Loading...
HomeMy WebLinkAboutEngineer's Design 10.19.2020Paul R. Bryant, P.E. 2141 Troy Court Colorado Springs, CO 80918 Phone: 719.330.3885 E-Mail: paulrbryant p.e(cu.outlook.com J Job # FR20-520 19 October 2020 Foundation Repair of Western Colorado 2575 Highways 6 & 50 Grand Junction, CO 81501 Soil Evaluation and Structural Repair Plan for Cheri Brown 48 County Road 260 Silt, CO 81652 Paul R. Bryant, P.E. • Use of plastic sheeting in landscaped areas near the foundation is regarded by most experts as detrimental to the overall, long-term performance of foundations. We discourage its use as well. Backfill: Backfill, if any occurs as part of this project shall be performed accordingly: Backfill against foundation walls should not contain heavy, expansive clays, large rocks, organic materials, mud, ice or snow. Density of backfilled soil against foundation components should be 85% Standard Proctor density (ASTM D698) and soil supporting concrete slabs or other structural elements should be 95% density, at a minimum, and must be performed by mechanical means. Water flooding is prohibited. Conclusion and Limitations: This report is valid only for the address and the project scope listed, by the client listed above. The observations described in this document are valid for the date of the observation and have been made under the conditions noted in the report. Use by any other entity or for any other purpose is prohibited, without the express, written consent of the undersigned engineer. This report is based on published and anecdotal information; variations from the anticipated the soil profiles may be encountered; contact the engineer immediately if they are discovered. This report does not cover geological hazards, such as slope stability or landslide. Such investigations require extensive investigative techniques and are well outside the scope of this report. Should such information be desired, contact the engineer for guidance. This report does not express or imply any warranty of the future performance of the structure or drainage condition. This report should not be considered a warranty of condition, and no warranty is implied. The opinions and recommendations presented in this report are based solely on visual observations available for viewing at the time of the site visit and information, if any, provided by the Client and/or their representative(s). We are not responsible for conditions that were not within the scope of our services at the time of inspection. We did not undertake or perform any destructive or invasive testing. No additional subsurface testing, material testing, calculations, nor monitoring over time of the conditions presented in this report are included in this