HomeMy WebLinkAboutEngineer's Design 04.05.2020Paul R. Bryant, P.E.
2141 Troy Court
Colorado Springs, CO 80918
Phone: 719 330.3885
E-Mail: pibryant23 ooutlook.com
Job # 20-501
Foundation Repair of Western Colorado
2575 Highways 6 & 50
Grand Junction, CO 81501
Soil Evaluation
and
Structural Repair Plan
for
Jay Phillips
354 Sun King Drive
Glenwood Springs, CO 81601
5 April 2020
Paul R. Bryant, P.E.
Introduction: This report describes the results of an investigation of the soil conditions at
the above -listed address for the purpose of performing a foundation repair. It also presents
a repair design for the house, as well as provides additional guidance and information
relevant to the proposed project. Soil information was obtained from limited visual
observations on site, and from the resources of the NRCS Web Soil Survey. The Web Soil
Survey (WSS) provides soil data and information produced by the National Cooperative Soil
Survey. It is operated by the USDA Natural Resources Conservation Service (NRCS) and
provides access to the largest natural resource information system in the world. The site is
updated and maintained online as the single authoritative source of soil survey information.
It is considered accurate enough to predict with reasonable certainty the probable soil
conditions that will likely be relevant for this particular project.
Observation of Property: The foundation inspection was performed by a qualified
foundation inspector, as authorized by this office. The home is listed in county records as
having been built in about 1973; it consists of a one-story home with a walk -out basement.
The foundation appears to consist of cast -in -place concrete. For purposes of this report, the
front of the house is assumed to face north.
The damage to be mitigated by this limited repair project will be to address a condition of
settlement of the north and east sides of the home, which could exceed 2" in total. The
foundation walls do not appear to be severely cracked but cracking and distortion of
surfaces and finishes are present. Basement finishes and exterior coverings obscure a
direct view of most foundation surfaces.
Cause of Damage: It is our opinion the damage has resulted from inadequate foundation
design and construction, exacerbated by long-term settlement of the supporting soil.
Possible causes of structural settlement and/or excess lateral soil pressure usually arise
from elevated soil moisture conditions, often from poor drainage, damaged downspouts or
broken sprinkler lines; poor compaction, overly -dry soils or other adverse soil conditions can
be major contributing factors as well. Excess lateral stress, often from the same causes of
settlement, are often associated with foundation wall cracks.
Soil Profiles: The soil at this site consists of the Showalter-Morval complex. This soil
profile exists in sloping locations as alluvial fans and consists of linear horizons of loam,
stony & cobbly loams and a variety of clay loams, all derived from basaltic alluvium. While
typically stable in an undisturbed state, the loams with low percentages of stone and
cobbles tend towards instability in the presence of high soil moisture contents, while
creating high lateral soil pressures, due to high clay contents. Development work during
construction can leave pockets of poorly compacted soil, and backfill around foundations is
prone to settlement, creating conditions for water accumulation with ensuing foundation
problems. Typically well -drained, a shallow water table is not expected to be a factor, but
could exist seasonally if poor drainage exists at or near a structure. Depth to dense material
could exceed 20 feet, but local cobbles can interfere with installation of piers. Lateral
movement a short distance will often allow the obstruction to be bypassed.
Project Scope: This limited repair plan will involve the use of (10) IMG Model PP21617-34
push piers, located according to the design accompanying this letter. It is not expected that full
recovery of the house to as -built conditions or to a fully level, true and plumb state is achievable
or even desirable, as such work would likely result in more damage than would be repaired.
The underlying/surrounding soil is considered capable of providing long-term support for the
selected systems. Adjustment of installed components may occasionally be required after
installation and minor settlement or movement (less than 1 ") should not be considered a defect,
as post -construction adjustments are considered common and typical.
Construction and Materials Information: Seismic activity is not considered to be a significant
factor with respect to this project. Frost depth is considered as 36" for this project; check with
the Building Department if there is any question. All structural concrete shall be Type 2, Sulfate -
Resistant, of a strength specified by the accompanying design, or if not stated, 3,500 psi
compressive strength. Typically, slabs, such as basement floors and driveways, are not
considered structural. Below -grade steel shall be galvanized or coated with a heavy tar layer to
prevent excessive corrosion.
Unforeseen site conditions occasionally arise, often when buried obstacles are encountered.
