HomeMy WebLinkAboutOWTS DesignSOIL PARAMETERS: x SCOPE OF WORK: INSTALLATION OF A NEW ON-SITE WASTEWATER SYSTEM FOR A PROPOSED ACCESSORY BUILDING WITH PLUMBING FIXTURES FOR A SINK, TOILET, AND SHOWER. FOR SIMPLICITY, THE OWTS CALCULATIONS PRESENTED IN THIS DESIGN PLAN EQUATE THE FIXTURES TO A ONE-BEDROOM DWELLING UNIT. PROPOSED IS A NEW ONSITE WASTEWATER SYSTEM WITH QUICK4 PLUS BED SYSTEM. x EXISTING UNDERLYING SOIL IS USDA SOIL TYPE 2, A SANDY LOAM SOIL; STIFF, SLIGHTLY MOIST, REDDISH BROWN; MODERATE BLOCKY STRUCTURE; LONG-TERM ACCEPTANCE RATE (LTAR, TREATMENT LEVEL 1): 0.60 GPD/SF. SOIL EVALUATION IS IN ACCORDANCE WITH THE PROFILE PIT EVALUATIONS FOR GENERAL LAND PRO DEVELOPED BY KUMAR & ASSOCIATES, INC. (PROJECT NUMBER 20-7-528.02) FOR PROFILE PITS EVALUATED ON JUNE 4, 2021. x LTAR = 0.60 GPD/SF PER GARFIELD COUNTY ON-SITE WASTEWATER TREATMENT SYSTEM (OWTS) REGULATIONS (ADOPTED JUNE 18, 2018) TABLE 10-1 FOR SOIL TYPE 2, TREATMENT LEVEL 1 (TL1). SOIL TREATMENT AREA: x FLOW, Q = (1 BEDROOM-EQUIVALENT * 150 GPD) = 150 GPD x UNFACTORED SOIL TREATMENT AREA (STA): A = Q/LTAR = 150 GPD / 0.60 GPD/SF = 250 SF x SYSTEM IS DESIGNED AS PRESSURE-DOSED x REDUCTION FACTORS ARE APPLIED PER TABLES 10-2 AND 10-3. xx TABLE 10-2: SIZE ADJUSTMENT FACTORS FOR METHODS OF APPLICATION IN SOIL TREATMENT AREAS ACCEPTING TREATMENT LEVELS 1, 2, 2N, 3 AND 3N EFFLUENT: A PRESSURE DOSED BED SYSTEM YIELDS A REDUCTION FACTOR OF 1.0. xx TABLE 10-3: SIZE ADJUSTMENT FACTORS FOR TYPES OF DISTRIBUTION MEDIA IN SOIL TREATMENT AREAS FOR TREATMENT LEVEL 1 SYSTEMS: A BED SYSTEM UTILIZING QUICK4 PLUS CHAMBERS YIELDS A REDUCTION FACTOR OF 0.70. x FACTORED SOIL TREATMENT AREA (STA):()175 SF PRESSURE-DOSED QUICK4 CHAMBER BED SYSTEM: x QUICK4 PLUS STANDARD CHAMBER FOOTPRINT: 4.0' L x 3.0' W = 12 SF EA. x # OF QUICK4 CHAMBERS: 175 SF / 12 SF =15 CHAMBERS (MINIMUM)() x PROPOSED LAYOUT: 1 BED ZONE WITH 3 ROWS & 5 CHAMBERS IN EACH ROW =15 TOTAL CHAMBERS x BED LAYOUT: 15 CHAMBERS * 12 SF/CHAMBER =180 SF TOTAL DESIGN STA x BED DIMENSIONS:9' WIDTH x 20' LENGTH = 180 SF x INSPECTION PORTS AND CLEANOUTS TO BE INSTALLED PER PLAN AS REQUIRED. x INSTALL AIR RELEASE VALVE AT HIGH POINT, PER PLAN AS REQUIRED. SEPTIC TANK INFORMATION: x MIN. TANK SIZE =500 GALLON TOP SEAM PUMP TANK WITH LOW HEAD PUMP (VALLEY PRECAST 500T-1CP-LH OR APPROVED EQUIVALENT) x GARFIELD COUNTY APPROVED EFFLUENT FILTER TO BE INSTALLED ON OUTLET PRESSURE DOSING: x FLOW RATE: 32.4 GPM x TDH: 13.1 FT x INSTALL ORENCO 6403 AUTOMATIC DISTRIBUTION VALVE AFTER AIR RELEASE VALVE AND BEFORE MANIFOLDS x SPECIFIED PUMP OPTION: ZOELLER MODEL152 PUMP - OR - APPROVED