HomeMy WebLinkAboutElectrical Inspection Reportlnspection Report
Permit #:861 304 Date lnspected:O1-
FEB-1 gPermit
HoIder:JAVI ER VICENCIO 7256 COUNTY
RD
306 PARACHUTE 81 635 Phone: (970)
366-0980 Fax: Email: VICENCIEO
@G MAI L.CO MS¡t e:7256 COUNTY RD
306 Parachute County: Garfieldowner
:JAVIER VICENCIO
Phone:(970)
366-0980 Status:REJECTED lnspection
Type: Rough ln Trim
Permit:N Constuction
Type: REMODEL Bu¡lding
Type: RESI DENTIAL lnspector:Norman
Feck 303-869-3 442 Corrections:Service
was upgraded and is energized. No
inspection on that until this point. At the
service: 1) 230.284 Missing mast
rr\ rrFrt Frr^r t\
ground rods flush with or below grade. 3)
250.50 Missing ground clamp at incoming
metal water p¡pe (Above grade p¡ping is
plastic). 4) 250.6484 Bury grounding
electrode conductor between rod
electrodes. Depth isn't required to be
T300.5 compliarìt. 5) 408.7 Close unused
breaker openings. 6) 250.9 4A or B
lntersystem Bond Terminal bar required.
Crawl: 1) 250.684 lnstall a crawl access.
Water pipe grounding electrode
connection shall remain accessible. 2)
33 4.15C 14, 12, and 10 gauge NM cable
may not be run on bottom of joists in
crawls or basements. Ok to install runner
boards, as discussed , along side the NM
cabl¡ng. Comments:1) Walls and ceilings
ok 2) Front and back porch outlets have no
junction boxes but will have surface mount
boxes.