Movement of any pier or brace laterally up to 12 inches is authorized; greater movement
requires contact with this engineer. Substitution of helical piers for push piers and vice versa is
authorized as long as original pier spacing and design capacity is maintained. Minimum
helical pier torque is 4,000 foot-pounds; minimum push pier installation pressure is 3,500
pounds prior to observable foundation lift. Deviations from minimum values require
consultation with the engineer. Interior basement pier installation may require use of a single
HSS 6"x6"x1/2"x8" steel spacer, or two HSS 4"x4"x3/8" x 8" spacers, side -by -side, to provide
clearance for the floor slab. Piers may be installed on the interior or exterior of the foundation,
with coordination and permission of the homeowner.
Subsurface Drainage: No new or additional subsurface drainage elements are required by this
document. If an existing drain is encountered, care must be exercised in preventing its damage,
and if damaged, it must be restored to an operational condition. Repairs to foundation drains
typically require inspection and approval by the Building Department. Groundwater is not
expected to be a significant consideration relative to this project; however, groundwater
elevations usually fluctuate seasonally, and mitigation of high groundwater is not within the
scope of this project.
Surface Drainage: Poor drainage is associated with many foundation problems. Property
owners and builders are cautioned that water accumulation around foundation elements is a
primary cause of structural and floor slab distress within homes. Foundation and slab
movement under virtually all conditions can be minimized by maintaining a stable moisture
content within the soil under and around the foundation. Subsequent to, and not included within
this project, the following guidelines are considered vital, as proper surface drainage is a crucial
part of a home's moisture defense system:
• The soil surface should be sloped away from the foundation at a minimum slope of one
foot in ten, for a minimum of ten feet along all sides of the structure. Areas of ponding
must be eliminated.
• Roof gutters should be employed, and all downspouts must discharge well away from the
foundation, either into a suitable drainage system or into a properly constructed drainage
swale.
• Landscaping requiring watering within five feet of the foundation should be eliminated, or
watered sparingly with drip systems.
• Use of plastic sheeting in landscaped areas near the foundation is regarded by most
experts as detrimental to the overall, long-term performance of foundations. We
discourage its use as well.
Backfill: Backfill, if any occurs as part of this project shall be performed accordingly: Backfill
against foundation walls should not contain heavy, expansive clays, large rocks, organic
materials, mud, ice or snow. Density of backfilled soil against foundation components should be
85% Standard Proctor density (ASTM D698) and soil supporting concrete slabs or other
structural elements should be 95% density, at a minimum, and must be performed by
mechanical means. Water flooding is prohibited.
Conclusion and Limitations: This report is valid only for the address and the project scope
listed, by the client listed above. The observations described in this document are valid for the
date of the observation and have been made under the conditions noted in the report. Use by
any other entity or for any other purpose is prohibited, without the express, written consent of
the undersigned engineer. This report is based on published and anecdotal information;
variations from the anticipated the soil profiles may be encountered; contact the engineer
immediately if they are discovered. This report does not cover geological hazards, such as
slope stability or landslide. Such investigations require extensive investigative techniques and
are well outside the scope of this report. Should such information be desired, contact the
engineer for guidance.
This report does riot express or imply any warranty of the future performance of the structure or
drainage condition. This report should not be considered a warranty of condition, and no
warranty is implied. The opinions and recommendations presented in this report are based
solely on visual observations available for viewing at the time of the site visit and information, if
any, provided by the Client and/or their representative(s). We are not responsible for conditions
that were not within the scope of our services at the time of inspection. We did not undertake or
perform any destructive or invasive testing. No additional subsurface testing, material testing,
calculations, nor monitoring over time of the conditions presented in this report are included in
this project, but may be obtained, if desired, under separate agreement.
Not included in this site visit was a review of the architectural, mechanical, electrical, plumbing,
cosmetic, landscaping, drainage or structural conditions, other than those items specifically
discussed, nor a comprehensive review of compliance with applicable building codes. The work
covered by this project is not held out as being a complete repair for all known or suspected
structural or foundational issues within the building; its scope has been limited to that work
described within this report with the full knowledge, understanding and cooperation of the
homeowner and/or their designated representative. Other work may be justified or needed, but,
work not included within this report is outside the scope of this repair project. If additional work
is required at a future date, it will be under a separate contract.
APPROVED
INSTALL (1) PUSH PIER AT
EACH CORNER OF CHIMNEY.