EQUAL SUCH AS ORENCO MODEL MEETING THESE REQUIREMENTS (PF3005) x NOTE: SPECIFIED PUMP SHOULD RUN BETWEEN 4-6 TIMES PER DAY FOR OPTIMAL PERFORMANCE. x SET LATERAL PIPE 5 32" DIA. ORIFICES ON-CENTER EVERY 4 FT. AT 12 O'CLOCK POSITION. EVERY FOURTH ORIFICE SET TO 6 O'CLOCK POSITION, INSTALL SPLASH SHIELDS AT 6 O'CLOCK ORIFICES. CALCULATIONS AND SPECIFICATIONS 01 © 2021 ENGINEERING LOCAL XPERTS, LLC: A SHAW RESIDENCE ONSITE WASTEWATER SYSTEM PROJECT NAME: 10/29/21 SUBMITTAL JOB #: 100189 PROFESSIONAL SEAL: DATE:DESCRIPTION: COPYRIGHT Phone: 719.308.9146 www.elxsoco.com Hablamos Español PROJECT LOCATION: 1773 CO. RD. 241 NEW CASTLE, CO CARLOS D .SE R RANOCARLOS D .SE R RANO52048 NOTES 02 © 2021 ENGINEERING LOCAL XPERTS, LLC: A SHAW RESIDENCE ONSITE WASTEWATER SYSTEM PROJECT NAME: 10/29/21 SUBMITTAL JOB #: 100189 PROFESSIONAL SEAL: DATE:DESCRIPTION: COPYRIGHT Phone: 719.308.9146 www.elxsoco.com Hablamos Español PROJECT LOCATION: 1773 CO. RD. 241 NEW CASTLE, CO GENERAL NOTES: 1. ALL WORK IS TO BE PERFORMED PER GARFIELD COUNTY ENVIRONMENTAL HEALTH DEPARTMENT AND STATE OF COLORADO CURRENT STANDARDS AND CODES. 2. ALL SETBACKS SHALL CONFORM TO GARFIELD COUNTY HEALTH REGULATIONS (TABLE 7-2). THE CONTRACTOR MUST VERIFY ALL SETBACKS AND OBTAIN UTILITY LOCATES TO VERIFY CLEARANCES PRIOR TO CONSTRUCTION. 3.THE CONTRACTOR SHALL CONFORM TO SETBACKS FROM EXISTING OWTS LEACH FIELDS THAT MAY BE LOCATED ON THE PROPERTY AND IN THE PROXIMITY OF THE PROPOSED LOCATION. 4. THE CONTRACTOR OR PROPERTY OWNER, WHOMEVER IS THE APPLICANT OF RECORD, IS RESPONSIBLE FOR PERMIT. 5.THE CONTRACTOR OR PROPERTY OWNER MUST OBTAIN APPROVAL OF ENGINEERED OWTS FROM THE GARFIELD COUNTY HEALTH DEPARTMENT PRIOR TO ANY SITE DISTURBANCE. 6. PAVEMENT, TREES, SHRUBS, IRRIGATION, VEHICULAR TRAFFIC OR HOOFED ANIMAL TRAFFIC OF ANY KIND IS STRICTLY PROHIBITED OVER THE STANDARD TREATMENT AREA AS IT MAY CAUSE PREMATURE FAILURE OF THE OWTS SYSTEM. 7. FINAL GRADING SHALL BE PERMANENTLY STABILIZED TO HAVE POSITIVE DRAINAGE AWAY FROM THE LEACH FIELD AREA WHICH MAY INCLUDE THE GRADING OF BERMS AND SWALES, AS NEEDED. 8.THE CONTRACTOR SHALL VERIFY THE EXISTING SEPTIC TANK(S). THE EXISTING SEPTIC TANK(S) SHALL MEET MINIMUM DESIGN AND STRUCTURAL CRITERIA OF IAPMO/ANSI Z1000-2007 (AMERICAN STANDARDS FOR PREFABRICATED SEPTIC TANKS) AND BE CERTIFIED BY A PROFESSIONAL ENGINEER AS MEETING THOSE STANDARDS. SEE REGULATIONS OF THE GARFIELD COUNTY HEALTH BOARD AND COLORADO DEPARTMENT OF PUBLIC HEALTH AND ENVIRONMENT FOR MORE INFORMATION. 