Loading...
HomeMy WebLinkAboutNotice of Boiler Inspection Deficienciesre@t coroRADo DMsilon of Oll and Rrblic Safety D{pi¡rtmrlnt ef l¡k and Errpèd}ymenl Division of Oil and Public Safety - Boiler Program 633 17th Street, Suite 500 Denver, CO 80202-3610 303-318-8484 | cdte_boiler@state.co.us www. cotorado. gov/ops Notice of Boiler lnspection Deficiencies August 16,2021 DMeerschaert@ gtenwoodcaverns. com GLENWOOD CAVERNS HOLDINGS LLC 51OOO TWO RIVERS PLAZA RD cLENWOOD SPRTNGS CO 81601-2809 RE: Boiler lnspection Deficiency lssues Boiter inspections were conducted, as required by the Division of Oit and Pubtic Safety (OPS), at the subject facitities tisted below. During the inspection, the fol[owing items were found to be out of compliance with the laws and regulations promutgated under Cotorado Revised Statutes, Title 8, Articte 20, and Titte 9, Articte 4. Faiture to correct the violation(s) may lead to criminal and civit penatties not to exceed one thousand dollars per violation, for each day of violation. Ptease comptete the repairs in accordance with the inspector's requirements listed betow. An extension may be requested by contacting the inspector or the OPS office at the number listed in the header above. Property: Glenwood Caverns Adventure Park, 51000 Two Rivers Ptaza Rd, Glenwood Facitity tD:2790397 lnspector: Wade Distet (State of Cotorado) Emait: wade.distel@state.co.us Phone: 970-712-7458 Jurisdiction #:CO118748 - lnspection Date:61312021 - Location: Smoke House Upstairs Deficiency #1:510C - INCORRECT SAFETY RELIEF VALVE INSTALLATION - The Safety-Retief Vatve has been incorrectly instatted in wrong location or with spindte in other than a vertical position Required Action: Reinstalt the Safety-Retief Valve as per ASME code. (HG-70f , HLW-801 .2 or Pg-71). Repairs Due By: 81112021 Deficiency #2:810 - REMOTE SAFETY SWITCH REQUIRED - A manually operated remote shutdown switch must be instatled just outside the boiler room and marked for easy identification Required Action: This emergency shutdown switch or circuit breaker must disconnect all power to the burner controts. This requirement is per CSD-1, CE-110(a). Repairs Due By: 811 12021 Jurisdiction #: CO118749 - lnspection Datez 6131202l - Location: Smoke House Upstairs Deficiency #1: 510C - INCORRECT SAFETY RELIEF VALVE INSTALLATION - The Safety-Retief Valve has been incorrectty instalted in wrong location or with spindte in other than a vertical position Required Action: Reinstall the Safety-Retief Valve as per ASME code. (HG-701, HLW-801 .2 or Pg-711. Repairs Due By: 811 12021 Deficiency #2:810 - REMOTE SAFETY SWITCH REQUIRED - A manuatty operated remote shutdown switch must be instatted just outside the boiter room and marked for easy identification Required Action: This emergency shutdown switch or circuit breaker must disconnect atl power to the burner controts. This requirement is per CSD-1, CE-110(a). Repairs Due By: 811 12021 RP tD: ó147483 - cLENWOOD CAVERNS HOLDINGS LLC,2nd Notice of Deficiencies, August 16,2021 re@t COLORADO Dtvtdon of Otl and hrbltc Saftty Dr¡rarlrrurlt uf tdlÀi ¿rl1l Ërrtp*:ryrïraítl Division of Oi[ and Public Safety - Boiler Program ó33 17th Street, Suite 500 Denver, CO 80202-3ó10 Jû1.318-8484 I cdle botler(4state,co,us www. cotorado.gov/ops Notice of Boiler lnspection Deficiencies Property: Glenwood Caverns Adventure Park, 51000 Two Rivers Ptaza Rd, Glenwood I Facitity tD:2790397 lnspector: Wade Distel (State of Colorado) Emait: wade.distet@state.co.us Phone: 970-712-7458 CERTI FICATION STATEMENT: I CERTIFY that the above listed violation(s) identified at Glenwood Caverns Adventure Park, 51000 Two Rivers Plaza Rd, Glenwood Springs, CO, has/have been corrected per the listed required action(s): Printed: Boiler Owner or Responsible Party Representing Signed Date: Boiler Owner or Responsible Party Please return this signed report via email or US Mai[, using the email address or mailing address listed in the header above. An inspection certificate witl be issued upon notification, by return of this signed report, that the boiter has been brought into comptiance and the invoice has been paid. Operation of this boiler without a vatid inspection certificate is untawfut. Your prompt attention to this matter is required. RP lD: ó147483 - GLENWOOD CAVERNS HOLDINGS LLC, znd Notice of Deficiencies, August ló, 2021