D Dm mZ 2 m 0) m 0 0 z 0 0 0 D m z 113M M3N NV H11M >1NH1011d3S 1N3W1 dooa ddd1 m X D () co —1 zz O G) O � zm m O 1- 0 w 61g13 :aagwnN joefoid G) CO ; ca— / -Cl) = r CD _ /ƒ0 E m \CD ?77 - «&(15 \o_ / 0 OD c0 IV CO 17 30 £ laagS oj b 31VOS 01 ION NO11O3S 831113 aNVS § « « J ` 2 > 0 0 _ m 0 \0- mƒ=c 003 Z -0 mP»ƒ I • < o f7o 7351.5 51- m m 0 > Tor 32w /Q z / 0/ _0 0 §-o §\ \\ m 0 m -o > 0 03 E § o j > 0 as �co $ m> oo 0 HZ E 0-0 0 O1 m0 0 $ 3adbo a3 \) j{ Qi _ m < m c %®m- ® // m_> o>/ zo eZ�® q�H mo To0 c0 ° m0 m0 0 m e { 0 0 / m / 3av io a3HSI _ SRA1VA ONIHSf11d o> z f o/c m�mm \ r 0 mTm\ H > rn /\/7 >r2 2222 > X )z >Q 5 £ z °0 0 @ \ $ 2 � . a1O: 0 64940 :JagwnN Taafoad 2 m @ 73 m @ 0. CD 0 CD E// - /»( _ KKK / 0Cr < / Ofq \ 0 b d0 17 laagS b 0 \ 0 DEPTH - FEET | 1| 1| 1| I I I| I| I| I| I| I I _ = w = NOIIVAVOX3 JNlbfla NO GROUNDWATER OR BEDROCK ENCOUNTERED 0 2 / E m 0 z O 1d?:131`d1 a3aN3dSflS OAd 017-HOS `dla S' 4 � 0 00 jK 0� 22 Ill 0 zz z «_ ¥ /ƒ TS 0 �0 \ 0 > x0 0 < m VIa31A113A`d J \ z is 00 mO \ 0 < §0 0 -1 \ § mm 0I r O O 6 'ON lld 1Sal 31IdOeld BIOS R \—> m z z 00 /\ zz 0 0 0 > 2 � \ 0 0 0 2 m m -1 0 > f O q 0 z GARFIELD COUNTY BUILDING AND SANITATION DEPARTMENT PEEL KNOWN — FAIR Otty 109 8th Slreet Suite 303 KO COMM Glenwood Springs, Colorado 81601 Phone (303) 945-8212 INDIVIDUAL SEWAGE DISPOSAL PERMIT IsP 1577 IThis does not constitute a building or use permit. Owner Walter Rots System Location Licensed Installer 1188 Co. Rd. 106, Carbondale net Willow * Conditional Construction approval is hereby granted for a ` gallon �._. Septic Tank or Aerated treatment unit. Absorption area (or dispersal area computed as follows: Perc rate of one inch in S minutes requires a minimum of sq ft of absorption area per bedroom. Therefore the no. of bedrooms x 4.2_./sq. ft. minimum requirement = a total of 32 Zcq. ft. of absorption area. May we suggest: /.2 ' X 2 7 y.,V 3 c,f e e p Date 7 Inspector, FINAL APPROVAL OF SYSTEM: No system shall be deemed to be in compliance with the Sewage Disposal Laws until the assembled system is approved prior to cover• ing any part. 11� Septic Tank access for inspection and cleaning within 12" of ground surface or aerated access ports above ground surface. Proper materials and assembly. Trade name of septic tank or aerated treatment unit. ffi e/ r„ / O U U ,,! f4,7 /es4.)/' Adequate absorption (or dispersal) area. / ter 1/ U rY'� Adequate compliance with permit requirements. QP` Adequate compliance with County and State regulations/requirements. Date Other /0/-7/8 7 Inspector RETAIN WITH RECEIPT RECORDS CONSTRUCTION SITE *CONDITIONS: 1. All Installation must comply with all requi rements of the Colorado State Board of Health Individual Sewage Disposal Systems Chapter 25, Article 10 G.R.S. 1973, Revised 1984. 2. This permit is valid only for connection to structures which have fully complied with County zoning and building requirements. Connection to or use with any dwelling or structures not approved by the Building and Zoning office shall automatically be a violation of a requirement of the permit and cause for both legal action and revocation of the permit. 3. Any person who constructs, alters, or installs an individual sewage disposal system in a manner which Involves a knowing and material variation from the terms or specifications contained in the application of permit commits a Class I, Petty Offense ($500.00 fine — 6 months in jail or both.). Applicant; Green Copy Department: Pink Copy ,Coped, //88 Co R/ /06 Co 1-e_ r o ] cCop r t1 - 2- 3 A_ 1 4. sw OWNER i;li11VIbUAL AlJA L L)I P0-:',! rll'i`i_1l.rdlu+d hil;)!.uv, H by County Official: LOCATION OF PROPOSED FACILITY: County Near what City of Town C), a/t, . Legal Description ADDRESS' S p-a 0066 PHONE 9‘, - ,? :?3V CONTRACTOR_ ADDRESS (°4, PHONE PERMIT REQUEST FOR: ( ) New Installation ( ) Alteration Or) Repair Attach separate sheets or report showing entire area with respect to surrounding areas, topography of area, habitable building, location of potable water wells, soil percolation test holes, soil profiles in test holes. (See page 4.) R Lot Size jr1 WASTES TYPE: ( A() Dwelling ( ) Transient Use ( ) Commercial or Institutional ( ) Non -domestic Wastes ( ) Other - Describe BUILDING OR SERVICE TYPE: Number of bedrooms cf,1 Number of persons ( ) Garbage grinder (k,) Automatic washer ( ) Dishwasher SOURCE AND TYPE OF WATER SUPPLY: ) well e.