September 5, 2018
Tom Provost
P.O. Box 1128
Carbondale, CO 81623
Subject: Sub -excavation and Structural Fill
Provost Residence
Lot 53-B, Panorama Ranches
Garfield County, Colorado
Project No. GS06219.000
CTL 1 Thompson, Inc. performed a geotechnical investigation for the Prov-
ost Residence under this project number (report dated April 17, 2018). An alter-
native that we recommended was to subexcavate the natural soils below the
building to a depth of at least 3 feet and moisture -treat and replace the excavated
soils as densely -compacted, structural fill.
During excavation operations, we visited the site to observe the bottom of
the sub -excavated area below the planned building. Subsequently,
CTL/Thompson, Inc. observed and tested structural fill during placement. In our
opinion, the structural fill is in general conformance with project specifications
and suitable for support of footings and floor slabs for the residence.
We appreciate the opportunity to work with you on this project. If you
have questions or we can be of further service, please call.
Very truly yours,
CTL 1 THOMPSON, INC.
\[�J .fir
Jes D. Kellogg, P.E
■'vision Manager
JDK:ac
cc: Via email to blkmagicweldino sorris.net
234 Center Drive 1 Glenwood Springs, Colorado 81601
Telephone: 970-945-2809 Fax: 970-945-7411
CTL l THOMPSON Compaction Testing
Report #: SNG-000007
812412018
Report Date: 8127/2018
Test Method: ASTM D 6938
Glenwood Springs
234 Center Drive
Glenwood Springs. CO 81501
Phone: 970-945.2800
Client:
Tom Provost
P.O. Box 1128
Carbondale, CO 81623
Project:
GS06219.000F-345
Provost Residence
Garfield County, CO
Test Results
Test #
Retest
Of
Test
Date
Proctor ID
Method
Soil
Classification
Optimum
Moisture
(%)
Maximum
Dry Density
(pcf)
In Place
Moisture
(%)
In Place
Dry Density
(pcf)
Probe
Depth
(in)
Percent
Compaction
Min Comp.
(%)
Remark
23
8/24/18
Curve No, 2
698C
Granular
8.5
132.0
4.3
133.3
8
101
98
D
24
8/24/18
Curve No, 2
698C
Granular
8.5
132.0
4.5
133.0
8
101
98
b
25
8/24/18
Curve No, 2
698C
Granular
8.5
132.0
4.2
134.4
8
102
98
0
26
8/24/18
Curve No, 2
698C
Granular
8.5
132.0
4.4
134.1
8
102
98
0
Test information
Test #
Test Location
Elevation
Reference
Gauge
Make / Model / SN / Calibrated
Field Technician
23
Structural Fill: grid lines 8.5/1.5
0.0
below bottom of footing
XPLORER /3500 / 1995 / 4/1 31201 7
Thibault, Sandon
24
Structural Fill: grid fines A.2/1.9 _
0.0
below bottom of footing
XPLORER / 3500 / 1995 / 4/13/2017
Thibault, Sandon
25
Structural Fill: grid tines C.114
0.0
below bnitorn of fooling
XPLORER/ 3500 / 1995 / 4/13/2017
Thibault. Sandon
26
Structural Fill: grid lines D.5/1.5
0.0
below bottom of footing
XPLORER / 3500 / 1995 / 4/13/2017
Thibault. Sandon
Remarks
Comments
D: Test result is considered acceptable with no moisture
requirement.
Tests are "Direct Transmission° (Method Aj unless probe depth is noted as
SackSCatter'. Gauge calibration data on Cita wit the testing agency.
26: The contractor had completed the structural fell placement below
footings and Footing pads. density tests results are satisfactory. A rock
correction was applied to the above density tests.
This report presents opinions formed as a result of our observations of fill placement and the test results shown above. Test data are not the sole basis for
opinions whether the fill meets project specifications. The contractor is responsible to apply necessary compaction effort and moisture to comply with project
specifications . Our test results, observations and opinions do not constitute acceptance of the work.
Page 1 of 1