HomeMy WebLinkAboutOWTS DesignOnsite Wastewater Treatment System Design
4-Bedroom Residence
Lot 27, Callicotte Ranch
Garfield County, Colorado
I29 CAINS LANE
CARBoNDALE,CO A16'23
970.309.5259
cARLA.OSTBERG@GMAIL.COM
srrtr¡'r'r(' (:()1\St Yf -'t'r¡¡<i
June 1 9,2021 Project No. C1629
Edgar Cuc
Valenz Construction
c/o Jeff Johnson
ieff(O i iarch itectual. com
RECEIVED
iliiiì iÌ i: ;ri, j
üAhT}.IELD COUNTY
COMMUNITY DEVELOPMENT
Edgar,
CBO lnc. has completed an onsite wastewater treatment system (OffiS) design for the subject
residence. The 3.996-acre property is located outside of Carbondale, in an area where OWTSs are
necessary.
Legal Description: Section: 24 Township: 7 Range: 88 Subdivision: CALLICOTTE RANCH SUB-DIV Lot:
27 AMENDED#754313 3.997 ACERS
Parcel lD 2393-243-06-027
SITE CONDITIONS
The property is currently undeveloped. A 4-bedroom, single-family residence is proposed.
The property will be served potable water from a community water system. The water line will enter the
property from the subdivision road to the east. The water line will not come within 5-feet of any sewer
line, 1O-feet from the septic tank, and 2S-feet from the soil treatment area (STA)
The proposed STA location has an approximate ten percent slope to the southwest. The proposed area
vegetated with native grasses and sage.
There should be no traffic or staging of material over the future STA site to avoid compaction of soils
prior to construction of the STA.
Page2
SUBSURFACE
The subsurface was investigated by Kumar and Associates. Their report dated March 26,2021, Project 21-
7-231is enclosed.
We are proposing sizing of the STA based on Soil Type 2A based on our interpretation of the Kumar and
Associates report, including the gradation information provided and our experience with soils in the area.
The narrative under the heading Subsurface Conditions states ..."the soils encountered below about 1 to
1 Tzleel of topsoil, consisted of dense silty sandy gravel and basalt rocks with white sandy silt matrix and
to the maximum excavated depth of I feet." The mention of density leads us to go with the more
conservative sizing based on Soil Type 2A. A gradation of a sample taken from Profile Pil? at between
2.5' to 4'was 31% gravel, 48% sand, 19% silt, and2To clay.
A long term acceptance rate (LTAR) of 0.5 gallons per square foot will be used to design the
OWTS.
Page 3
DES¡GN SPECIFICATIONS
Desiqn Calculations:
Rverage Oes¡gn flow = 75 GPD x 2 people/bedroom x 3 Bedrooms + 75 GPD (4rh Bedroom) = 525 GPD
LTAR = 0.5 GPD/SF
525 GPD / 0.5 GPD/SF x 1.0 (gravity trenches) x 0.7 (chambers) = 735 SF
The OWTS design is based on 4-bedrooms. An average daily wastewater flow ol 525 GPD will be used
For the purposes of this OWTS design, Benchmark Elevation 100' has been identified at grade 6645.2'.
Finished Floor elevation has been identified as 101' 21l8'. CBO lnc. should be notified of any
discrepancies or problems with grade elevations of proposed components during installation of the
OWTS.
*Elevations are based upon standard OWTS installation practices Component elevations may change during
installation due to site conditions.
The 4-inch diameter SDR-35 sewer line exiting the residence must have a double-sweep clean out and a
minimum 2To grade to the septic tank.
The system installation must include a 1500-gallon, two-compartment poly lnfiltrator@ septic tank with an
effluent filter on the outlet tee. A concrete septic tank may be substituted, if desired. Risers must bring
the manhole lids to grade for access. lf more than one riser is added to the septic tank, an extension
handle must be installed on the effluent filter.
Effluent will gravity flow to a distribution box, and then to four gravelless chamber trenches. The
distribution box must be accessible from grade and must have flow equalizers, or similar product,
installed on each outlet pipe in the distribution box to assure equal flow to each trench.
Each trench will consist of 16'Quick 4' Standard Plus lnfiltrator@ chambers for a total of 768 square feet
of infiltrative area. There must be at least 4-feet of undisturbed soil between each trench. lnspection
ports must be installed at the beginning and end of each trench. Ports may be cut to grade and placed in
sprinkler boxes for access.
OWTS Gomponent Minimum Elevation
Primary Tank lnlet lnvert Approximate horizontal distance 60' / min. 2% fall
to septic tank / min. 15" fall
Distribution Box Approximate horizontal distance 8' / min. 1o/o fall to
d-box / min. 1" fall
lnfiltrative Surface Approximate horizontal distance 10' / min. 1% fall
to infiltrative surface / min. 1.25" to upper-most
trench
Page 4
COMPONENT SPECIFICAT¡ONS
The component manufacturers are typical of applications used by contractors and engineers in this area.
CBO lnc. must approve alternative components prior to installation of the OWTS. Requests must
be submitted, in writing, to our office for approval prior to installation. Component technical data
sheets are available upon request.
Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, the
OWTS Permit provided by Garfield County Building Department, and this design.
INSTALLATION GONTRACTOR
CBO lnc. expects that the installer be experienced and qualified to perform the scope of work outlined in this
design. The installer must review this design thoroughly and coordinate with our office in advance of
installation. Any additional conditions in this design or county permit must be completed and documented
prior to final approval of the OWTS installation. Communication between the installer and this office is
expected throughout the installation.
INSTALLATION OBSERVATIONS
CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before
backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing
siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours
in advance to observe the installation.
ln an effort to improve the accuracy of the record drawing, we request that the installer provide a
sketch of the installation, including path of the sewer lines, water line installation (if applicable),
septic tank location, STA location, and measurements from building corners or another fixed
objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design
Packet. Photographs of the installation and final cover are also requested to supplement our installation
documentation.
REVEGETATION REQUIREMENTS
An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire
disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing
characteristics (but without taproots), provides a maximum transpiration rate, and competes well with
successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over
the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented
and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation
cover.
COMPONENT IMANUFACTURER MODEL NO.IcoMMENTS
Septic Tank
llnfiltrator@
tM-1530-2CP 11 500-gallon, 2-compartment
loolv seotic tank
Biotube Effluent Filter
lorenco@
lFull Size Effluent Filter and
lhousinq
fank Risers and Lids
lorencoo
lDouble-walled PVC Risers and
llids
(2+" diameter)
Distribution Box
leotvt-ok
lDistribution box. flow
leoualizers. risers. lid
0hambers
llnfìltrator@
Standard Plus 164 'Quick 4' Standard Plus
lchambers
Page 5
OPERATION INFORMATION AND MAINTENANCE
The property owner shall be responsible for the operation and ma¡ntenance of each OWTS servicing the
property. The property owner is responsible for maintaining service contracts for manufactured units,
alternating STAs, and any other components needing maintenance.
Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials
should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during
construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing
fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a
running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA.
lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned
annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals be
flushed annually, or as needed.
The homeowner should pump the septic tank every two years, or as needed gauged by measurement of
solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not
be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener
should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS.
Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste
only.
ADDITIONAL CONSTRUCTION NOTES
lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of
freezing. The pump shall have an audible and visual alarm notification in the event of excessively high
water conditions and shall be connected to a control breaker separate from the high water alarm breaker
and from any other control system circuits. The pump system shall have a switch so the pump can be
manually operated.
Excavation equipment must not drive in excavation of the STA due to the potential to compact soil.
Extensions should be placed on all septic tank components to allow access to them from existing grade.
Backfill over the STA must be uniform and granular with no material greater than minus 3-inch.
LIMITS:
The design is based on information submitted. lf soil conditions encountered are different from conditions
described in report, CBO lnc, should be notified. All OWTS construction must be according to the county
regulations. Requirements not specified in this report must follow .aPPlicable county regulations. The
contractor should have documented and demonstrated knowledge of the requirements and regulations of
the county in which they are working. Licensing of Systems Contractors may be required by county
regulation.
Please call with questions.
Sincerely,
CBO lnc.
(p.,,[* ts+hmg
Carla Ostberg, MPH, REHS
IGIIi;ffihffifffiin,iiiå'*"
An Employec tl¡rncd Compony
5020 Courtly Roar.l 154
Glonrvood Springs, CO 81601
phone: (970) 945-7988
fax: (970) 945-8454
email: kaglenwood@kumarusa.com
www.kumarusa.com
Office Locations: Denver (HQ), Parkeq Colorado Springs, Fort Collins, Glenwood Springs, and Summit Comty, Colorado
March 26,2021
Edgar Cuc
1853 County Road 109
Glenwood Springs, Colorado 81601
valenzcuc@gmail.com
Project No.2l-7-231
Subject: Subsoil Study for Foundation Design, Proposed Residence, Lot27, Callicotte
Ranch, Callicotte Ranch Drive, Garfield County, Colorado
Dear Edgar:
As requested, Kumar & Associates, Inc. performed a subsoil study for design of foundations at
the subject site. The study was conducted in accordance with our agreement for geotechnical
engineering services to you dated March2,202l. The data obtained and our recommendations
based on the proposed construction and subsurface conditions encountered are presented in this
report.
Proposed Construction: The proposed residence is assumed to be a 1 and 2 story wood frame
structure with an attached garuge located on the site between Pits I and 2 shown on Figure 1.
Ground floor will be structural over crawlspace for the living area and slab-on-grade for the
garage. Cut depths are expected to range between about2 to 5 feet. Foundation loadings for this
type of construction are assumed to be relatively light and typical of the proposed type of
construction.
If building conditions or foundation loadings are signihcantly different from those described
aboveo we should be notified to re-evaluate the recommendations presented in this report.
Site Conditions: The subject site was vacant at the time of our field investigation. The ground
surface is variably sloping generally down to the weslsouthwest at grades between 5 and
20 percent. Vegetation consists of grass, weeds, sage brush and juniper and pinyon trees. Basalt
cobbles and boulders are scattered on the ground surface.