-( k) spring ( ) stream or creek Give depth of all wells within 180 feet of system: �j- If supplied by community water, give name or supp,1,i, GROUND CONDITIONS: `I/" . Depth to bedrock: Depth to first Ground Water Table: 1 Percent ground slope: DISTANCE TO NEAREST COMMUNITY SEWER SYSTEM: Was an effort made to connect to community system? TYPE OF INDIVIDUAL SEWAGE DISPOSAL SYSTEM PROPOSED: (Y4) Septic Tank ( ) Aeration Plant ( ) Vault ( ) Vault Privy ( ) Composting Toilet ( ) Recycling, potable use ( ) Pit Privy ( ) Incineration Toilet ( ) Recycling, other use ( ) Chemical Toilet ( ) Other - Describe: FINAL DISPOSAL BY: (') Absorption Trench, Bed or Pit ( ) Evapotranspiration ( ) Underground Dispersal ( ) Sand Filter ( ) Above Ground Dispersal ( ) Wastewater Pond ( ) Other - Describe: WILL EFFLUENT BE DISCHARGED DIRECTLY INTO WATERS OF THE STATE? Page 2 SOIL PERCOLATION TEST RESULTS: (To be completed by Registered Professional Engineer.) Minutes per inch in hole No. 1 Minutes per inch in hole No. 3 Minutes per inch in hole No. 2 Minutes per inch in hole No. Name, address and telephone of RPE who made soil absorption tests: Name, address and telephone of RPE responsible for design of the system: Applicant acknowledges that the completeness of the application is conditional upon such further mandatory and additional tests and reports as may be required by the local health department to be made and furnished by the applicant or by the local health department for purposes of the evaluation of the application; and the issuance of the permit i-s subject to such terms and conditions as deemed necessary to insure compliance with rules and regulations adopted under Article 10, Title 25, C.R.S. 1973, as amended. The undersigned hereby certifies that all statements made, information and reports submitted herewith and required to be submitted by the applicant are or will be represented to be true and correct to the best of my knowledge and belief and are designed to be relied on by the local department of health in evaluating the same for purposes of issuing the permit applied for herein. I further under- stand that any falsification or misrepresentation may result in the denial of the application or revocation of any permit granted based upon said application and in legal action for per- jury as provided by law. Date 9- PLEASE DRAW AND ACCURATE MAP TO YOUR PROPERTY Alcus S1 gneed �•4 6 Sign Page 3 PLOT PLAN AND DESIGN FEATURES: Include by measured distance location of wells, springs, potable water supply lines, cisterns, buildings, property lines, subsoil drains, lake, water course, stream, dry gulch and show location of proposed system by direction and distance from dwelling or other fixed reference object, and additional submissions in support of this application such as data, plans, specifications, statements and commitments. --TT) Page 4 Garfield County Community Development Department 108 8th Street, Suite 401 Glenwood Springs, CO 81601 Phone (970) 945-8212 P '4MIT KEEP AVAILABLE AT PROJECT SITE Permit Type Residential - Other Work Classification Addition PERMIT # BLRE-07-17-4825 8/10/2017 2/6/2018 Issue Date Expiration Date Project Address 1188 CR 106 Parcel No. 239328308015 Subdivision Cooperton Townsite Lot C, 17 & Section -Township -Range 28-07-88 Owner Name Karen Wahrmund Owner Phone 512-971-8552 Owner Mailing Address 1188 CR 106, Carbondale, CO 81623 Contractor(s) OWNER Contractor Phone Work Description: addition of master bedroom and bathroom Valuation $17,923.00 Square Feet IMPORTANT: APPLICATION IS HEREBY MADE TO THE BUILDING OFFICIAL FOR A PERMIT SUBJECT TO THE CONDITIONS AND RESTRICTIONS SET FORTH ON THIS APPLICATION. PLEASE NOTE: Final inspection of the work authorized by this permit is required. A Certificate of Occupancy must be obtained prior to use and occupancy of new buildings and structures. A Building Permit becomes null and void if the authorized work is not commenced within 180 days of the date of issuance and if work is suspended or abandoned for a period of 180 days after commencement. SA3AHf1S 4Nd1 Z VT/ V m 3N 13 Al 13 I lfl GV3HH3A0 m o 0 C 6 ml m 0 0 m 0 - D - 1 Ct n 1 m 1 n m z m 1 z m 3N 11 30N3d X 0 v m m m 0 D 1 1- m < m 43NdVIA1 d'd0 V 2i'd83d 41. DATE 04/14/20/5 SCALE l" = 10' JOB NO.: 15 /3 67 GLENW00D AVE CARBONDALE CO. 970-963-3852 SYDNEY LINCICOME (L. S /4 / / / ) cr3' r Ili (f) (f) h. CARBONDALE. COLORADO 1188 COUNTY ROAD 106 IMPROVEMENT SURVEY PLAT (> 111 3W0313N I 1 1.3N RS cn co COUNTY ROAD 106 — t-o m cn- -10')m • -70 cn — m C ooco m1 <ry - r 2 m mmx — a73-1 cncnm- mom im• CZ cn D D• cn-1 Z — OMZO z0z nor o acn7o mc»- C)2or - 1K73 m1- - 1z w o-m. tf)31 -1 D N 2 D P1 0 mZm— v v, Co m730> cn—C — 10cntn 2PC 0-1 70 mcn*< DM MOcn-< - m m* 7c*OD Z DC V) 0<z vm r- m m Z—17o OM -mom z m O 0 0ZZ n W comcn-< m ro—K — 0M "r1 7c -u 0 • ZDZ 0 31 ZM2 rm OD-0 cn a mcnCC) >0m mzo cnom 2zr 0z z2v 11 aLVO I A I 11120 N U) 2.4' GI N 00°38'00"E a 74.00' D D 11.9' .9'51 3SflOH 3NV J AdOlS-I10N I S 12.9' .8'33 v v 24.8' o rn 6.3' Z'bl 10.0' X X X d004 dVd X X X Y, X S 00° 0720"E 74.01' 4) D -H — cn0-ID J -1DC) m=zm C)mol- m - 0(n-- -1m00• - C)• 00 cn zzmm o r C) Z 0 0 0DC)Z • 01ZooD ND• ulm m OJ-HZ — 0 -gym • nZD D cn > - r m TIm - mC)o - 0710 mol- C)000 0 -0-I CDmcn z-u; - — 0 • • nZ CND• 0 N C) r • C) — 0 0 ul z,Nzi• D 0 G, 0C.JZ� NOIZdI2I0S2Q 'IVOa9 to 0 N, v*D m—c) m x mx0 f)—z 1Zv — Z MI c) 1m1 xmo W<0 MO car czo Xl N.m < D O < m O 1 Wmr mWa 00 oo< Mco mmc Z)zc C m(0( 011 MOO moM MOM DMm Z co> MO< Z x mmcm) mmr l4C) m.