SUBJECT TO NOTE: D
EXCEPTIONS & INSPECTIONS
GARFIELD COUNTY
BUILD G DEPARTMENT
DATE 40 BY D
S'-0" MAX
• CORNERS
ELC COPY
NO INSPECTION WITHOUT
THESE PLANS ON SITE
Page Of
6'-0' MAX
V-0' MAX
MATS
6'-0" MAX
REFAIR LAYOUT
SCALE: N.T.S
ALL CONSTRUCTION 15 TO BE IN
ACCORDANCE WITH THE 2015 IRO AND
ANY LOCAL CODES THAT MAY APPLY
GRADING AND DRAINAGE IMPROVEMENTS MAY NOT
BE PART OF THE CONTRACTED REPAIR WORK. THE
CONTRACTOR 15 ENCOURAGED TO ENGAGE THE
HOMEOWNER TO REMEDY T1-1E5E CONCERNS.
Refer to plan attachments for
Garfield County
Building Requirements
and comprehensive list of
Plan Review Notations.
EN&INEER'5 STATEMENT
TTE R1'PAR S !DEWED TO PROVIDE FaIe OF MNOR STAG FRACTURES IN TFE
WEAVE FOUOATION PALLS, TR NSV9EY AND M6RATORY REFLFLTILN CRACKS N
MASC RY VEI!®R SYSTEM NO 5.0P916 FLOCK SYSTEM, ARD AS A PIEAENTATNE
FIFAEUE TO BELRE CRACKS AND ODER DISTRESSES THAT ARE PRIMER DO rim -
mono.
TNK MIMES ARIV R'RAU_ BRACK!. PROJECT !S NOT A. OU4tAtpff TFUT REEFER.
XTTLEER an 11,41 c7vrc.F M HILL NW cc TEE iH 0DR P: RR LP TY HOES PET
FEUDED IN TES PRO.ECT, OR TEAT'eRLEER OR MOVEMENT OF UEDI4RED
PORTIONS VC- NOT RES.1T N ALMON& GRAM* N THE REPAIFIED SECTIONS.
PROPER SRADVS NO DRAMS! MILL MP PROTECT TM WAR l'O K PROM
EEC EINS A CONDIT FOR MOISTURE IMTNSION TO DE DEEPER SOIL STRIGTLRES
REMICHE A PO/CATION SYNTE1 IN A WOVEN OR DRAMATIC FASHION ISMS
TECORZES LIKE FEUDAL PIRSIS, PU5f1-PIEFS,, RIB 6RDVNNS, OR ODER
GLICK-AGTIFN LEMURS FIRGDOL061E5 CAN NAVE ADM/EE BT5'TS, SUCH A6
EMTBMIVE INTERIOR FINSE (GRYl41) DAMASE CRACKS IN TILE FLOCKS, PUMAS OR
e'ARATIGN O' MOD FLOORS, STIAONS OR NbMLNCTIGNAL DOOR NO MICE JAMBS,
OR F emn 5TIECTURAL DAMM6E TO FLCICR ARV/OR ROOF SEAM FROM SAL:84
RE-STMEN6.
Ea1�O JEGY S I 4:5N raA1 A
HELICAL PIERS. NONE
PUSH PIERS: (10)
WALL ANCHORS, NONE
MAU_ BRACES, NOW
SMARTIAGKS, NONE
"PIER DEPTH WILL VARY J4EI.ICAL PIERS SHALL BE INSTALLED TO
4/000 FOOT-POUNDS TORQUE, CONTACT ENSINEER IF THI5TOROLE
GANT BE ACHIEVED. PUSH PIERS SHALL BE INSTALLED TO REFUSAL.
HELICAL PIERS MAY BE 5115.5TITUTED FOR PUSH PIERS WITHOUT
CONSULTATION WITH THE ENGINEER, AT THE SAME SPAGIN6. C.HANSIN6
FROM HELICAL TO PU5F1 PIERS REQUIRES CONSULTATION WITH TM
EN61NEER
2015 IRG/IBG
115 MPH WIND LOAD, EXP 'G', 5-SEC &UST
50 P5F &ROUND SNOW LOAD (UF TO ap00 FEET 1 6LBI600P 5PROS
i5 P5F (g000 FT), 100 PS' (I0,000 FT)
SEISMIC B, FROST 56'(UP TO 5,000 FT i SLEWOD SPRISD, 45'
ABOVE 6,000 FT
rj., EXTBOJOR OE0K LOADS..
DEAD. 10 P5F
LIVE. 40 P5F
THESE PLANS ARE GOPYRI6HTED
2020 AU. R OHM RESERVED.
ANY SALE, REPRODUCTION
CREATION OF DERIVATIVE
WORKS BASED ON THESE FLANS,
OR U5E OF THESE FLANS FOR
ANY PURPOSE WITHOUT PROPER
COMPENSATION TO AND THE
EXPRESS WRIr1EN CONSENT OF
DESIENER 15 STRICTLY
PROHIBITED,
J050: 20-501
z
rz g
,l_ A
ce
O- U1
zo a
zre 2ot� d
1.Q T-
PAUL R. BRYANT, P.E.