Subsident Potential: Bedrock of the Pennsylvanian age Eagle Valley Evaporite underlies the
site. These rocks are a sequence of gypsiferous shale, frne-grained sandstone and siltstone with
some massive beds of gypsum and limestone. There is a possibility that massive gypsum
deposits associated with the Eagle Valley Evaporite underlie portions of the lot. Dissolution of
the gypsum under certain conditions can cause sinkholes to develop and can produce areas of
localized subsidence. During previous work in the area, sinkholes have been observed scattered
throughout the lower Roaring Fork Valley. Thesc sinkholcs appcar similar to othcrs associatcd
with the Eagle Valley Evaporite in the area.
a
Sinkholes were not observed in the immediate area of the subject lot. No evidence of cavities
was encountered in the subsurface materials; however, the exploratory pits were relatively
shallow, for foundation design only. Based on our present knowledge of the subsurface
conditions at the site, it cannot be said for certain that sinkholes will not develop. The risk of
future ground subsidence on Lot 27 throughout the service life of the proposed residence, in our
opinion, is low; however, the owner should be made aware of the potential for sinkhole
development. If further investigation of possible cavities in the bedrock below the site is desired,
we should be contacted.
Subsurface Conditions: The subsurface conditions at the site were evaluated by excavating
2 exploratory pits in the building envelope and2 profile pits in possible septic areas at the
approximate locations shown on Figure l. The logs of the pits are presented on Figure 2. The
subsoils encountered, below about I to l% feet of topsoil, consist of dense silty sandy gravel and
basalt rocks with a white sandy silt matrix to the maximum excavated depth of 8 feet. The soils
were similar in both the excavated pits and the profile pits. Results of a gradation analysis
performed on samples (minus 3-inch fraction) obtained from the site are presented on Figures 3
and 4. No free water was observed in the pits at the time of excavation and the soils were
slightly moist to moist.
Foundation Recommendations: Considering the subsoil conditions encountered in the
exploratory pits and the nature of the proposed construction, we recommend spread footings
placed on the undisturbed natural subsoil designed for an allowable soil bearing pressure of
2,000 psf for support of the proposed residence. The soils tend to compress after wetting and
there could be some post-construction foundation settlement. Footings should be a minimum
width of 1 6 inches for continuous walls and 2 feet for columns. Loose and disturbed soils and
existing topsoil encountered at the foundation bearing level within the excavation should be
removed and the footing bearing level extended down to the undisturbed natural soils. Exterior
footings should be provided with adequate cover above their bearing elevations for frost
protection. Placement of footings at least 36 inches below the exterior grade is typically used in
this area. Continuous foundation walls should be reinforced top and bottom to span local
anomalies such as by assuming an unsupported length of at least l0 feet. Foundation walls
acting as retaining structures should be designed to resist alateral earth pressure based on an
equivalent fluid unit weight of at least 50 pcf for the on-site soil as backfill.
Floor Slabs: The natural on-site soils, exclusive of topsoil, are suitable to support lightly to
moderately loaded slab-on-grade construction. To reduce the effects of some differential
movement, floor slabs should be separated from all bearing walls and columns with expansion
joints which allow unrestrained vertical movement. Floor slab control joints should be used to
reduce damage due to shrinkage cracking. The requirements for joint spacing and slab
reinforcement should be established by the designer based on experience and the intended slab
Kumar & Associates, lnc. @ Project No. 21-7-23'l
-3-
Llse. A minimum 4 inch layer of free-draining gravel should be placed beneath basement level
slabs to facilitate drainage. This material should consist of minus 2-inch aggregate with less than
50% passing the No. 4 sieve and less than2Yo passing the No. 200 sieve.
All fill materials for support of floor slabs should be compacted to at least95Yo of maximum
standard Proctor density at a moisture content near optimum. Required fill can consist of the on-
site soils devoid of vegetation, topsoil and oversized rock.
Underdrain System: Although free water was not encountered during our exploration, it has
been our experience in the area that local perched groundwater can develop during times of
heavy precipitation or seasonal runoff. Frozen ground during spring runoffcan create a perched
condition. We recommend below-grade construction, such as retaining walls and crawlspace
areas, be protected from wetting and hydrostatic pressure buildup by an underdrain system.
The drains should consist of drainpipe placed in the bottom of the wall backfill surrounded above
the invert level with free-draining granular material. The drain should be placed at each level of
excavation and at least I foot below lowest adjacent finish grade and sloped at a minimum l%oto
a suitable gravity outlet. Free-draining granular material used in the underdrain system should
contain less than 2%o passing the No. 200 sieve, less than 50%o passing the No. 4 sieve and have a
maximum size of 2 inches. The drain gravel backfill should be at least l% feet deep.
Surface I)rainage: The following drainage precautions should be observed during construction
and maintained at all times afler the residence has been completetl:
1) Inundation ofthe foundation excavations and underslab areas should be avoided
during construction.
2) Exterior backfill should be adjusted to near optimum moisture and compacted to
at least 95%o of the maximum standard Proctor density in pavement and slab areas
and to at least 90% of the maximum standard Proctor density in landscape areas.