9.THE SAND FILTER MEDIA MUST MEET SPECIFICATIONS TO SATISFY THE REGULATIONS OF THE GARFIELD COUNTY BOARD OF HEALTH ON-SITE WASTEWATER TREATMENT SYSTEMS REGULATIONS AND STATE CDPHE REGULATIONS. ADDED SOIL MUST MEET THE SPECIFICATIONS OF SAND FILTER MEDIA, AS SPECIFIED IN THE STATE CODE SECTION 43.11.C.2.a.(1). ALL ADDED SOIL MUST BE COMPLETELY SETTLED PRIOR TO INSTALLATION OF COMPONENTS AS SPECIFIED AND APPROVED BY THE DESIGN ENGINEER. THE LOADING RATE FOR SAND FILTERS MUST BE USED. PRESSURE DISTRIBUTION MUST BE USED. THE SPECIFIED SAND MEDIA IS CONSIDERED "SECONDARY SAND" WITH A LONG-TERM ACCEPTANCE RATE OF 0.80 GAL./SF/DAY. SECONDARY SAND MEDIA HAS AN EFFECTIVE SIZE OF 0.15-0.60 MM WITH A UNIFORMITY COEFFICIENT OF LESS THAN OR EQUAL TO 8.0 AND PERCENT FINES PASSING #200 SIEVE OF LESS THAN OR EQUAL TO 3.0. OWNER RESPONSIBILITY AND MAINTENANCE: 1. IT IS RECOMMENDED THAT THE ON-SITE WASTEWATER SYSTEM BE INSPECTED BY A LICENSED PROFESSIONAL ANNUALLY. INSPECTION TASKS INCLUDE, BUT ARE NOT LIMITED TO, OBSERVATION OF A CLEAN EFFLUENT FILTER, WATER LEVELS IN INSPECTION PORTS, SEPTIC TANK INTEGRITY, FUNCTION OF DISTRIBUTION BOX AND VALVES, CHECK FOR CLOGGED SEPTIC LINES VIA CLEAN OUTS, AND CHECKING FOR ANY POTENTIAL LEAKS AND LACK OF WATERTIGHT FIXTURES. 2. IT IS RECOMMENDED THAT THE SEPTIC TANK BE PUMPED EVERY 3-5 YEARS OR AS NEEDED BASED ON INSPECTIONS BY A LICENSED PLUMBER. 3. NATIVE GRASS PERMANENT SEEDING OVER THE SOIL TREATMENT AREA IS RECOMMENDED FOR PLANTING. NO PLANTS WITH ROOTS OR THAT REQUIRE IRRIGATION ARE TO BE PLANTED WITHIN THE SOIL TREATMENT AREA. 4. NO TRASH IS TO BE EXPELLED DOWN DRAINS OR TOILETS. MINIMAL TOILET PAPER FLUSHING PER FLUSH IS RECOMMENDED. USE OF GARBAGE DISPOSAL IS DISCOURAGED. 5.DO NOT POUR CHEMICALS DOWN DRAINS OR TOILETS. 6.OTHER RECOMMENDATIONS CAN BE FOUND ON THE LOCAL HEALTH DEPARTMENT'S WEBSITE AND BROCHURES AS WELL AS CDPHE'S (COLORADO DEPARTMENT OF PUBLIC HEALTH AND ENVIRONMENT) RESOURCES. REQUIRED INSPECTIONS: 1. A COLORADO LICENSED PROFESSIONAL ENGINEER IS REQUIRED TO INSPECT THE INSTALLATION OF ALL OWTS COMPONENTS INCLUDING THE TANK, PUMP CHAMBER, PLUMBING COMPONENTS, AND STANDARD TREATMENT AREA INFRASTRUCTURE PRIOR TO BACKFILL. 2. THE ENGINEER IS REQUIRED TO INSPECT THE SOIL TREATMENT AREA AFTER BACKFILL TO ENSURE THAT MINIMUM COVER AND PROPER DRAINAGE AWAY FROM THE STANDARD TREATMENT AREA IS ACHIEVED. 3. IT IS RECOMMENDED THAT THE CONTRACTOR AND/OR PROJECT MANAGER NOTIFY OUR OFFICE AT LEAST 48 HOURS PRIOR TO SCHEDULED INSPECTION DATE(S). OWTS SPECIFICATIONS: 1.SLOPES ABOVE OR ADJACENT TO THE SEPTIC FIELD SHALL NOT EXCEED THREE FEET HORIZONTAL FOR EVERY ONE FOOT VERTICAL. 