2141 TROY COURT
COLORADO SPRI1'465, GO eoala
SHEET I OF 2
ENGINEER OF RECORD SHALL FIELD VERIFY INSTALLATION OF STRUCTURAL RESISTANCE DRIVEN
PIERS AT UNDERPINNING OF EXISTING FOUNDATION/FOOTINGS. ENGINEER'S STAMPED APPROVAL
REPORT IS REQUIRED FOR FINAL BUILDING INSPECTION.
BLRE-08 20-6434
q7
ro
SA
0
C9
L
=1
itg
C
CA*J
L
J CV
L
co
C3. �
CO y
CO
CO CO
0 CO
LL C I
Wm 00=2 NU
"".A. - Pt. n"Ln•Ys.
MW RNMU1Ile
n Wow.
OrlD was
Anil a WoI IOW olive ITN
CO -1!H'
o am I uL12 AI1u11
1 ALL1MOR 10a M AKDMMR MU NO OI WOW
MIL MM OMMI MI MONIER
A MAI rum owe A twin momwo o
MAMMA el PAM2/22. WO NO Wm 1M11X OR M'MOM1M.
PYr OLL•Olr VAL 0111 -0! AGAIAVIICA NM MIN 413.
MAPIMK AV'r MID ID IUDtP M'AM11YOMAMR roOSIrYR
rift rim wpm MR PAR241.11.4.2012112
A T .I IlrMM:R r RMOrMILCII1m0
RAM MMLDRW101MMMIMrMA
RAI*
MN RAs*
A AM 0d9MRr HAFT 10 UM M AMONG
00[21221FI1r A SOW VA IOIYL Pl. IawT roe
MAMA IMlvs•. x2 MIX Alte 2127UOIAL2*02
WARM MOM rani t! NUN FLAW AU earn
OOP MVO MAT RiGLLMOrO11020.-5 AW
nLfRa Ia
n nPLATC 1tC Mr'Rl' TSMS aIMAN EWEN 21CW Mk MIA "MCA.
/C111sIMA11AO ROA'w1Y.YU was
MVtOMIN MRL{W OBI IKON 16ATM WWI.
Garda t0Ili nt 124021Vall}MAINLY MA=ao
M11RiH�e 4=0.42 �1K1r1AOML
M210RU MM1AASY IOIR OMMMmL
�LMOAOA>!r PALL IRIOOMMMIa MIME Mat. 01.0A/r2.M.2
WO MAW MA 0 RAOMIOM/iWr MAMM1AA NL
W MOW/ UMW /101L7•LtpiallYMN7RroNl�/rt,F'µ,�Rr
OM[1111rP.
GRIP TITS -HELICAL PIER (RnS2875)
MWMrMInfPr. AM1 AAA
MINA"MaN - et�n•nr
W1.22/2ly-�AI1IyNaNC w4l C
YAIHo!►1.1rr Y/Y egg/ r IVLIM
Mend. OW M111 mom
OI-�V UM Wrw-2.•22
waaW WY*
2.22I1204.0011 1 Hobos
1 ALL rumA. 10 AO0ooI12 MO NOM
1Msrre O7•I LIMN MI MOM
A MAMA OAAA NO AMID__YMKLN
Olio[ RAM Ira 011 WM, IALVir ■
MGORW 02 MI11 MM AO. A Y r KM 121M
MD mu MMr110 UMW MMM
We, 622/211219.
4 MMOa IMr21RS1AMOr M IMP=
MAW r AfOAO1YIM MM MI11 Ma
n sammak•RNr toO MMAMIMIAA
MAT* RR M n22IE9ogMIOAADm/i
NU RIAU=UM MAME
BRACKET Perm.
I MG PUSH PIER (PP216.17-34)
THEME PLAN. ARE COPYRIGHTED
2020 ALL RI6HT5 RESERVED.
ANY SALE, NZ P.CFAOTION,
CREATION OF DERIVATIVE
WORKS BASED ON THESE PLANS,
OR USE OF THESE PLANS FOR
ANY PURPOSE WITHOUT PROPER
GOMPRhSATION TO MD THE
E PRE55 WRITTEN GOFUBIT OF
DESI6HER 15 STRICTLY
PROHIBITED.
J0B4: 20-501
PAUL R. BRYANT, P.E.
2141 TROY COURT
GOLORADO SPRRKS, CO 50915
SHEET 2 OF 2