HomeMy WebLinkAboutInterior Lighting Compliance Certificate 10.09.20201 (ift
COMcheck Software Version 4.1.4.1
interior Lighting Compliance Certificate
Project Information
Energy Code:
Project Title:
Project Type:
2015 IECC
Aspen Glen
New Construction
Construction Site: Owner/Agent: Designer/Contractor:
Carbondale
CO
Additional Efficiency Package(s)
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts / ft2 (B X C)
1-Dining: Bar Lounge/Leisure 3570 0.91 3245
Proposed Interior Lighting Power
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
1 Dining: Bar Lounge/Leisure
LED 1: LT-100: Other:
LED 2: LT-101: Other:
LED 3: LT-102: Other:
LED 4: LT-103: Other:
LED 5: LT-104: Other:
LED 6: F: Other:
LED 7: G: Other:
LED 8: H: Other:
LED 9: J: Other:
LED 10: K: Other:
Total Allowed Watts = 3245
B C D E
Lamps/ # of Fixture (C X D)
Fixture Fixtures Watt.
1 10 8 75
1 3 38 112
1 3 68 202
1 1 60 60
1 1 45 45
1 21 11 225
1 6 21 126
1 6 11 65
1 1 60 60
1 1 60 60
Total Proposed Watts = 1030
Interior Lighting PASSES: Design 68% better than code
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcherk Version 4.1.4.1 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Jack Shattuck
Name - Title
Signature
10/9/2020
Date
Project Title: Aspen Glen Report date: 10/09/20
Data filename: \\Filesol\shares\Projects\05066 - Club Corp\05066.44 - Aspen Glen\11-ComCheck\Blackstone G Page 1 of 5
Electrical Comcheck.cck
COMcheck Software Version 4.1.4.1
rift
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
& Req.ID
C103.2
[PR4]1
Plan Review
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies?
®Complies
❑Does Not
❑Not Observable
❑Not Applicable
Comments/Assumptions
C406 k Plans, specifications, and/or
[PR9]1 :calculations provide all information
with which compliance can be
:determined for the additional energy
efficiency package options.
Complies
❑Does Not
['Not Observable;
ENot Applicable [
11
Additional Comments/Assumptions:
1
High Impact (Tier 1)
2
Medium Impact (Tier 2)
3
Low Impact (Tier 3)
Project Title: Aspen Glen Report date: 10/09/20
Data filename: \\Filesol\shares\Projects\05066 - Club Corp\05066.44 - Aspen Glen\11-ComCheck\Blackstone C. Page 2 of 5
Electrical Comcheck.cck
Section
#
& Req.ID
Rough -In Elec!crical Inspection
Complies?
Comments/Assumptions
C405.2.1
[EL15]1
Lighting controls installed to uniformly
reduce the lighting load by at least
50%.
ElComplies
•Does Not
❑Not Observable
■Not Applicable
C405.2.1 !Occupancy sensors installed in
[EL18]1 i required spaces.
I
®Complies
In Does Not
['Not Observable
❑Not Applicable
C405.2.1,
C405.2.2.
3
(EL23]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
'visible to occupants.
G
®Complies
❑Does Not
❑Not Observable
•Not Applicable
C405.2.2.
1
[EL22]2
lAutomatic controls to shut off all
building lighting installed in all
buildings.
®Complies
❑Does Not
❑Not Observable
Not Applicable
C405.2.3
[EL1O
;Daylight zones provided with
individual controls that control the
lights independent of general area•
lighting.
•Complies
•Does Not
Not Observable
FA Not Applicable
C405.2.3,
C405.2.3.
C405.2.3.1,
2®Not
[EL20]1
Primary sidelighted areas are
equipped with required lighting
controls.
■Complies
I■Does Not
Not Observable
Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
3
[EL21]1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting•
controls.
❑Complies
❑Does Not
Not Observable
Not Applicable
C405.2.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
f''IComplies
•Does Not
•Not Observable
❑Not Applicable
C405.2.4
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
®Complies
•Does Not
•Not Observable
❑Not Applicable
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
®Complies
❑Does Not
•Not Observable
•Not Applicable
Additional Comments/Assumptions:
1
High Impact (Tier 1)
2
Medium Impact (Tier 2)
3
Low Impact (Tier 3)
Project Title: Aspen Glen Report date: 10/09/20
Data filename: \\Files0l\shares\Projects\05066 - Club Corp\05066.44 - Aspen Glen\11-ComCheck\Blackstone C Page 3 of 5
Electrical Comcheck.cck
Section
#
& Req.ID
Final Inspection
Complies?
Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
. representative.
•Complies
❑Does Not
Not Observable
■Not Applicable
C405.4.1
[F118]1
;Interior installed lamp and fixture
I lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
I watts.
.CDComplies
ISee the Interior Lighting fixture schedule for values.
•Does Not
Not Observable
•Not Applicable
C408.2.5. i Furnished as -built drawings for
1 ielectric power systems within 90 days
[F116]3 !of system acceptance.
•Complies
•Does Not
Not Observable
■Not Applicable
C408.3 Lighting systems have been tested to
[F133]1 .ensure proper calibration, adjustment,
k programming, and operation.
f
•Complies
■Does Not
®Not Observable
■Not Applicable
Additional Comments/Assumptions:
1
High Impact (Tier 1)
2
Medium Impact (Tier 2)
3
Low Impact (Tier 3)
Project Title: Aspen Glen
Data filename: \\Files0l\shares\Projects\05066 - Club Corp\05066.44 - Aspen Glen\11-ComCheck\Blackstone C. Page 4 of 5
Electrical Comcheck.cck
Report date: 10/09/20
Project Title: Aspen Glen Report date: 10/09/20
Data filename: \\Files0l\shares\Projects\05066 - Club Corp\05066.44 - Aspen Glen\11-ComCheck\Blackstone C Page 5 of 5
Electrical Comcheck.cck