From: Dave Argo
Sent: Thursday, January 7, 2021 5:50 PM
To: Bill Gavette (gavette@carbondalefire.org)
Subject: Western Slope Materials - New Addition to Existing Building
Attachments: Western Slope Materials Addition.docx
Bill:
Just wanted to give you a head's up that Western Slope Materials — the gravel pit across Highway 82 from Ranch at
Roaring Fork — is building an addition onto the existing steel building located across from their scale & office building.
Since the total size of the steel building (Type V-B construction) is still < 7,500 S.F. it doesn't appear to require fire
sprinklers (actual total size = 6,515 S.F.)
However, I wanted to let you know that they should be in touch with you since we are going to require sign -off from the
Fire District prior to final inspection & C.O. The general manager is Sean Mello, and you should be getting a call from him
to discuss/confirm I.F.C. requirements.
Dave Argo
Plans Examiner
. Garfield County
Community Development Department
108 8th Street, Suite 401
Glenwood Springs, CO 81601
Tel: 970-945-8212 Ext. 1610
Email: dargo@garfield-county.com
Web: garfield-county.com
1
CONDITIONS OF PERMIT
BLCO-12-20-6621
Western Slope Materials, LLC
Mfd. Steel Building — Addition to Existing Structure
14682 Highway 82 Carbondale, Colorado
1) ALL WORK SHALL COMPLY WITH THE 2015 I.B.C., I.F.C., I.M.C., I.P.C., I.F.G.C. AND 2009 I.E.C.C., AS
WELL AS MANUFACTURER'S INSTALLATION REQUIREMENTS.
2) REFER TO PLAN ATTACHMENTS FOR GARFIELD COUNTY'S COMMERCIAL BUILDING REQUIREMENTS,
DESCRIPTION OF PLAN REVIEW REDLINE COMMENTS & INSPECTIONS POLICIES.
3) ALL WORK MUST COMPLY WITH GARFIELD COUNTY'S "RURAL" ZONE DISTRICT REGULATIONS AND
WITH ALL REQUIREMENTS INCLUDED IN THE CURRENT LAND USE PERMIT.
4) THIS NEW ADDITION IS APPROVED AS TYPE V-B CONSTRUCTION, OCCUPANCY GROUP "S-1"
(MODERATE HAZARD STORAGE). EXISTING BUILDING ALSO INCLUDES OFFICES ("B" OCCUPANCY
GROUP). FIRE SPRINKLER SYSTEM NOT REQUIRED, BECAUSE OVERALL BUILDING SIZE < 7,500 S.F.
SIZE, AS PER GARFIELD COUNTY RESOLUTION FOR ADOPTION OF 2015 I.F.C. (TABLE A).
5) APPLICANT SHALL CONTACT THE LOCAL FIRE DISTRICT FOR FIRE CODE REQUIREMENTS INCLUDING:
FIRE ALARM SYSTEM, FIRE EXTINGUISHERS & OTHER PERTINENT ITEMS. FINAL APPROVAL LETTER
FROM FIRE DISTRICT IS REQUIRED PRIOR TO FINAL BUILDING INSPECTION & CERTIFICATE OF
OCCUPANCY.
6) OPEN -HOLE SOILS REPORT REQUIRED AT FOOTING INSPECTION TO VERIFY SOIL BEARING CAPACITY
AND STRUCTURAL FILL REQUIREMENTS UNDER THE NEW CONCRETE FOUNDATION & SLAB AS PER
STRUCTURAL ENGINEER'S SPECIFICATIONS.
7) ALL HIGH -STRENGTH BOLTING AND FIELD WELDING REQUIRES SPECIAL INSPECTOR. PROVIDE
APPROVAL REPORT AT FRAMING INSPECTION.
8) EGRESS REQUIREMENTS PER 2015 I.B.C., CHAPTER 10. LOCKS, LATCHES & LANDINGS AT DOORS AS
PER SECTION 1010. VERIFY DIRECTIONAL EXIT SIGNS AND EMERGENCY LIGHTING LOCATIONS PRIOR
TO ELECTRICAL ROUGH -IN INSPECTION.
9) LIGHT, VENTILATION & TEMPERATURE CONTROLS PER 2015 I.B.C., CHAPTER 12.
10) RESTROOM FACILITIES ARE REQUIRED IN THIS BUILDING, INCLUDING A LAVATORY AND WATER
CLOSET. BUILDING INSPECTOR SHALL VERIFY INCLUSION OF RESTROOM FACILITIES AT EXISTING
STRUCTURE, AS DETAILED PLANS OF THE EXISTING BUILDING ARE NOT AVAILABLE IN BUILDING
DEPT. RECORD FILES.
11) ACCESSIBILTY REQUIREMENTS PER 2015 I.B.C., CHAPTER 11 AND I.C.C. A117.1- 2009. PROVIDE
ACCESSIBLE ROUTE FROM PARKING AREA TO ACCESSIBLE ENTRANCE INTO OFFICE, INCLUDING
LANDINGS, RAMP, RAILINGS, ETC.
12) ELECTRICAL REQUIREMENTS, PERMITTING & INSPECTIONS BY COLORADO STATE ELECTRICAL
BOARD. ELECTRICAL ROUGH -IN APPROVAL IS REQUIRED AT FRAME INSPECTION, AND FINAL
ELECTRICAL APPROVAL IS REQUIRED PRIOR TO FINAL BUILDING INSPECTION & CERTIFICATE
OF OCCUPANCY.