HomeMy WebLinkAboutCorrespondenceDave Argo
From: Dave Argo
Sent: Tuesday, July 21, 2020 8:06 AM
To: Patrick Stuckey (stucarch@comcast.net)
Cc: Andy Schwaller (aschwaller@garfield-county.com)
Subject: Ironbridge Lot 295 - Permit #BLRE-06-20-6356
Patrick:
I am currently reviewing a new residence located on Lot 295 at Ironbridge PUD, but before I can finalize my review &
issue a permit the following items need to be addressed:
A. Site Plan — Obviously, this home is located very close to the property line and an existing home located on the
adjacent Lot 296, and that is why one-hour wall construction is required where the two structures are closest
together. However, there is no clear indication as to where exactly the actual property line is located on your
site plan (or the main level plan). Please provide a supplemental site plan drawing clearly indicating the
following: (1) actual property line, (2) "imaginary" property line used for purposes of determining fire separation
between adjacent structures, and (3) minimum distances from each residence to these respective property lines.
This supplemental drawing can be an 11 x 17 size portion of the actual site plan if you like, but please also clearly
indicate extent of actual roof overhangs at the existing home on Lot 296 so that we can verify required fire
separation setbacks as per IRC, Table R302.1(1).
B. Location of Fire -Rated Exterior Wali — You do not clearly indicate on your drawings the exact location of the
required one-hour rated fire wall for the new residence, but instead simply refer to it as the "west wall of the
great room" in your notation. The specific location and extent of this wall needs to be more clearly illustrated on
the main level floor plan to include the entirety of the westerly wall and, in addition, the fireplace chimney chase
walls outboard of the great room exterior wall.
C. Fire -Rated Wall Listing & Specifications — We also require that you submit to our office a fire -rated listing
agency ID number (including specifications/details) of the fire -rated wall construction from a nationally
recognized testing agency (for example, Underwriters' Laboratory of U.S. Gypsum Council). Again, this
supplemental information can be submitted in smaller sized sheet format, but we will ultimately attach it to the
approved set of plans prior to our office issuing a building permit.
Thank you for your attention to this matter.
Dave Argo
Plans Examiner
. Garfield County!
Community Development Department
108 8th Street, Suite 401
Glenwood Springs, CO 81601
Tel: 970-945-8212 Ext. 1610
Email: dargo@garfield-county.com
Web: garfield-county.com
1
Dave Argo
From: Patrick Stuckey <stucarch@comcast.net>
Sent: Tuesday, July 21, 2020 5:56 PM
To: Dave Argo
Cc: Andy Schwaller;-Wesley Cole; Robert Schneider
Subject: [External] Ironbridge Lot 295 - Permit #BLRE-06-20-6356
Attachments: Specifying 1 Hour fire -Rated Walls Engineered Wood Blog.pdf; 01 1. FR Site Pian.pdf;
GA File No. WP 8105.pdf
Hello Dave,
Attached is an 11 x 17 Fire Rated Wall and Construction Plan. It shows the Actual Property Lines, the existing structure
per survey, Imaginary Property Line, area of fire rated wall and description of fire rated wall assembly including the GA
File Number (WP 8105).
Also included is the specification for GA File Number (WP 8105) in a PDF format. I attached an additional assembly for
use of LP Flame Block Fire -Rated OSB Sheathing in case the General Contractor would prefer to use it over the fire -rated
gyp sheathing.
Best Regards,
Patrick
Patrick W. Stuckey Architects
NCARB, AIA
Email: stucarch0.comcast.net
MAILING ADDRESS:
960 Clubhouse Drive
New Castle, CO 81647
970.984.9220 Office
970.984.9220 Fax
EXTERIOR WALLS
GA FILE NO. WP 8105
L
GENERIC
GYPSUM WALLBOARD, GYPSUM SHEATHING, WOOD STUDS
EXTERIOR SIDE: One layer 48" wide 5/8" type X gypsum sheathing applied parallel to
2 x 4 wood studs 24" o.c. with 1 3/4" galvanized roofing nails 4" o. c. at vertical joints and
7" o.c. at intermediate studs and top and bottom plates . Joints of gypsum sheathing
may be left utreated. Extrerior cladding to be attached through sheathing to studs.