project, but may be obtained, if desired, under separate agreement. Not included in this site visit was a review of the architectural, mechanical, electrical, plumbing, cosmetic, landscaping, drainage or structural conditions, other than those items specifically discussed, nor a comprehensive review of compliance with applicable building codes. The work covered by this project is not held out as being a complete repair for all known or suspected structural or foundational issues within the building; its scope has been limited to that work described within this report with the full knowledge, understanding and cooperation of the homeowner and/or their designated representative. Other work may be justified or needed, but, work not included within this report is outside the scope of this repair project. If additional work is required at a future date, it will be under a separate contract. f efer to plan attachments Tor Garfield County Building Requirements and comprehensive list of Plan Review Notations. Condition of Permit: ENGINEER OF RECORD SHALL FIELD VERIFY INSTALLATION OF STRUCTURAL RESISTANCE DRIVEN PIERS AT UNDERPINNING OF EXISTING FOUNDATION/FOOTINGS. ENGINEER'S STAMPED APPROVAL REPORT IS REQUIRED FOR FINAL BUILDING INSPECTION. HOUSE APPROVED SUBJECT TO NOTED EXCEPTIONS & INSPECTIONS GARF ELD COUNTY BUILDINDEPARTMENT DATE 1I/I EY��(ArA(�._ FIELD COPY NO INSPECTION WITHOUT THESE PLANS ON SITE Page Of FA I R LA O.� SCALE: N.T.S ALL CONSTRUCTION 15 TO BE IN ACCORDANCE WITH THE 2015 IRS AND ANY LOCAL GODES THAT MAY APPLY Brown, Cheri BLRE-11-2O-6562 Foundation Repair C 48 CR 261:1, Rifle C.R. Commercial Properties Exemption, Lot I GRADING AND DRAINAGE IMPROVEMENTS MAY NOT BE PART OF THE CONTRACTED REPAIR WORK. THE CONTRACTOR I5 ENCOURAGED TO ENGAGE THE HOMEOWNER TO REMEDY THESE CONCERNS. SPEC, IAL I NSPEGT1ONS: (THEW ARE Rf5HiRI P OH ALL PER PRQ.£CTSJ CONTINUOUS PIER LOGGING OF ALL HELICAL AND PUSH PIERS 15 REQUIRED. INSTALLATION DATA SHALL BE RECORDED ON A STANDARD PIER INSTALLATION LOG PAGE. THIS INSTALLATION LOG SHALL BE MADE AVAILABLE TO THE CITY INSPECTOR UPON R5Qt 5T AND SHALL BE PRESENTED TO THE ENGINEER UPON COMPLETION OF THE JOB. REQUIRED ELEMENTS OF THE SPECIAL INSPECTION ARE DETERMINE}' BY THE IBC (2009 OR LATER) SECTION 1105.1, AND INCLUDE; 1, DATE, ADDRESS AND NAME OF CLIENT. 2. MANUFACTURER AND SIZE/SERIES OF PIERS USED IN PROJECT. 5. INSTALLATION TORQUE OR PRESSJRE FOR EACH SECTION OF PIER USED, RECORDED 1.1-Edi THAT SECTION HAS BEEN INSTALLED. A SEPARATE SHEET 15 REQUIRED FOR EACH DAYS WORK AND/OR EACH TYPE OF PIER USED. 4. FINAL DEPTH OF PIER, WITH FINAL TORGIE OR PRESSURE. 