Free-draining wall backfill should be capped with about 2 feet of the on-site, finer
graded soils to reduce surface water infiltration.
3) The ground surface surrounding the exterior of the building should be sloped to
drain away from the foundation in all directions. We recommend a minimum
slope of 12 inches in the fìrst l0 feet in unpaved areas and a minimum slope of
3 inches in the first l0 feet in pavement and walkway areas.
4) Roof downspouts and drains should discharge well beyond the limits of all
backfill.
5) Landscaping which requires regular heavy irrigation should be located at least
5 feet from the building. Consideration should be given to the use of xeriscape to
limit potential wetting of soils below the foundation caused by inigation.
Kumar & Associates, lnc. @ Project No. 21-7-23'l
-4-
Limitations: This study has been conducted in accordance with generally accepted geotechnical
engineering principles and practices in this area at this time. We make no warranty either
express or implied. The conclusions and recommendations submitted in this report are based
upon the data obtained from the exploratory pits excavated at the locations indicated on Figure 1
and to the depths shown on Figure 2,the proposed type of construction, and our experience in
the area. Our services do not include determining the presence, prevention or possibility of mold
or other biological contaminants (MOBC) developing in the future. If the client is concerned
about MOBC, then a professional in this special field of practice should be consulted. Our
findings include interpolation and extrapolation of the subsurface conditions identified at the
exploratory pits and variations in the subsurface conditions may not become evident until
excavation is performed. If conditions encountered during construction appear different from
those described in this report, we should be notified at once so re-evaluation of the
recommendations may be made.
This report has been prepared for the exclusive use by our client for design purposes. We are not
responsible for technical interpretations by others of our information. As the project evolves, we
should provide continued consultation and field services during construction to review and
monitor the implementation of our recommendations, and to verify that the recommendations
have been appropriately interpreted. Significant design changes may require additional analysis
or modifications to the recommendations presented herein. We recommend on-site observation
of excavations and foundation bearing strata and testing of structural fill by a representative of
the geotechnical engineer.
If you have any questions or if we may be of further assistance, please let us know.
Respectfu lly Submitted,
Kumar & Associates, fnc.
}rr"rrt4- T. P*u<¿>¿n r'
James H. Parsons, P.E
Reviewed by:
Daniel E.
JHP/kac
attachments of Exploratory Pits
Figure 2 - Logs of Exploratory Pits
Figures 3 and 4 - Gradation Test Results
Table I - Summary of Laboratory Test Results
¡/:r \:*t
Kumar & Associates, lnc. @ Project No. 21-7-231
0
2
"+..i#i
-i \\.\
*
I
ffi
\\.,
\ùpj,\{¡l
IOT 27 I'irr,.1ìt,,
CALLICOTTE RANCH Î,,.
PROFII¡ PIT I
I
I
I
o
Ptl 2
riri-l
ìlAllq :l
1;!*
?
t=L
1'/
,!!i*
#
lì
t:
\.
\
I
V
o
SCALE-FEET
21 -7-231 Kumar & Associates LOCATIONS OF TXPLORATORY PITS Fig. 1
PIT 1
EL.=6638'
PtÍ 2
EL.=6642'
PROFILE PIT 1
EL.=6615'
PROFILE PIT 2
EL.=6638'
0 o
Fl¡l
t¡JtL
I
:EF(L
t¡Jo
WC= 1 0,6- *4=28
-2OO=34
-, WC= 10.4
' -2OO=57
WC=8.8I GRAVEL=31
I st¡to=¿e- SILT= 1 9
CLAY=2
t-LJ
TJt!
I-t-fL
LJê
5 5
10 10
LEGEND
TOPSOIL: SILT, SANDY, COBBLES AND B0ULDERS, ORGANICS, FIRM, MOIST,
BROWN TO DARK BROWN.
BASALT GRAVEL (GM-GC): COBBLES, BOULDERS lN A SILTY SAND MATRIX,
DENSE, SLIGHTLY MOIST, LIGHT BROWN TO BROWN.
t
I
DISTURBED BULK SAMPLE
PRACTICAL AUGER REFUSAL.
NOTES
1. THE EXPLORATORY PITS WERE EXCAVATED WITH AN EXCAVATOR ON MARCH 3, 2021
2. THE LOCATIONS OF THE EXPLORATORY PITS WERE MEASURED APPROXIMATELY BY PACING FROM
FEATURES SHOWN ON THE SITE PLAN PROVIDED.
3. THE ELEVATIONS OF THE EXPLORATORY PITS WERE OBTAINED BY INTERPOLATION BETWEEN
CONTOURS ON THE SITE PLAN PROVIDED.
4. THE EXPLORATORY PIT LOCATIONS SHOULD BE CONSIDERED ACCURATE ONLY TO THE DEGREE
IMPLIED BY THE METHOD USED.
5. THE LINES BETWEEN MATERIALS SHOWN ON THE EXPLORATORY PIT LOGS REPRESENT THE
APPROXIMATE BOUNDARIES BETWEEN MATERIAL TYPES AND THE TRANSITIONS MAY BE GRADUAL.