INTERIOR SIDE: One layer 5/8" type X gypsum wallboard, water-resistant gypsum
backing board, or gypsum veneer base applied parallel or at right angles to studs with
6d coated nails 1 7/8" long, 0.0915" shank, 1/4" heads 7" o.c. (LOAD-BEARING)
1 HOUR
FIRE
Thickness: Varies
Approx. Weight: 7 psf
Fire Test: See WP 3510
(UL R3501-47, -48, 9-17-65,
UL Design U309;
UL R1319-129, 7-22-70,
UL Design U314)
Specifying 1 Hour fire -Rated Walls I Engineered Wood I Blog
7/21/20, 5:47 PM
IN; rift. -7,1. S`k`O[ES I 6min
SPECIFYING 1 HOUR FIRE -RATED
WALLS
For about a century, architects and builders have used gypsum panels in
wall assemblies to meet the testing criteria for 1 hour fire -rated walls. As
NIP
product engineering develops, more and more architects are now looking
Infor product solutions that bring added value to their 1 hour fire -rated walls.
Many are specifying LP° FlanneBlock® Fire -Rated OSB Sheathing because it
meets building codes while providing faster and easier installation than
in assemblies that use gypsum and structural panels. They can also provide
added design flexibility by reducing wall thickness.
LP FlameBlock sheathing can be used in a few different 1 hour fire -rated
https://Ipcorp.com/blog/specifying-1-hour-fire-rated-walls Page 1 of 5
Specifying 1 Hrnir fire -Peters Walls 1 Engineered Wood 1 Blog 7/21/20, 5'47 PM
wall assemblies, including:
Intertek Design LPB/WPPS-60-01:This Intertek-listed assembly is
commonly used in 1 hour exterior walls along the property line, including
single-family construction. This assembly is fire -rated for 1 hour from both
sides.
1 •SIDED
LR' FLAMEaLOCK'
EXTERIOR
CLADDING
MINERAL WOOL INSULATION
2X6STUDS
(MINIMUM)
TYPE X
GYPSUM
UL Design U348: This UL -listed assembly is commonly used in Type V
multifamily construction in load-bearing exterior walls. It also allows for the
use of fiberglass insulation. This assembly is fire -rated for 1 hour from the
interior side only, except when brick is the exterior facing.
https://Ipcorp.com/blog/specifying-1-hour-fire-rated-walls Page 2 of 5
Specifying 1 Hour fire -Rated Walls I Engineered Wood I Blog 7/21/20, 5:47 PM
FIBERGLASS IIISULATION
HIDEO
LP" FLABIEB*OGif'
tt
•
EXTERIOR TYPE X
CLAIM GYPSUM
2-X4 STUDS
When specified for these 1 hour fire -rated assemblies, LP FlameBlock
sheathing reduces dead load and wall thickness versus common
alternatives. It also providesbetter substrate for securely fastening exterior
facing materials. Unlike gypsum, LP FlameBlock sheathing has an Exposure
1 classification—which means it can withstand normal exposure to moisture
during construction.
Fire -rated walls shouldn't interfere with your design capabilities and
construction schedules. Check out our LP FlameBlock page to learn more
about the U348 and WPPS-60-1 assemblies.
flameblock fire resistance codes & compliance
https://Ipcorp.com/blog/specifying-1-hour-fire-rated-walls Page 3 of 5
Specifying 1 Hour fire -Rated Walls I Engineered Wood 1 Blog 7/21/20, 5:47 PM
CONTINUE READING
Top 5 Benefits of
LPO BuiIdSmartTM
Preferred
Contractor Program
When it comes to the wide variety of
contractor loyalty programs that exist on
the market, the tangible payoff it can have
on your business is not always clear. But,
https://Ipcorp.com/blog/specifying-1-hour-fire-rated-walls
It's Getting Hot in Here: The
Benefits Of LP® TechSh ield®
Radiant Barrier
Radiant barriers have become very popular
with efficiency -minded builders in the
recent years. This is largely due to the fact
that when installed properly, a radiant
barrier can reduce the impact of summer
heat and yield tangible savings in cooling
costs of a home—a persuasive selling point
when addressing potential homeowners.
But how does radiant barrier work and
what exactly are its effects?