(D) 0 - - m-o zz mon mon y vmm n<v 1m mzc 1 0 o• z m; 1 D D m<z m < > ozo m<m X - D m - 0C) m 1 1 coo - >zz 1 — W 1 onx Zln- mv Nv x occ o< zzm zm = < mz m m< 1 z 1 C:IProgram Files\General CADD 81GxdIGROBERTS.gxd -- 04/14/2015 -- 03:40 PM -- Scale 1 : 120.0000 1250 Gallon TopSeam - 2CP Item # 1250T-2CP-HH with High Head Pump DESIGN NOTES • Design per performance test per ASTM C1227 • Top surface area 56.25 ft2 • f'c ® 28 days; concrete = 6,000 PSI Min. Installation: • Tank to be set on 5" min. sand bed or pea gravel • Tank to be backfilled uniformly on all sides in lifts less than 24" and mechanically compacted • Excavated material may be used for backfill, provided large stones are removed • Excavation should be dewatered and tank filled with water prior to being put in service for installation with water table less than 2' below grade • Meets C1644-06 for resilient connectors • Inlet and Outlet identified above pipe • Delivered complete with internal piping • Control Panel to be mounted in sight line of tank • 4' Maximum bury depth ALLOWABLE BURY (Based on Water Table) WATER TABLE ALLOWABLE EARTH FILL 0'-0" 2'-0" 1'-0" 3'-0" 2'-0" 3'-0" 3'-0" 4'-0" DRY 4'— 0" 6 Fle Boot ,• 6 5 *Service conbada available 35" TANK ID Wires to Panel Rubber Sealant ' 49" Top View 24" Minimum Riser Height 130" Ink Disconnect Bali Valve /Altemate Discharge Height 73" Pump: • Lowers TSS and improves effluent quality to field • Complete installation (wiring, panel, mounting and start-up procedures) • Complete warranty 54" Section View Digging Specs Invert Dimensions Net Capacity Net Weight Min. 13' Long x 7' Wide Inlet Outlet Length Width Height Inlet Side Outlet Total Lid Tank Total 56" below inlet 56" 54"or73" 135" 60" 92" 843 gal 416 gal 1259 gal 3120 lbs 10880 lbs 14200 lbs lirVALLEY PRECAST, Inc. Buena Vista, Colorado Phone: 719-395-6764 Fax: 719-395-3727 Website: www.valleyprecastcom Email: frontdesk©valleyprecastcom Double Walled PVC Riser & Lid Options Poly Lid (Static load tested to 5000 Ibs) • Skid resistance surface • Available in green • Highest level of UV Protection included • Includes a foam gasket for airtight and watertight applications Includes square drive screws to discourage unauthorized entry Insulation panels achieve R-10 insulation rating • • c' C C) 2) C Double Walled PVC Riser 41 I\ / N /I-n /1-wl I\ 4 2" of Insulation Standard Orenco ® DuraFiber'" Access Lids (FLD) Not recommended for vehicular traffic 24" and 30" Diameters • Solid, resin -infused fiberglass construction • 20,000-Ib breaking strength • Standard green or brown colors • Available with or without urethane lid gasket • Available with carbon filtration • 4 stainless steel flathead socket cap screws & hex key wrench • Insulated lids available - 2" or 4" • Available in 24" and 30" Diameter • Cut to length • Sold in +/- 2" increments • Must be cut between ribs V!c!VALLEY � PRECAST, & Wastewater • Systems • Products PRECAST, Inc. • Service (719) 395�764 28005 Co. Rd. 317 P.O. Boc925 Fax: (719) 395-3727 Buena Yam' CO 81211 Webslte: www.valleyprecastcom Email: frontdesk©valleyprecastcom Orenco® Technical Data Sheet Biotube® ProPak Pump PackageTM 60-Hz Series Pump Packages Float External splice box Optional; internal splice box comes standard.) bracket Support pipe Control panel Riser lid (not included) 0 Riser (not included) Discharge assembly Pump vault Float stem Floats Float collar Vault inlet holes 4-in. (100-mm) turbine effluent pump Biotube® filter cartridge 00 00 00 00 00 O 0 00 0▪ 0 00 00 O 0 00 00 00 00 Pump liquid end Pump motor Biotube© ProPakTM pump package components. General 0renco's Biotube® ProPak"" is a complete, integrated pump package for filtering and pumping effluent from septic tanks. And its patented pump vault technology eliminates the need for separate dosing tanks. This document provides detailed information on the ProPak pump vault and filter, 4-in. (100-mm) 60-Hz turbine effluent pump, and control panel. For more information on other ProPak components, see the following Orenco technical documents: • Float Switch Assemblies (NSU-MF-MF-1) • Discharge Assemblies (NTD-HV-HV-1) • Splice Boxes (NTD-SB-SB-1) • External Splice Box (NTD-SB-SB-1) Applications The Biotube ProPak is designed to filter and pump effluent to either gravity or pressurized discharge points. It is intended for use in a septic tank (one- or two -compartment) and can also be used in a pump tank. The Biotube ProPak is designed to allow the effluent filter to be removed for cleaning without the need to remove the pump vault or pump, simpli- fying servicing. Complete packages are available for on -demand or timed dosing sys- tems with flow rates of 20, 30, and 50-gpm (1.3, 1.9, and 3.2 Usec), as well as with 50 Hz and 60 Hz power supplies. Standard Models BPP2ODD, BPP2ODD-SX, BPP3OTDA, BPP3OTDD-SX, BBPP5OTDA, BPP5OTDD-SX