6. GROUNDWATER WAS NOT ENCOUNTERED IN THE PITS AT THE TIME OF EXCAVATION
7. LABORATORY TEST RESULTS:
WC = WATER CONTENT (%) (ASTM D 2216);
+4 = PERCENTAGE RETAINED ON NO. 4 SIEVE (¡STU O ¿ZZ);
-2OO= PERCENTAGE PASSING NO. 2OO SIEVE (ASTM D 1140);
GRAVEL= PERCENTAGE RETAINED ON NO. 10;
SAND = PERCENTAGE PASSING N0.10 SIEVE AND RETAINED ON N0.325;
SILT = PERCENTAGE PASSING NO. 325 SIEVE TO PARTICLE SIZE .O02MM;
CLAY = PERCENTAGE SMALLER THAN PARTICLE SIZE .002MM;
21 -7 -231 Kumar & Associates LOGS OF EXPLORATORY PITS Fig. 2
=
I
too
30
ao
70
a0
50
40
30
20
to
ö
to
20
30
40
50
60
70
ao
90
=
o loo
.o0r .125 2.O
DIAMETER OF PARTICLES IN MILLIMETERS
152
CLAY TO SILT COBBLES
GRAVEL 2A % SAND
LIQUID LIMIÏ
SAMPLE 0F: Silly Sond wilh Grovel
38%
PLASTICITY INDEX
SILT AND CLAY 31 %
FROM:Pît1O4.5'-5'
lhrs. l.st rôsulls opply ohly lo th.
soñplô! which *crc loslod. lhol.sllñg r.porl shôll nol b. rcproduccd,
êxcêpt lñ full, vllhoul lha vrlil€n
opprovol of Kumor & Assoclol.s, lnc.
Sl.v6 onolyll! l.lllng l. p6rfom.d ln
occordonc. wlth ASTM 06913, ASTM D7928,
ÀSTM Cl36 ond,/or ASTM Dll40.
HYDROMETER ANALYSIS
HRS 7 HRS
SIEVE ANALYSIS
6tl
I I af_tl-.'.......--
--
rl
:l_*-: -{-- -l l
.,-l]--rl-
I
,ltl----+
_J_
I
--_I
I
-T'---_l'
-i
+
=+--f-.---f -i -]-
Êt
._.-J t -r]-
--_l-.-1=
SANO GRAVEL
FINE MEDTUM ICOARSE FINE COARSE
21 -7 -231 Kumar & Associates GRADATION TTST RESULTS Fig. 3
SIEVE ANALYSISHYDROMETER ANALYSIS
24
045
7HR 1 MIN,
#325
U,S. STANDARD SERIES
#140 +60 #35 #1A #10
CLEAR SQ
3/8', 314',4 MIN.#4 1 112',5"6" A
100
10 90
20 80
30 70
ô
l-¡Jz.
FLIt
Fz.tdOÉLJ
o_
40 60
Oz
U)
U)
o_
Fz.
L¡J(-)É
LJ
o_
50
60 40
70 30
80 20
90 10
100 0.001 .002 .005 .009 .019 .045 106 .025 .500 1,00 2.00 4_7s 9.5 19.0 37.5 76.2 152 203
DIAMETER OF PARTICLES IN MILLIMETERS
CLAY COBBLES
GRAVEL 31 %SAND 48 %SILT 19 %CLAY 2 %
USDA SOIL TYPE: Gravelly Loamy Sand FROM: Profile Pit 2 @ 2.5'Ío 4'
_4-
-l-
-t
MFDIIM I ARGESILT
21-t-231 Kumar & Associates GRADATION TEST RTSULTS 7ig. 4
IC'TKumr & Associates, lnc.6Geotechnical and Materials Engineersand Environmental ScientistsTABLE 1SUMMARY OF LABORATORY TEST RESULTSNo.21-7-231SOIL TYPESihy* Sand and GravelVery Silty Sand andGrarrelGrar.elly Loamy SandCLAY(/"1SILT$l(%)SAND2t948USÐA SOIL TEXTURE(o/"1GRAVEL31SILT&CLAYl"/"13457SAND("1"138GRADATIONGRAVELV"l28NATURALDRYDENSI'ÍY(pcrlNATURALMO¡STURECONTENT$t10.6r0.48.8DEPTH(ft)4%- sI3-42%- 4SAMPLE LOCATIONPIT24
CBO lnc.'129 Ca¡ns LaneCarbondale, Colomdo 81623Phone 970-309.5259cada.ostberg@gma¡l.comNII\\SCALE: 1 = 50'=0")ILOCATION OF PROPOSED IMPROVEMENTS SHOWN ARENOT THE RESULT OF A PROPERTY SURVËY. IHE LOCATIONSARE APPROXIIVATE. ¡T IS THE HOIMEOWNERS' DUTY TOENSURE ALL CONSTRUCTION AND II\4PROVEMENT LOCATIONSARE ACCURATE. PROPERTY LINES AND SETBACK DISTANCESSHOULD BE CONFIRMED PRIOR TO EXCAVAIION. SCALEDFOR PRINTING ON 1 1' X 17' PAPER.jriïrËsr*Valenz ConstructionLot 27, Call¡ætte RanchGarf¡eld County, ColoradoPrciectNumben C1629Date: 06/19/2021Designedby: CBODDDrawnby:w1 .0Sheet 1 0F 4