5. LOCATION OF EACH PIER RECORDED ON A BENCHMARKING SHEET, IN ORDER THAT EACH PIERS LOCATION CM BE DETERMINED AFTER THE FACT IF NEEDED. ..NO SPECIAL INSPECTIONS FOR WALL ANCHORS OR INTELIJAGKS ARE REQUIRED" ENGINEER'S STATEMENT THE REPAIR 15 INTENDED TO PROVIDE RELIEF OF MINOR STRESS FRACTURES IN THE CONCRETE FOUNDATION WALLS, TRANSVERSE AND MIGRATORY REFLECTION CRACKS IN MASONRY VENEER SYSTEMS MO SLOPING FLOCK SYSTEMS, AHD AS A PRT?VEXTATVE YEAWRE TO ENSURE CRACKS AND OT E'R DI3TRE55 THAT ARE PRG-SEIT DO NOT WORSEN. THIS PIERING AND/OR WALL BRACING PROJECT 15 NOT A GUARANTEE THAT FURTHER SETTLEMENT OR WALL CRACKING HILL NOT OCCUR IN OTHER PARTS OF THE HOUSE NOT INCLUDED IN TH15 FRO.EGT, OR THAT SETTLEMENT OR MOVEMENT OF UNREPAIRED PORTIONS WILL NOT RESULT IN ADDITIONAL CRACKING IN THE REPAIRED 5ECT/ONG PROPER GRADING AND DRAINAGE HILL HELP PROTECT THE REPAIR WORK FROM BECOMING A CONDUIT FOR MOISTURE INTRUSION TO THE DEEPER SOIL STRUCTURES REPAIRING A FOUNDATION SYSTEM IN A SUDDEN OR DRAMATIC FASHION USING TECHNIQUES LIKE HELICAL PIERS, PUSH-PIER-5, PRE5SIR5 SRGUTINS, OR OTHER QUICK -ACTING LEVELING METHODOLOGIES GAN HAVE ADVERSE EFFECTS, 9aGN AS EXTENSIVE INTERIOR FINIEN (DRYWALL,} DAMAGE, CRACKS IN TILE FLOORS, BLGKLING OR %EPARATION Cr MOP FLOORS, STICKING OR NONFUNCTIONAL DOOR AND WINDOW JAMBS, OR PERHAPS STRUCTURAL DAMAGE TO FLOOR AND/OR ROOF BEAMS FROM SUDDEN RE -STRESSING. PRPJEGT aESI6N HELICAL PIERS: NONE PUSH PIERS: (II) WALL ANCHORS: NONE WALL BRACES: NONE INTELLIJACKS: NONE TIER DEPTH WILL VARY. HELICAL PIERS SHALL BE INSTALLED TO 4000 FOOT-POUNDS TORQUE, CONTACT ENGINEER IF THIS TORQUE CAN'T BE ACHIEVED. PUSH PIERS SHALL BE INSTALLED TO 3,00 P51 MIN. OR CONTACT ENGINEER. HELICAL PIERS MAY BE 9U65TIT TED FOR PUSH PIERS WITHOUT CONSULTATION WITH THE ENGINEER, AT THE SAME SPACING. CHANGING FROM HELICAL TO PUSH PIERS REQUIRES CONSULTATION WITH THE ENGINEER, CODE DATA 7A, i, 2015 IRS/IBC 115 MPH WIND LOAD, EXP "G", 5-5EG GUST 50 PSF SNOW LOAD SEISMIC, B, FROST 56" FLOOR [ Ex 1 LRIOR DECK LOADS: DEAD: 10 P5F LIVE: 40 PSF • 'THESE PLANS ARE COPYRIGHTED 2020 ALL RIGHTS RESERVED. ANY SALE, REPRODUCTION, CREATION OF DERIVATIVE WORKS BASED ON THESE PLANS, OR USE OF T11505 PLANS FOR ANY PURPOSE WITHOUT PROPER COMPENSATION TO AND THE EXPRESS WRI 1 1 tN CONSENT OF DESIGNER 15 STRICTLY PROHIBITED. JOB#: 20-520 EPARED FOR: • PALL R. BRYANT, P.E. 2141 TROY COURT COLORADO SPRINGS, GO 8091E SHEET I OF 2 12I=OD, X ORB MILL I AK CO MrIC11 OLD MLEXPµ1131 NIX PLAN A E2DE OD. x O2M INML 1 161160N (PART Mm1 VAOZ) Ma 64 033E OD. x 0211 HALL PA ULLLES716 O.*AM 14EL0 AID U0 • war N6e1 VAITdP MLA RATE62 MAX RMEq 49' MITER balM SMWTs-Po • 6O W.F• 12 PM *510 -Ai .TOLAN• CO log MOT RAM- OA66TMDARD T EAMB 651716612 6•1OIR115 41112 *UPI OLFLAICMME - (2) - 41 61. GRAM 6 B0.T5 WIN WIS 7. ALL MEDOS TO Cr Il6000Ira50 C 11116.6121 LATETT lSfA[ R6TN EICI-TO1 P1R EECTROOL 6. 