Product Code Diagram BPP Standard options: Blank = 57-in. (1448-mm) vault height, internal splice box, standard discharge assembly 68 = 68-in. (1727-mm) vault height SX = external splice box CW = cold weather discharge assembly DB = drainback discharge assembly 0 = cam lock MFV = non -mercury float Control panel application: DD = demand -dosing TDA = timed -dosing, analog timer TDD = timed dosing, digital timer, elapsed time meter & counters Pump flow rate, nominal: 20 = 20 gpm (1.3 Usec) 30 = 30 gpm (1.9 L/sec) 50 = 50 gpm (3.2 Usec) Biotube® ProPak'" pump vault Orenco Systems° Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-BPP-1 Rev. 1.2, © 08/14 Page 1 of 4 Orenco° Technical Data Shee ProPakTM Pump Vault Materials of Construction Vault body Polyethylene Support pipes PVC Dimensions, in. (mm) A - Overall vault height B - Vault diameter 57 (1448) or 68 (1727) 17.3 (439) C - Inlet hole height 19 (475) D - Inlet hole diameter (eight holes total) E - Vault top to support pipe bracket base F - Vault bottom to filter cartridge base 2 (50) 3 (76) 4 (102) y -1E3 iH is A C B JCS...... B • ProPakTM pump vault (shown with Biotube filter and effluent pump) ggg ggg ggg Biotube° Filter Cartridge Materials of Construction Filter tubes Polyethylene Cartridge end plates Polyurethane Handle assembly PVC Dimensions, in. (mm) A - Cartridge height 18 (457) B - Cartridge width 12 (305) Performance Biotube® mesh opening Total filter flow area 0.125 in. (3 mm)* 4.4 ft2 (0.4 m2) Total filter surface area 14.5 ft2 (1.35 m2) Maximum flow rate *0.062-in. (1.6-mm) filter mesh available 140 gpm (8.8 t-/sec) J ckLD LTrE3 g. so gg OC o o o o o o o o o o o o o o o o. og 0. og o. og o. og Biotube® filter cartridge (shown with float switch assembly) NTD-BPP-1 Rev. 1.2, © 08/14 Page 2 of 4 0renco Systems° Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com 4-in. (100-mm) Turbine Effluent Pumps 0renco's 4-in. (100 mm) Turbine Effluent Pumps are constructed of lightweight, corrosion -resistant stainless steel and engineered plastics; all are field -serviceable and repairable with common tools. All 60-Hz PF Series models are CSA certified to the U.S. and Canadian safety standards for effluent pumps, and meet UL requirements. Power cords for 0renco's 4-in. (100-mm) turbine effluent pumps are Type SOOW 600-V motor cable (suitable for Class 1, Division 1 and 2 applications). Materials of Construction Discharge: Stainless steel or glass -filled polypropylene Discharge bearing: Engineered thermoplastic (PEEN Diffusers: Glass -filled PPO Impellers: Acetal (20-, 30-gmp), Noryl (50-gpm) Intake screens: Polypropylene Suction connection: Stainless steel Drive shaft: 300 series stainless steel Coupling: Sintered 300 series stainless steel Shell: 300 series stainless steel Lubricant: Deionized water and propylene glycol Specifications Nom. flow, Length Weight gpm (Usec) in. (mm) lb (kg) Discharge Impellers in., nominal 1 20 (1.3) 22.5 (572) 26 (11) 1.25 30 (1.9) 21.3 (541) 25 (11) 1.25 50 (3.2) 20.3 (516) 27 (12) 2.00 4 3 2 Performance Nom. flow, gpm (Usec) 20 (1.3) 30 (1.9) 50 (3.2) hp (kW) Design Rated Min liquid flow amps cycles/day level, in. (mm) 2 0.5 (0.37) 12.3 300 18 (457) 0.5 (0.37) 11.8 300 20 (508) 0.5 (0.37) 12.1 300 24 (610) 1 Discharge is female NPT threaded, U.S. nominal size, to accommodate 0renco® discharge hose and valve assemblies. Consult your 0renco Distributor about fittings to connect discharge assemblies to metric -sized piping. 2 Minimum liquid level is for single pumps when installed in an Orenco Biotube® ProPakTM Pump Vault. Pump Curves Pump curves, such as those shown here, can help you determine the best pump for your system. Pump curves show the relationship between flow (gpm or L/sec) and pressure (TDH), providing a graphical representation of a pump's performance range. Pumps perform best at their nominal flow rate, measured in gpm or Usec. 140 120 a p 100 1— a z 80 E 60 40 20 Flow 'n liters per second (L/sec) 0.63 1.26 1.89 2.52 3.15 3.79 4.42 PF 200511 ▪ PF 300511 ▪ PF 5005111 10 20 30 40 50 60 70 Flow in gallons per minute (gpm) 43 37 30 24 18 12 6 Total dynamic head (TDH) in meters 0renco Systems° Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-BPP-1 Rev. 1.2, © 08/14 Page 3 of 4 Control Panel (Demand Dose) Orenco's ProPak'" demand dose control panels are specifically engineered for the ProPak pump package and are ideal for applications such as demand dosing from a septic tank into a conventional gravity drainfield. Materials of Construction Enclosure UV -resistant fiberglass, UL Type 4X Hinges Stainless steel Dimensions, in. (mm) A - Height 11.5 (290) B - Width 9.5 (240) C - Depth 5.4 (135) Specifications Panel ratings 1. Motor -start contactor 120 V, 3/4 hp (0.56 km, A, single phase, 60 Hz 16 FLA, 1 hp (0.75 kW), 60 Hz; 2.5 million cycles at FLA (10 million at 50% of FLA) 2. Circuit 120 V, 10 A, OFF/ON switch, Single pole breakers 3. Toggle switch 