\\:BO lnc.læ Ca¡ns Lanelarbondale, ColoEdo 8'1623rhone 970.309.5259:ãla.ostberg@gma¡1.æmooValenz ConstructionLot 27, CalliætÞ RanchGarfeld County, ColoradoProiect Number C1629Date: 0611912021DrawnDes¡gnedby:by: CBODDSheei 2 0F 4w2.0II\\\\LXIIII1\\\,\a,ì-It_rII¿'D!{ SDR-35 SEWER LINE TO EACH TRENCH(vtN. 17c SLOPE TO TRENCH)at--I'¡\\uffihN= ,ìx,,,,,L-(1 50O-GALLON, TWO.COMPARTMENT('tot'21;'SEPTIC TANK WITH EFFLUENT SCREEN'-ì'.\-iNW)'.,\ 4'DlA SDR-35 SEWER PIPE WlrH DOUBLE SWEEPPROPOSED4-BEDROOM, RESIDENCEIII\-l'I\t_/-lvllN 2% FALL TO TANK)I\IIÐkT\//\_l)\/(\\\\ta\\\II'1""\, ,",/,{\LINE4' DIA SDR-35 INSPECTION PORT ATBEGINNING AI\¡D END OF EACH TRENCH - \ \\\\\\--ì\,OUICK-4' CHAMBER TRENCHES4 TRENCHES WITH TO CHNMECRS PER TRENCHFOR A TOTAL OF 64 CHAMBERS AND 768 SF.\\DISTRIBUTION BOXWITH ACCESS AT GRADE\4'DIA SDR-35 PVC SEWERBM 100'1% FALL TO D-BOX)\¡ ¡ (664s.2')\'../ORIVEWAYNSCALE: 1" = 2010"--
CBO lnc-129 Cains LaneCarbondale, ColoEdo 81623Phone 970.309.5259carla.ostberg@gmail.æm15 CHAMBERS PERMENCH-¿II-INFILTMTOR,/ eno eureGMVELLESS 'QUICK4'CHAMBER (4'x 3)4" DTASDR-35 SÊWERLINE TO ACH TRENCH(MrN. 1% SLOPÉ TOTæNCH)4" DIA SDR.35EFFLUENT PIPE FROMNOTE: MAINTAIN SHALLoWINSTALßTION BETWEEN 2'AND 3'DISTRIBUTION BOXWITHDIA SDR.35AT GMDEIINSPECTIONPORIPUCEÐ INTOP PORTOFCHAMBER ENDPUTÉS4'rsolL_lLIMITEXCAVATION'outcK4'SCARIFYCHAMBER (4'x3')OIASDR.35 INSPÉCTION/^CHAMBER'IRENCH SECT|ON\yPORT AT BEGINNING NDEND ÕF EACH TRÊNCHA CHAMBER 1RENCH PLAN\r,--ffiFINISHED GRADESMALL VALVE COVERBOXOR IRRIGATIONVALVE BOX AT GWESLIP.ON PVCDO NOT GLUECAP ORTHREÆED24'MtN.CLEANOUT ASSEMBLYINSULATÊDTRACER WIREFINISHED GRADEBASE TO SUPPOffiBOXPVC PIPE CUTTO4" DIA4" DIA SDR-35 SEWER LINE(t\,ilN 2% SLOPE TO TANK,i,IN. 1% TO STA)FTSEWER LINESCREENEDUSE HOLE SAWTOCUT THRU TOPOFOR SAND FORBEDOING3" MtN.ENDTO TANK8'MIN-/ãINSPECTION PORÌ DETAIL\9t-æ^CLËAN OUT DETAIL\9t----æ/ã1RENCH DETAIL\:/,-.rcValenz Construction06t't9t2021Lot 27, Callicotte RanchGarf¡eld County, ColoradoProjectNumber: C1629by: CBOby: DDw3.0Sheet 3 0F 4
CBO lnc.129 Cains LaneCarbondale, CdoEdo 81623Phone 970.309.5259ærla.ostberg@gmail.æmD:SIGN4-BEDROOM RESIT¡CNCE75 GPD X 2 PERSONS/BEDROON4 X 3 BEDROOMS + 75 GPD (4th SEDROOM)\,\'ASTEWATER FLOW = 525 GPDTANK:IilIN.1250 GALLONSUSE 1 sOO-GALLON, TWO-COMPARTIVENT POLY SEPTIC TANKSOIL TREATMENT AREA (STA):LONG TERIII ACCEPTANCE RATE (LTAR) = 0.5 GALi SFCALCULATED SfA = CüLTAR = 525 / 0.5 = 1050 SFGRAVITY, TRENCHES = 1050 SF X 1.0 = 1050 SFCIAMBERS = '1050 SF XO.7 =735 SF I 12 SF / CHAMBER = 62 CHAIIIBERSFCUR GRAVELLESS CHAMBER TRENCHES16 'OUICK 4' CHAMEERS IN EACH TRENCHTOTAL 6¿ 'QUICK 4' CHAMBERSBOX AND COVER BROUGHT TO GRADÊCONCRÉÎE LIDFINSHEDGRADEBAFFLE ORANGLED PIPETO BE USEDAT INLETADISIRIBUTION BOX DETAIL\r,-HOUSÊ TO SEPTIC TANKSTA TO HOUSESTÀTO WATER COURSEN/AI 50'STA TO WELLN/AI too'20'50'N/ASEPT|C-ANKTOWATERCOURSE, 50'SEPTIC -ANK TO WELLN/Aì so'MINIMUIV REQUIREDSFTRAEKOWTS COMPONENTS ANDfHYSCAI FFATIIRFSAPPROXIMATE PROPOSEDSFTRACKOUTLETS[:ooooValenz GonstructionLot 27, Call¡ætte Ranc*ìGarfield County, ColcradoPrciect Number: C1629Dale: 0611912021Des¡gnedby: CBODDDramby:w4.0Sheet 4 0F 4