Crushing the Top Rumors About
Engineered Wood
LP Building Solutions uses engineered
wood to create a portfolio of products that
help professionals build smarter, better
and faster. The innovations of engineered
wood siding are relatively new. For
instance, LP® SmartSide® Trim & Siding
Page 4 of 5
Specifying 1 Hour fire -Rated Walls 1 Engineered Wood 1 Blog 7/21/20, 5:47 PM
not to worry. Today we break down the
details of the LP® BuildSmartTM Preferred
Contractor Program.
CONTINUE READING
was introduced in 1997. Thanks to its
advanced manufacturing process, it is one
of the most durable siding solutions
available. Sometimes people are skeptical
of things that are really that good. So, let's
crush a few myths with engineered wood
facts.
BUSINESS ADVICE 14 min
Building Pier and Beam
Foundation to Ease Maintenance
and Repairability
Pier and beam design was among the most
popular foundation techniques until the
1960s when concrete technology improved
its floating slab system. Many builders use
slab -on -grade construction—especially in
warmer regions. We're going to find out
why professionals Jordan Smith of
@jordansmithbuilds and Kyle
Stumpenhorst of ®rrbuildings chose pier
and beam over slab -on -grade for the All -
in -LP Build in Bellville, Texas. But first,
let's delve into pier and beam foundation.
https://Ipcorp.com/blog/specifying-1-hour-fire-rated-walls Page 5 of 5
LOT 296
ELEC.
ETER
E
-UAL
TY
r
_
M1
- o
2100
O ,..1
M1
OI
‘1I
1 5e -On
STONE
COLUMN
(TYP.)
1
`�_ ACTUAL
_•
N 86°49'23" W PROPERTY LINE 36.92'
rit` IMAGINARY PROPERTY LINE
5 FEET FROM EXISTING STRUCTURE
' IMAGINARY 5 SETBACK FROM ACTUAL PROPERTY LINE
1
DININ61. PATIO
3/
n
U..,
2,
co-
J Q
CO
c
a▪ wl
1 HR FIRE RATED WALL CONSTRUCTION @ WEST O 1
WALL OF GREAT RM PER IRC 2015, TABLE 720.1(2) ac 1
ITEMS 15-1,13 $/OR I5-114GAFile ry LIIP.ALQ5Q—
EXTERIOR FINISH - INSTALL PER MFG RECOMMENDATIONS, -
MAINTAIN REQUIRED CLEARANCE FROM GRADE - 6" MIN.) OVER
TYVECK (OR EQ. HOUSE WRAP) ON 5/B" TYPE "X" EXTERIOR
GYPSUM SHEATHING ON 2x6 WOOD STUDS @ 16" o c. W/
5 1/2" BATT INSULATION (R -2I) W/ CERTAINTEED (MEMBRAIN)
VAPOR RETARDER $ 5/B" TYPE "X" GYP. BD.
LOT 295
1
22" x 30" MINi5EALED
ATTIC ACCE54 (AIV)
VFRTFV HFA 1-1T R(1"+
1
IMAGINARY 5' SETBACK FROIIMACTUAL PROPERTY_LIVIj
U
▪ 1
0
LLI
GREAT ROOM
106
HALL
Fire Rate Wall Location/Const.
SCALE: 1/4" = l' -O"
ENTRY
CLOSET
102
/
TOP OF SLAB ELEV 128'—
SITE ELEV = 5944.7)'
/
/
/
/
/
u
DINING
105
1
1
1
1
11
1
1
1
1
r
L
_v 0
PANTRY
103
30" refrigerator
PE
I9
■
PATRICK W. MCREY ARCHITECTS
WES COLE
CAL KENDRICK
430 IRONBRIDGE
DRIVE
LENW000 SPRING
COLORADO
61601
IRONBRIDGE
BLOCK 2
PHASE 0
Lot 295
GARFIELD,
COLORADO
CUSTOM
RESIDENCE
PRINT DATE:
07.21.2020
ISSUE DATE
07.21.2020
1
ALL DRAWN AND VIIMEN INRCHATION
APPEARING HEREIN SHALL NOT RE
EMULATE, DISCLOSED, OR 01 I IERWISE
BE USED WM IOUT WRITTEN CONSENT Of
51101,
ARCH