4. Audio alarm Single -pole, double -throw HOA switch, 20 A 95 dB at 24 in. (600 mm), warble -tone sound, UL Type 4X 5. Audio alarm 120 V, automatic reset, DIN rail mount silence relay 6. Visual alarm 7/8-in. (22-mm) diameter red lens, "Push -to -silence," 120 V LED, UL Type 4X / O D41-461 mmmm xmO 1 Control panel, demand -dose Control Panel (Timed Dose) Orenco's ProPak timed dose control panels are specifically engineered for the ProPak pump package and are ideal for applications such as timed dosing from a septic tank into a pressurized drainfield or mound. Analog or digital timers are available. Materials of Construction Enclosure UV -resistant fiberglass, UL Type 4X Hinges Stainless steel Dimensions, in. (mm) A - Height 11.5 (290) B - Width 9.5 (240) C - Depth 5.4 (135) Specifications Panel ratings Dual -mode 120 V, 3/4 hp (0.56 kV , 14 A, single phase, 60 Hz Programmable for timed- or demand -dosing (digital timed -dosing panels only) la. Analog timer (not shown) 120 V, repeat cycle from 0.05 seconds to 30 hours. Separate variable controls for OFF and ON time periods 1 b. Digital timer (shown below) 120-V programmable logic unit with built-in LCD screen and programming keys. Provides control functions and timing for panel operation 2. Motor -start contactor 16 FLA, 1 hp (0.75 kW), 60 Hz; 2.5 million cycles at FLA (10 million at 50% of FLA) 3. Circuit breakers 120 V, 10 A, OFF/ON switch. Single pole 120 V 4. Toggle Switch 5. Audio alarm Single -pole, double -throw HOA switch, 20 A 95 dB at 24 in. (600 mm), warble -tone sound, UL Type 4X 6. Visual alarm 7/8-in. (22-mm) diameter red lens, "Push -to -silence", 120 V LED, UL Type 4X Control panel, timed -dose (digital timer model shown) NTD-BPP-1 Rev. 1.2, © 08/14 Page 4 of 4 0renco Systems° Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com Orenco® Technical Data Sheet PF Series 4-inch (100-mm) Submersible Effluent Pumps Applications Our 4-inch (100-mm) Submersible Effluent Pumps are designed to transport screened effluent (with low TSS counts) from septic tanks or separate dosing tanks. All our pumps are constructed of lightweight, corrosion -resistant stainless steel and engineered plastics; all are field - serviceable and repairable with common tools; and all 60-Hz PF Series models are CSA certified to the U.S. and Canadian safety standards for effluent pumps, meeting UL requirements. Orenco's Effluent Pumps are used in a variety of applications, including pressurized drainfields, packed bed filters, mounds, aerobic units, effluent irrigation, effluent sewers, wetlands, lagoons, and more. These pumps are designed to be used with a Biotube° pump vault or after a secondary treatment system. Franklin Liquid End S4® C US LR80980 LR2053896 Discharge Connection — Bypass Orifice — Suction Connection 0 Powered by Franklin Electric Features/Specifications To specify this pump for your installation, require the following: • Minimum 24-hour run -dry capability with no deterioration in pump life or performance* • Patented 1/8-inch (3-mm) bypass orifice to ensure flow recirculation for motor cooling and to prevent air bind • Liquid end repair kits available for better long-term cost of ownership • TRI-SEALTM floating impeller design on 10, 15, 20, and 30 gpm (0.6, 1.0, 1.3, and 1.9 L/sec) models; floating stack design on 50 and 75 gpm (3.2 and 4.7 L/sec) models • Franklin Electric Super Stainless motor, rated for continuous use and frequent cycling • Type SOOW 600-V motor cable • Five-year warranty on pump or retrofit liquid end from date of manu- facture against defects in materials or workmanship Not applicable for 5-hp (3.73 k1M models Standard Models See specifications chart, pages 2-3, for a list of standard pumps. For a complete list of available pumps, call Orenco. Product Code Diagram PF Cord length, ft (m): Blank = 10 (3) 20 = 20 (6) 30 = 30 (9) 50 = 50 (15) Voltage, nameplate: 1 = 115* 200 = 200 2 = 230t 4 = 460 Frequency: 1 = single-phase 60 Hz 3 = three-phase 60 Hz 5 = single-phase 50 Hz Horsepower (kW): 03 = 1/3 hp (0.25) 07 = 3 hp (0.56) 15 = 1-Y2 hp (1.11) 30 = 3 hp (2.24) Nominal flow, gpm (L/sec): 10 = 10 (0.6) 15 = 15 (1.0) 20 = 20 (1.3) 30 = 30 (1.9) 50 = 50 (3.2) 75 = 75 (4.7) 05 = 12 hp (0.37) 10=1hp(0.75) 20 = 2 hp (1.50) 50 = 5 hp (3.73) Pump, PF Series Y2-hp (0.37kw) only r220 volts for 50 Hz pumps 'Note: 20-foot cords are available only for single-phase pumps through 1 % hp Orenco Systems° Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 1 of 6 Orenco° Technical Data Sheet Specifications, 60 Hz Pump Model N cn E a)«9 ti aQi 3 R o = c V a)) R I co Ql di R iN N §- . E ate i tlN g R O S d Z> Q C co rL Length, in. (mm) Rated cycles/day PF100511 10 (0.6) 0.50 (0.37) 1 115 120 12.7 12.7 6 1 '/4 in. GFP 23.0 (660) 16 (406) 26 (12) 300 PF100512 10 (0.6) 0.50 (0.37) 1 230 240 6.3 6.3 6 1 '/4 in. GFP 23.0 (660) 16 (406) 26 (12) 300 PF10053200 10 (0.6) 0.50 (0.37) 3 200 208 3.8 