GD qPublic.tËt* Garfield County, CO
81623
2019Total Actual
Value
Overview
Legend
f] Parcels
Roads
Parcel/Account
Numbers
Highways
æ Limited Access
- Highway
' ' Major Road
' Local Road
'' Minor Road
Other Road
Ramp
** Ferry
Pedestrian Way
Owner Name
å'l Lakes&Rivers
- CountyBoundary
Line
$180,000 Last2Sales
Date Price
3/5/2021 $O
3/s/202t $237,500
Account R044200 Physical 0 103COUNTY RD
Number Address
Parcel 239324306027 CARBONDALE
Number OwnerAddress VALENZUELA¡KEILA
Acres 4 185SCOUNryROAD 109
Land SqFt 0 GLENWOOD SPRINGS CO
TaxArea OII 81601
2019Mill Levy 75.5380
D ate cr e ated: 6/23/ 2O2t
Last Data Uploaded: 6/23/2027 2:38:52 AM
Deverooed bv f I $:ltEp¡dçf
6qPuHic.net'" Garfield County, CO
Summary
Account
Parcel
Property
Address
Legal
Descrlptlon
Acres
Land SqFt
TaxArea
MlllLevy
subdlvls¡on
@u
Owner
PURPLE CACTUS LLC
2ó7ó WEST LONG PLACE
LITTLETON CO 80120
Land
Unit Type VACANT REs LoTs - oroo lVncnlr UÑO¡
Square Feet 0
Actual Values
Assessed Yeâr
Land Actual
lmprovement Actual
Totål Actuel
Assessed Values
Assessed Year
Land Assessed
lmprovement Assessed
Total Assessed
Tax History
R044200
239324306027
O 103 COUNTY RD, CARBONDALE, CO 8T623
Section: 24Township: 7 Range: 88 Subdivlsion: CALLICOTTE RANCH
SUB-DlV Lot: 27 AMENDED #754313
3.996
0
IT
75.5380
CALLICOTTE RANCH SUB-DIV
2019
$3,315.08
20L8
$2,8s7.r2
2020
$1s0,000.00
$o.oo
$15o,ooo.oo
2020
$43,500.00
$o.oo
$43,s00.0o
2017
$2,725.s2
2079
$15O,OOO.OO
$o.oo
$1s0,000.00
2019
$43,500.00
$o.oo
$43,500.00
2016
$3,430.1ó
Click here to view the tax information for this parcel on the Garfield Countv l€asurer's website.
Transfers
TãxYeär
Taxes Bîlled
Sale Date
7/26/20t7
Reception Book
Number - Page
895251
Grantee
PURPLE CACTUS LLC
Deed Type
SPECIAL
WARRANry
DEED
STATEMENTOF
AUTHORIry
2020
$3,2s5.92
SalePrice Grantor
$242,OOO BOKF-DBA
7/25/20L7 895250 $O THEOBALD,TOM PURPLECACTUSLLC
tt/8t2072 PUBLIC
TRUsTEES DEED
ro/24/20L2 PUBLIC
TRUSTEES CERT
5/25/2072
6/78/2007
5tt4t2007
5/14/2007
5/ttl2007
s/71-/2007
s/7/2007
5/5/2007
5t4t2007
NOTICE
826802
825977
a79691
730012
723324
723322
723325
723323
723763
723764
723762
70a964
665072
663346
ó583ó0
644162
63!397
ó31395
637399
628047
628046
625568
63t394
6273LO
ó318ó0
622244
608456
588887
589763
577935
577934
$o
$o
$o
$o
$o
$o
$4,500,000
$O PUBLICTRUSTEE-
GARFIELD
COUNTY
$7.324,235 CALLICOTTE
RANCH LLC
BOKF NA DBA BK OF OKLAHOMASCCR IN INTTO BK OF OKLAHOMA&
BOKF DBACOLORADO BK &TRUSTSCCR IN INTTO COLORADO ST BK
ÏRUST
BOKF NA DBA BK OF OKLAHOMA SCCR IN INT TO BK OF OKLAHOMA &
BOKF DBACOLORADO BK &TRUSTSCCR IN INTTO COLORADO ST BK
TRUsT
PUBLIC TRUSTEE-GARFIELD COUNTY
BOCC OF GARFIELD COUNTY
CALLICOTTE RANCH OWNERS ASSOCIATION
CALLICOTTE RANCH, LLC.