18I1( PATES PM! A 11161E6. 6' P ITCH 11111 LFAOOM MD TIMMSE60 RMIS MD l 141.6. Cur OP MOLLS_ 4. LH06 A/1 EXTEN5 01C ME AVAILABLE M 11T1MR PLAIN 611371. GR 1I0T-0IP 6ALVA6TED IN ACCORDANCE WTN A5TM A125. A •4' S A00ED TO TEED OF TIC PART NICER TO DERMATM PAR' A9IIOT-01P 6ALVANZED. 0. E4fr CGI•L6161WmMYE *5 pEartrzfro M ELgAROLIC P ANO P Af/4670440 WM A5TM eeb. 6. 115 Doc/BR 5 MMMM TO SERVE AS A GEE G DEEGRIP110N OP A STMDAPD HELICAL PLO LAYOR FOR 9E6IITAL RIB. 11E ATML I49.1X PLATS COFI6IRATOL (4V4E1E¢ Nb GIMIITY OP HELIX PLATE) PILL VARY OE1901N6 O1 TIE PRO.IOT SPEGPIO LOAD PEAMEB@OS AND SOIL FROPLE6 TYPIOM. I®1X RATE COIFl601671015 OT6.0E WPM OLE MD RIVE HELIX PLAT. MI6AL CGFNLRATIONS ALSO LEE 1121X PLATES OF E4106RIESIVELY INGEA9N6 DI MEIEI NTH TIE 6MMLWT DIATETEIE If= PLAT LOCATED GLOBES' TO 1TE FEE TIP. IEL1X 1•LAT9 ,NE TYPICALLY SPADED AT TI/6E HELIX 1266EIERS A5 SHAH, A. 14216N WW1.. SPAINS EE11@124 MD 56 181X 12166C1ERS GAN EE LOW 70 AVOID INIEdEFES6E PITH 7TE RLES GO.PLER1 AS`Pa*E FOR 66T1ARG IH1X RAT: COW16. ATION6 ARE ALSO AVML•ELE AD MLR! DETAILED MVILPATIRIN6 111611N65 PRE AVMLAELE LPOI RS9.BT. 6 x 60.64 4E6L YLV1 x WV LONG NUMITE OIvsM-2-0%-4&4 1�iva,rx-x�+ E xr0.64 Tray 19981 .1 QC115d_ kciP120) GRIP TITS—HEL'GAL PIER (Rr,S=815) I1 MINIT MAMMAL REG6RE45DS, ERAKET PHLFBII - A5111 AS6 EXTERNAL SLEET! - FFyy• 90 164 PU • 62 kx GP RATE - A5174 A6112 SPADE SD ERA6P2=T I6•06 11P E - (2) - 66i x 16' LONG GRADE 61- FL • 126 kY ALL-711•EAD ROD PUN NR6 06PTR-5210-2o75-16 k W6NLF0-019 O•IIONAL BRACKET ILMDWNE - (2)-¢% x16• LO61N51104- RI . 127kM CO111211 (COIL) 7PRA0 ROO PRN NUM OE GR-5170•Z-01S16 1 I41CI14-075) 2 A11H1XN6 TO BE M Frr+wAWE 1.111 AAE D11 LATEST 15ELE W1N E761IX Mw E EDINOCE 5. BRACKETS, GAS, MD SL.E5V15 AIRS AVAME A5 MINX RAN 51113- OR 1101-04F 6ALVM>ED R AOOROANCE P07N ASTM A05. A' 6 5 ADDEO TO TE ED Cr 71E PAW WEER TO CE516NA1E PART AS N771-0IP MLVM1 . 4. BRACKET IlARCIPA E 5 PROJIDED A6 E EGTRODN' RATED IN A.GOm1D1 WTI AVM 17616. 5. 7115 DOC11491 5 PEAT TO 51115E As A GEIER& O 155 IPTION FOR TC PRODUCTS SHOJI MR 9.EMT'AL RRPDEMS. MOPE DETAILED MWIFARWR6 CRAWS ARE AVAILABLE UPON MOLEST. BRACKET DETAIL PROJECT DETAIL I MG PUSH PIER (PF2 16P l 1-54) THESE PLANS ARE COPYRIGHTED 2020 ALL RIGHTS RESERVED. ANY SALE, REPRODUCTION, CREATION OF DERIVATIVE WORKS BASED ON THESE PLANS, OR USE OF THESE PLANS FOR ANY PURPOSE WITHOUT PROPER COMPENSATION TO AND THE EXPRESS WRITTEN CONSENT OF DESIGNERI5 STRICTLY PROHIBITED. JOB#: 20-520 PREPARED FOR: eIz - O li O 0 ILL (- 73 • O ® oo CZ < Q W ®coo Q� 4 � Q Z(1- ® 0 �-A� LL 0 0 PNI . 1- N z O Q 0 Z 0 U- PAUL R. BRYANT, P.E. 2141 TROY COURT COLORADO SPRINGS, CO 80118 SHEET 2 OF 2