3.8 6 1 A in. GFP 23.0 (660) 16 (406) 26 (12) 300 PF100712 4' 5 10 (0.6) 0.75 (0.56) 1 230 240 8.3 8.3 8 1 '/4 in. GFP 25.9 (658) 17 (432) 30 (14) 300 PF10073200 4' 5 10 (0.6) 0.75 (0.56) 3 200 208 5.1 5.2 8 1 '/4 in. GFP 25.4 (645) 17 (432) 31 (14) 300 PF101012 5' 6 10 (0.6) 1.00 (0.75) 1 230 240 9.6 9.6 9 1 '/4 in. GFP 27.9 (709) 18 (457) 33 (15) 100 PF10103200 5, 6 10 (0.6) 1.00 (0.75) 3 200 208 5.5 5.5 9 1 '/4 in. GFP 27.3 (693) 18 (457) 37 (17) 300 PF102012 5' 6, 7, 8 10 (0.6) 2.00 (1.49) 1 230 240 12.1 12.1 18 1 '/4 in. SS 39.5 (1003) 22 (559) 48 (22) 100 PF102032 5' 6, 8 10 (0.6) 2.00 (1.49) 3 230 240 7.5 7.6 18 1 '/4 in. SS 37.9 (963) 20 (508) 44 (20) 300 PF10203200 5, 6, 8 10 (0.6) 2.00 (1.49) 3 200 208 8.7 8.7 18 1 A in. SS 37.9 (963) 20 (508) 44 (20) 300 PF150311 15 (1.0) 0.33 (0.25) 1 115 120 8.7 8.8 3 1 '/4 in. GFP 19.5 (495) 15 (380) 23 (10) 300 PF150312 15 (1.0) 0.33 (0.25) 1 230 240 4.4 4.5 3 1 '/a in. GFP 19.5 (495) 15 (380) 23 (10) 300 PF200511 20 (1.3) 0.50 (0.37) 1 115 120 12.3 12.5 4 1 '/4 in. GFP 22.3 (566) 18 (457) 25 (11) 300 PF200512 20 (1.3) 0.50 (0.37) 1 230 240 6.4 6.5 4 1 A in. GFP 22.5 (572) 18 (457) 26 (12) 300 PF20053200 20 (1.3) 0.50 (0.37) 3 200 208 3.7 3.8 4 1 '/4 in. GFP 22.3 (566) 18 (457) 26 (12) 300 PF201012 4' 5 20 (1.3) 1.00 (0.75) 1 230 240 10.5 10.5 7 1 '/4 in. GFP 28.4 (721) 20 (508) 33 (15) 100 PF20103200 4, 5 20 (1.3) 1.00 (0.75) 3 200 208 5.8 5.9 7 1 '/4 in. GFP 27.8 (706) 20 (508) 33 (15) 300 PF201512 4' 5 20 (1.3) 1.50 (1.11) 1 230 240 12.4 12.6 9 1 IA in. GFP 34.0 (864) 24 (610) 41 (19) 100 PF20153200 4'5 20 (1.3) 1.50 (1.11) 3 200 208 7.1 7.2 9 1 '/a in. GFP 30.7 (780) 20 (508) 35 (16) 300 PF300511 30 (1.9) 0.50 (0.37) 1 115 120 11.8 11.8 3 1 '/4 in. GFP 21.3 (541) 20 (508) 28 (13) 300 PF300512 30 (1.9) 0.50 (0.37) 1 230 240 6.2 6.2 3 1 '/4 in. GFP 21.3 (541) 20 (508) 25 (11) 300 PF30053200 30 (1.9) 0.50 (0.37) 3 200 208 3.6 3.6 3 1 '/4 in. GFP 21.3 (541) 20 (508) 25 (11) 300 PF300712 30 (1.9) 0.75 (0.56) 1 230 240 8.5 8.5 5 1 '/4 in. GFP 24.8 (630) 21 (533) 29 (13) 300 PF30073200 30 (1.9) 0.75 (0.56) 3 200 208 4.9 4.9 5 1 A in. GFP 24.6 (625) 21 (533) 30 (14) 300 PF301012 4 30 (1.9) 1.00 (0.75) 1 230 240 10.4 10.4 6 1 IA in. GFP 27.0 (686) 22 (559) 32 (15) 100 PF30103200 4 30 (1.9) 1.00 (0.75) 3 200 208 5.8 5.8 6 1 '/4 in. GFP 26.4 (671) 22 (559) 33 (15) 300 PF301512 4' 5 30 (1.9) 1.50 (1.11) 1 230 240 12.6 12.6 8 1 A in. GFP 32.8 (833) 24 (610) 40 (18) 100 PF30153200 4'5 30 (1.9) 1.50 (1.11) 3 200 208 6.9 6.9 8 1 '/4 in. GFP 29.8 (757) 22 (559) 34 (15) 300 PF301534 4'5 30 (1.9) 1.50 (1.11) 3 460 480 2.8 2.8 8 1 '/4 in. GFP 29.5 (685) 22 (559) 34 (15) 300 PF302012 5' 6, 7 30 (1.9) 2.00 (1.49) 1 230 240 11.0 11.0 10 1 '/4 in. SS 35.5 (902) 26 (660) 44 (20) 100 PF30203200 5, 6 30 (1.9) 2.00 (1.49) 3 200 208 9.3 9.3 10 1 A in. SS 34.0 (864) 24 (610) 41 (19) 300 PF303012 5' 6, 7, 8 30 (1.9) 3.00 (2.23) 1 230 240 16.8 16.8 14 1 '/4 in. SS 44.5 (1130) 33 (838) 54 (24) 100 PF303032 5' 6, 8 30 (1.9) 3.00 (2.23) 3 230 240 10.0 10.1 14 1 '/4 in. SS 44.3 (1125) 27 (686) 52 (24) 300 PF305012 5' 6, 7, 8 30 (1.9) 5.00 (3.73) 1 230 240 25.6 25.8 23 1 A in. SS 66.5 (1689) 53 (1346) 82 (37) 100 PF305032 5' 6' 8 30 (1.9) 5.00 (3.73) 3 230 240 16.6 16.6 23 1 '/4 in. SS 60.8 (1544) 48 (1219) 66 (30) 300 PF30503200 5, 6' 8 30 (1.9) 5.00 (3.73) 3 200 208 18.7 18.7 23 1 '/4 in. SS 60.8 (1544) 48 (1219) 66 (30) 300 PF500511 50 (3.2) 0.50 (0.37) 1 115 120 12.1 12.1 2 2 in. SS 20.3 (516) 24 (610) 27 (12) 300 PF500512 50 (3.2) 0.50 (0.37) 1 230 240 6.2 6.2 2 2 in. SS 20.3 (516) 24 (610) 27 (12) 300 PF500532 50 (3.2) 0.50 (0.37) 3 230 240 3.0 3.0 2 2 in. SS 20.3 (516) 24 (610) 28 (13) 300 PF50053200 50 (3.2) 0.50 (0.37) 3 200 208 3.7 3.7 2 2 in. SS 20.3 (516) 24 (610) 28 (13) 300 PF500534 50 (3.2) 0.50 (0.37) 3 460 480 1.5 1.5 2 2 in. SS 20.3 (516) 24 (610) 28 (13) 300 PF500712 50 (3.2) 0.75 (0.56) 1 230 240 8.5 8.5 3 2 in. SS 23.7 (602) 25 (635) 31 (14) 300 PF500732 50 (3.2) 0.75 (0.56) 3 230 240 3.9 3.9 3 2 in. SS 23.7 (602) 25 (635) 32 (15) 300 PF50073200 50 (3.2) 0.75 (0.56) 3 200 208 4.9 4.9 3 2 in. SS 23.1 (587) 26 (660) 32 (15) 300 NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 2 of 6 Orenco Systems° Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com Technical Data Sheet Orenco® Specifications, 60 Hz (continued) Pump Model a1 ca o 'a c) c -ad a7 N co7 o � = - - z > a E lC lx0 aa) E Length, in. (mm) Rated cydes/day PF500734 50 (3.2) PF501012 50 (3.2) PF50103200 50 (3.2) PF501034 50 (3.2) PF5015124 50 (3.2) PF501532004 50 (3.2) PF503012 4, 5, 7, 8 50 (3.2) PF50303200 4, 5' 8 50 (3.2) PF503034 4' 5, 8 50 (3.2) PF505012 5,6,7,8 50 (3.2) PF505032 5,6,7,8 50 (3.2) PF751012 75 (4.7) PF751512 75 (4.7) 0.75 (0.56) 3 460 480 1.8 1.8 3 2 in. SS 34.8 (884) 25 (635) 31 (14) 300 1.00 (0.75) 1 230 240 10.1 10.1 4 2 in. SS 27.0 (686) 26 (660) 35 (16) 100 1.00 (0.75) 3 200 208 5.7 5.7 4 2 in. SS 26.4 (671) 26 (660) 39 (18) 300 1.00 (0.75) 3 460 480 2.2 2.2 4 2 in. SS 26.4 (671) 26 (660) 39 (18) 300 1.50 (1.11) 1 230 240 12.5 12.6 5 2 in. SS 32.5 (826) 30 (762) 41 (19) 100 1.50 (1.11) 3 200 208 7.0 7.0 5 2 in. SS 29.3 (744) 26 (660) 35 (16) 300 3.00 (2.23) 1 230 240 17.7 17.7 8 2 in. SS 43.0 (1092) 37 (940) 55 (25) 100 3.00 (2.23) 3 200 208 13.1 13.1 8 2 in. SS 43.4 (1102) 30 (762) 55 (25) 300 3.00 (2.23) 3 460 480 5.3 5.3 8 2 in. SS 40.0 (1016) 31 (787) 55 (25) 300 5.00 (3.73) 1 230 240 26.2 26.4 13 2 in. SS 65.4 (1661) 55 (1397) 64 (29) 300 5.00 (3.73) 3 230 240 16.5 16.5 13 2 in. SS 59.3 (1506) 49 (1245) 64 (29) 300 1.00 (0.75) 1 230 240 9.9 10.0 3 2 in. SS 27.0 (686) 27 (686) 34 (15) 100 1.50 (1.11) 1 230 240 12.1 12.3 4 2 in. SS 33.4 (848) 30 (762) 44 (20) 100 Specifications, 50 Hz Pump Model PF100552 PF100752 4' 5 PF101552 5, 6 PF300552 PF300752 PF301052 PF301552 4, 5 PF500552 PF500752 PF501052 PF501552 PF751052 10 (0.6) 10 (0.6) 10 (0.6) 30 (1.9) 30 (1.9) 30 (1.9) 30 (1.9) 50 (3.2) 50 (3.2) 50 (3.2) 50 (3.2) 75 (3.2) 0.50 (0.37) 0.75 (0.56) 1.50 (1.11) 0.50 (0.37) 0.75 (0.56) 1.00 (0.75) 1.50 (1.11) 0.50 (0.37) 0.75 (0.56) 1.00 (0.75) 1.50 (1.11) 1.00 (0.75) 220 220 220 220 220 220 220 220 220 220 220 220 230 230 230 230 230 230 230 230 230 230 230 230 3.9 6.2 10.5 4.1 6.1 7.4 9.3 4.0 6.3 7.3 9.1 7.3 4.1 6.2 11.4 4.1 6.1 7.4 9.3 4.0 6.4 7.4 9.1 7.3 6 9 18 4 5 7 8 2 3 4 5 4 1 '/a in. GFP 1 Ya in. GFP 1 '/a in. SS 1 '/4 in. GFP 1 '/a in. GFP 1 '/4 in. GFP 1 1/4 in. GFP 2 in. SS 2 in. SS 2 in. SS 2 in. SS 2 in. SS 23.0 (584) 26.8 (658) 39.5 (1003) 22.5 (572) 24.8 (630) 28.4 (721) 35.4 (899) 20.3 (516) 23.7 (602) 27.0 (686) 32.5 (826) 30.0 (762) 17 (432) 17 (432) 22 (559) 19 (483) 19 (483) 20 (508) 24 (610) 25 (635) 25 (635) 26 (660) 30 (762) 27 (686) 26 (12) 30 (14) 46 (21) 26 (12) 29 (13) 32 (15) 40 (18) 29 (13) 31 (14) 35 (16) 42 (19) 34 (15) 300 300 300 300 300 100 100 300 300 100 100 100 1 GFP = glass -filled polypropylene; SS = stainless steel. The 1 '14-in. NPT GFP discharge is 2 7i8 in. octagonal across flats; the 1 3/4-in. NPT 2-in. NPT SS discharge is 2 7B in. hexagonal across flats. Discharge is female NPT threaded, U.S. nominal size, to accommodate Orenco® Distributor about fittings to connect hose and valve assemblies to metric -sized piping. 2 Minimum liquid level is for single pumps when installed in an Orenco Biotube® Pump Vault or Universal Flow Inducer. In other applications, Orenco for more information. 3 Weight includes carton and 10-ft (3-m) cord. 4 High-pressure discharge assembly required. 5 Do not use cam -lock option (Q) on discharge assembly. 6 Custom discharge assembly required for these pumps. Contact Orenco. 7 Capacitor pack (sold separately or installed in a custom control panel) required for this pump. Contact Orenco. 8 Torque locks are available for all pumps, and are supplied with 3-hp and 5-hp pumps. SS discharge is 2 1/8 in. octagonal across flats; and the discharge hose and valve assemblies. Consult your Orenco minimum liquid level should be top of pump. Consult Orenco Systems° Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 3 of 6 Orenco® Technical Data Sheet Materials of Construction Discharge Glass -filled polypropylene or stainless steel Discharge bearing Engineered thermoplastic (PEEK) Diffusers Glass -filled PPO (Noryl GFN3) Impellers Celcon® acetal copolymer on 10-, 20, and 30-gpm models; 50-gpm impellers are Noryl GFN3 Intake screen Polypropylene Suction connection Stainless steel Drive shaft 7/16 inch hexagonal stainless steel, 300 series Coupling Sintered stainless steel, 300 series Shell Stainless steel, 300 series Motor Franklin motor exterior constructed of stainless steel. Motor filled with deionized water and propylene glycol for constant lubrication. Hermetically sealed motor housing ensures moisture -free windings. All thrust absorbed by Kingsbury -type thrust bearing. Rated for continuous duty. Single- phase motors and 200 and 230 V 3-phase motors equipped with surge arrestors for added security. Single-phase motors through 1.5 hp (1.11 kV) have built-in thermal overload protection, which trips at 203-221° F (95-105° C). Using a Pump Curve A pump curve helps you determine the best pump for your system. Pump curves show the relationship between flow (gpm or L/sec) and pressure (total dynamic head, or TDH), providing a graphical representation of a pump's optimal performance range. Pumps perform best at their nominal flow rate — the value, measured in gpm, expressed by the first two numerals in an Orenco pump nomenclature. The graphs in this section show optimal pump operation ranges with a solid line. Flow flow rates outside of these ranges are shown with a dashed line. For the most accurate pump specification, use Orenco's PumpSelect software. Pump Curves, 60 Hz Models Total dynamic head (TDH) in feet 800 700 600 500 400 300 200 100 1 1 1 1 I PF10 Series, 60 Hz, 0.5 2.0 hp PF1020 '' - PF1010 - PF1007 • PF1005 "" PF1005-FC ` w/'/4" flow controller 0 2 4 6 8 10 12 14 Flow in gallons per minute (gpm) Total dynamic head (TDH) in feet 160 140 120 100 80 60 40 20 PF15 Series, 60 Hz, 0.3 hp PF1503 0 0 3 6 9 12 15 18 21 Flow in gallons per minute (gpm) 24 NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 4 of 6 Orenco Systems° Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com 60 Hz Models (continued) 400 350 4- c 300 f=1 - 250 -a c • 200 • 150 - 100 4- Total dynamic head (TDH) in feet 50 PF2015 1 1 1 1 1 1 1 PF20 Series, 60 Hz, 0.5 - 1 5 hp PF2010 13F20051 ..... ..... ..... ..... 