MINETREE, THOMAS A
ROCKY MOUNTAIN MANSIONS III, LLC
SMILACK, STEPHEN & PHYLLIS
SMILACK, STEPHEN & PHYLLIS
MINETREE, THOMAS A
BOARD OF COUNTY COMMISSIONERS
ROCKY MOUNTAIN MANSIONS III, LLC
ROCKY MOUNTAIN MANSIONS III, LLC
DECLARATION
QUITCLAIM
DEED
AGREEMENT
SPECIAL
WARRANTY
DEED
BARGAIN AND
SALE DEED
STATE|'\4ENT OF
AUTHORITY
AGREEMENT
EAsEl.,lENT CALLICOTTE
RANCH, LLC.
CALLICOTTE
RANCH, LLC.
CALLICOTTE
RANCH, LLC,
CALLICOTTE
RANCH, LLC.
ROCKY
MOUNTAIN
MANSIONs III, LLC
CALLICOTTE
RANCH, LLC.
ROCKY
MOUNTAIN
MANsIONS III, LLC
$o RocKY
MOUNTAIN
MANSIONS III, LLC
$O MINETREE,
THOMA5 A
$o RocKY
MOUNTAIN
MANSIONS III, LLC
$O ROCKY
MOUNTAIN
MANSIONS III, LLC
$O ROCKY
MOUNTAIN
MANSIONS III, LLC
$o
CALLICOTTE
RANCH, LLC
$O ROCKY
MOUNTAIN
MANSIONS III, LLC
t?26-
679
1926-
627
L926-
ó85
7926-
665
t925-
906
1925-
910
t92s-
905
1853-
t
7647-
407
9/25/2006
9/24/2004
9t2412004
2/2/2004
72/77/2003
6124/2003
6/24/2003
6/23/2003
5/23/2003
5/23/2003
4/16/2003
3/t7/2003
2/27/20,03
2/14/2003
POWER OF
ATTORNEY
BOUNDARY
LINE
ADJUSTN4ENT
BOUNDARY
LINE
ADJUSTN4ENT
RESOLUTION
BOUNDARY
LINE
ADJUSTMENT
BOUNDARY
LINE
ADJUSTMENT
QUIT CLAIM
DEED
QUITCLAIM
DEED
AGREEMENT
BOUNDARY
LINE
ADJUSTN4ENT
AFFIDAVIT
LIS PENDENs
QUIT CLAIM
DEED
7639-
L6t5-
7552-
r497-
510
82
JöO
66
1460-
4t2
t49t-
59
1469-
ó88
7493-
643
1443-
7t2
$o
$o
$o
$o
$o
$o
$o
$o
$o
$o
$o
$o
t49t-
61
1-491-
73
1,473-
257
254
QUIT CLAIM
DEED
r7/22t20o2 QUITCLAIM
DEED
8/6/2002
9/24/2007
9/4/2007
3/12/2007
3/8/200I
LIS PENDENS
RESOLUTION
RESOLUTION
QUITCLAIM
$o
$7,642,600
$o
CALLICOTTE,
5TEPHEN H.
CALLICOTTE,
STEPHEN H.
!376-
tL7
t289-
10
DEED
PERSONAL REP
DEED
7292-
819
7239-
77
!239-
73
3/A/2001
8/U2000
7/S/2000
).1/Ut999
lt7t1900
1/rltgoo
tlrl1900
uu7900
7/U7900
Ltltt900
DEED
QUITCLAIM
DEED
BOUNDARY
LINE
ADJUSTMENT
LETTERS
Deeds
Deeds
Deeds
Deeds
Deeds
Deeds
i¿lJJÂ'ï
570340
570339
577932
t239-
12rt-
1217-
7t
58
55
$o
$o
$o
$o
$o
$o
$o
$o
$o
$o
CALLICOTTE,
STEPHEN H.
CALLICOTTE,
STEPHEN H.
ROCKY MOUNTAIN MANsIONS III, LLC
ROCKY MOUNTAIN MANSIONS III, LLC1239-
70
497-
LT?
468-
455
457-
103
423-
468
354-
L78
0457-
0105
Photos
No data avallableforthe followlng modules: Buildings, Sketches.
Tbe C¡rficld County Asse:sor's OfÍ.:e nrake: rr;e¡y elforl tc produc.e tho rnôsi ;.curâie ¡1r,'ormuticn possible. Nc utarr:rrrties, exptessed or
r.\rtnJl I | 8.rJrJr,lucrJ.
User Privacy Policy
GDPR Privacv Notice
Last Datallpjcadig52q2l;¡95?f}rvl Version 2.3.10e
Developccl by
Cr*åE#r