Notice of Boiler lnspection Deficiencies
August 16,2021
DMeerschaert@ gtenwoodcaverns. com
GLENWOOD CAVERNS HOLDINGS LLC
51OOO TWO RIVERS PLAZA RD
cLENWOOD SPRTNGS CO 81601-2809
RE: Boiler lnspection Deficiency lssues
Boiter inspections were conducted, as required by the Division of Oit and Pubtic Safety (OPS), at the
subject facitities tisted below. During the inspection, the fol[owing items were found to be out of
compliance with the laws and regulations promutgated under Cotorado Revised Statutes, Title 8,
Articte 20, and Titte 9, Articte 4. Faiture to correct the violation(s) may lead to criminal and civit
penatties not to exceed one thousand dollars per violation, for each day of violation.
Ptease comptete the repairs in accordance with the inspector's requirements listed betow. An
extension may be requested by contacting the inspector or the OPS office at the number listed in the
header above.
Property: Glenwood Caverns Adventure Park, 51000 Two Rivers Ptaza Rd, Glenwood Facitity tD:2790397
lnspector: Wade Distet (State of Cotorado) Emait: wade.distel@state.co.us Phone: 970-712-7458
Jurisdiction #:CO118748 - lnspection Date:61312021 - Location: Smoke House Upstairs
Deficiency #1:510C - INCORRECT SAFETY RELIEF VALVE INSTALLATION - The Safety-Retief Vatve has been
incorrectly instatted in wrong location or with spindte in other than a vertical position
Required Action: Reinstalt the Safety-Retief Valve as per ASME code. (HG-70f , HLW-801 .2 or Pg-71).
Repairs Due By: 81112021
Deficiency #2:810 - REMOTE SAFETY SWITCH REQUIRED - A manually operated remote shutdown switch must
be instatled just outside the boiler room and marked for easy identification
Required Action: This emergency shutdown switch or circuit breaker must disconnect all power to the burner
controts. This requirement is per CSD-1, CE-110(a).
Repairs Due By: 811 12021
Jurisdiction #: CO118749 - lnspection Datez 6131202l - Location: Smoke House Upstairs
Deficiency #1: 510C - INCORRECT SAFETY RELIEF VALVE INSTALLATION - The Safety-Retief Valve has been
incorrectty instalted in wrong location or with spindte in other than a vertical position
Required Action: Reinstall the Safety-Retief Valve as per ASME code. (HG-701, HLW-801 .2 or Pg-711.
Repairs Due By: 811 12021
Deficiency #2:810 - REMOTE SAFETY SWITCH REQUIRED - A manuatty operated remote shutdown switch must
be instatted just outside the boiter room and marked for easy identification
Required Action: This emergency shutdown switch or circuit breaker must disconnect atl power to the burner
controts. This requirement is per CSD-1, CE-110(a).
Repairs Due By: 811 12021
RP tD: ó147483 - cLENWOOD CAVERNS HOLDINGS LLC,2nd Notice of Deficiencies, August 16,2021
re@t COLORADO
Dtvtdon of Otl and hrbltc Saftty
Dr¡rarlrrurlt uf tdlÀi ¿rl1l Ërrtp*:ryrïraítl
Division of Oi[ and Public Safety - Boiler Program
ó33 17th Street, Suite 500
Denver, CO 80202-3ó10
Jû1.318-8484 I cdle botler(4state,co,us
www. cotorado.gov/ops
Notice of Boiler lnspection Deficiencies
Property: Glenwood Caverns Adventure Park, 51000 Two Rivers Ptaza Rd, Glenwood I Facitity tD:2790397
lnspector: Wade Distel (State of Colorado) Emait: wade.distet@state.co.us Phone: 970-712-7458
CERTI FICATION STATEMENT:
I CERTIFY that the above listed violation(s) identified at Glenwood Caverns Adventure Park, 51000
Two Rivers Plaza Rd, Glenwood Springs, CO, has/have been corrected per the listed required
action(s):
Printed:
Boiler Owner or Responsible Party Representing
Signed Date:
Boiler Owner or Responsible Party
Please return this signed report via email or US Mai[, using the email address or mailing address
listed in the header above.
An inspection certificate witl be issued upon notification, by return of this signed report, that the
boiter has been brought into comptiance and the invoice has been paid. Operation of this boiler
without a vatid inspection certificate is untawfut. Your prompt attention to this matter is required.
RP lD: ó147483 - GLENWOOD CAVERNS HOLDINGS LLC, znd Notice of Deficiencies, August ló, 2021