0 0 450 400 350 300 250 200 150 100 50 5 10 15 20 25 30 35 Flow in gallons per minute (gpm) 40 I I PF5050 I I I I I I I PF50 Series, 60 Hz, 0.5 - 5.0 hp PF5030 PF5010 ....... .......... jPF5007 ..... 1••• PF5005 ....... ..... 10 20 30 40 50 60 70 80 90 Flow in gallons per minute (gpm) Total dynamic head (TDH) in feet Total dynamic head (TDH) in feet 900 P F3050 800 700 600 I I I I PF30 Series, 60 Hz, 0.5 - 5.0 hp PF3030 500 400 300 200 100 .... PF3020 PF3015I PF3010 ... PF3007 1 1 PF3005 ..... ..... ••• .... .......... ........ '• ............ ..... oo 100 90 80 70 60 50 40 30 20 10 5 10 15 20 25 30 35 40 45 Flow in gallons per minute (gpm) jPF7515 111111 I I I PF75 Series, 60 Hz, 1.0 - 1.5 hp PF7510 oo 10 20 30 40 50 60 70 80 90 Flow in gallons per minute (gpm) 100 Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 5 of 6 Orenco° Technical Data Sheet Pump Curves, 50 Hz Models 180 160 140 E .E 120 1— 100 -Fa = • 0 E = 80 60 40 20 45 40 35 30 25 20 15 10 5 0 0 Flow in gallons per minute (gpm), nominal 1.6 3.2 4.8 6.3 7.9 9.5 11 13 EMEMEMMMI.1-----3---- EMMEIMMENNEMENNEN MENEMOMMENNEMMEN MENEME„MENNEll MENEMEN"NMENNEM IIMMINMENNEMENNEMEM LRE IMMEME■■■■,■■■■■ MillinnillEMMEMEMEN IMMENESIIMMEMMEN LTATZMEEMENNIIMOM MENNIMENElliiiEWONIM ■■■■ PF1005-FC „■.,E„■ • •I wcont m Herw MM„NE'EM • Immmlll EMENSMvEN 525 _ = 459 394 d 328 x H 262 197 131 66 01 02 0.3 0.4 05 06 07 08 09 Flow in liters per second (L/sec) Flow in gallons per minute (gpm), nominal 7.9 16 24 32 40 48 56 63 131 115 98 82 66 49 33 16 PF50 Series, 50 Hz, 0.37 -1.11 kW — PF5015521 ,.I PF501052 PF5007521 PF500552. 05 10 1.5 2.0 25 30 3.5 40 45 F ow in liters per second IL/sec) a _ s= 120 100 a) m E .E 80 x = 60 m 0 E = 40 a 20 Flow in gallons per minute (gpm), nominal 63 13 19 25 32 PF30 Series, 50 Hz, 0.37 -1.11 kW PF301552I IPF3010521 -PF300752 00 30 27 e: _ o y 24 = y a) = 21 0 18 x co 15 a a) s •= 12 c.e _ _ e: > 9 6 H 3 0 0 06 1.2 18 24 30 36 42 48 54 60 Flow in liters per second (L/sec) JPF3005521 • 04 08 12 16 20 Flow in liters per second (L/sec) Flow in gallons per minute (gpm), nominal 10 19 29 38 48 57 67 76 86 328 = 0 262 e x 197 I- -= m 131 'g 24 PF75 Series, 50 Hz, 0.75 kW PF751052 = 66 89 R 79 0 69 Is 0) 59 = 49 H a R 39 = 30 0 20 To NTD-PU-PF-1 Rev. 2.2, © 09/14 Page 6 of 6 0renco Systems° Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com Orenco® Technical Data Sheet Orifice Shields Applications Orenco® Orifice Shields are used in a pressurized distribution system to protect the orifices from backfill debris that might cause orifice blockage. Orifice shield installed on lateral pipe, standard configuration Shield Orifice Cutaway view, standard configuration P a a a< <R a<< t Orifice Shield Cutaway view, cold weather configuration General Orenco Orifice Shields snap -fit onto laterals. They may be placed on top of or beneath a lateral, depending on the location of the orifice. Orifice shields are covered by method -of -use patent # 5,360,556. Standard Models OS075, OS100, 0S125, OS150, OS200 Product Code Diagram OS Lateral pipe size, nominal: 075 = 0.75 in. (20 mm) 100 = 1.00 in. (25 mm) 125 = 1.25 in. (32 mm) 150 = 1.50 in. (40 mm) 200 = 2.00 in. (50 mm) Orifice shield Material of Construction PVC per ASTM D-1784 Physical Specifications Model Shield O.D. in. (mm) Lateral pipe O.D. in. (mm) OS075 OS100 0S125 0S150 OS200 3.5 (89) 3.5 (89) 3.5 (89) 4.5 (114) 4.5 (114) 1.05 (27) 1.315 (33) 1.66 (42) 1.90 (48) 2.375 (60) Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-SF-OS-1 Rev. 1.1, © 09/14 Page 1 of 1 Item# SEK- Orenco® Flushing Assemblies Flushing Assemblies Orenco® flushing assemblies provide easy access for lateral maintenance. Flushing assembly kits include a PVC sweep with ball valve and a polyethylene valve box enclosure. Orenco K flushing assemblies are available in the following sizes: • 1" diameter • 1.25" diameter • 1.5" diameter • 2" diameter Valve Boxes Orenco® valve boxes are used to provide access to flushing assemblies. Constructed of polyethylene. Valve Box, 7-in. diameter round enclosure Note: Kits include VB7 valve box enclosure. OM VI VALLEY PRECAST, inc. Water & Wastewater • Systems • Products • Service (719) 395-6764 28005 County Road 317 P.O. Box 925 Fax: (719) 395-3727 Buena Vista, CO 81211 Website: http://valleyprecast.com/ Email: frontdesk@valleyprecast.com