2. FINISHED GRADE TO BOTTOM OF CHAMBERS IS A MAXIMUM OF 4 FEET MEASURED FROM THE HIGH SIDE OF THE BED. FINISHED GRADE TO TOP OF CHAMBERS IS A MINIMUM OF 1 FOOT MEASURED FROM LOW SIDE OF THE BED. 3. DESIGN IS FOR INSTALLATION OF QUICK4 PLUS STANDARD CHAMBERS. USE OF ALTERNATIVE CHAMBERS REQUIRES REDESIGN FOR COUNTY APPROVAL. CONSTRUCTION NOTES: 1. THE CONTRACTOR SHALL VERIFY THAT THE SEPTIC LINE TO THE TANK IS 4" DIAMETER SCHEDULE 40 PVC AND BUILDING SEWER CLEAN-OUTS ARE INSTALLED AND ACCESSIBLE. 2. ANY REQUIRED FITTINGS SHALL BE LIMITED TO 45 DEGREE BENDS OR LONG SWEEP QUARTER BENDS. NO 90 DEGREE BENDS SHALL BE INSTALLED. FOR ANY AREAS WHERE FITTINGS ARE TO BE INSTALLED, WHICH MAY EXPERIENCE VEHICULAR LOADS, THE PIPES AND FITTINGS SHALL BE PROTECTED PER GARFIELD COUNTY HEALTH DEPARTMENT REGULATIONS. THE SITE PLAN ON THIS SHEET SHOWS THE DESIGNED ANTICIPATED FITTINGS REQUIRED FOR INSTALLATION. SITE CONDITIONS MAY WARRANT THE INSTALLATION OF ADDITIONAL BENDS TO FOLLOW THE PROPOSED SEPTIC ALIGNMENT AND LOCATION OF THE PROPOSED INFRASTRUCTURE. 3. THE LEACH FIELD AREA IS TO BE COVERED WITH A MINIMUM OF 6-INCHES OF TOPSOIL FOR NATIVE PERMANENT SEEDING. 4. VEGETATION SHALL BE MAINTAINED AND MOWED TO PREVENT BIO-MATTING. 5. IT IS RECOMMENDED THAT SWALES AND BERMS BE INSTALLED AS NEEDED TO HAVE POSITIVE DRAINAGE AWAY FROM THE SOIL TREATMENT AREA, MOST NOTABLY ON THE UPHILL SIDE TO DRAIN AROUND THE TREATMENT AREA. SEE OTHER SHEETS FOR MORE DETAIL ON MINIMUM/MAXIMUM GRADING LONGITUDINALLY AND LATERALLY WITHIN THE SOIL TREATMENT AREA. 6.OWTS TO BE ROPED OFF WITH CAUTION TAPE OR TEMPORARY CONSTRUCTION FENCING PRIOR TO AND DURING CONSTRUCTION TO PREVENT CONSTRUCTION TRAFFIC FROM COMPACTING SOILS... 7. EROSION CONTROL MEASURES SHOULD BE INSTALLED AS NEEDED. AT A MINIMUM, SILT FENCE OR SEDIMENT CONTROL LOGS SHOULD BE INSTALLED ON DOWNSTREAM SIDES OF AREA OF DISTURBANCE. IT IS RECOMMENDED THAT UPSTREAM SIDES HAVE EROSION AND SEDIMENT CONTROL MEASURES INSTALLED TO PROTECT THE SOIL TREATMENT AREA, ESPECIALLY IF THERE IS TO BE A DELAY IN WORK FOR MORE THAN 24 HOURS AND/OR INCLEMENT WEATHER IS ANTICIPATED DURING CONSTRUCTION.CARLOS D .SE R RANOCARLOS D .SE R RANO52048 SITE PLAN 03 © 2021 ENGINEERING LOCAL XPERTS, LLC: A SHAW RESIDENCE ONSITE WASTEWATER SYSTEM PROJECT NAME: 10/29/21 SUBMITTAL JOB #: 100189 PROFESSIONAL SEAL: DATE:DESCRIPTION: COPYRIGHT Phone: 719.308.9146 www.elxsoco.com Hablamos Español PROJECT LOCATION: 1773 CO. RD. 241 NEW CASTLE, CO AREAA OF INTERESTSSTSSSSSTTTSTTSSSSSTTTSSSSSSSTTSSSSSTTTSTSSTTSTTESESSSSSSSSESSSSTTTSTAAOAAOAAOAAOAA OAAOAAOAAO TEERRRRRREREEEERRRRRRRA O VICINITY MAP N.T.S. SEE SHEETS 01 AND 02 FOR NOTES, CALCULATIONS, AND SPECIFICS FOR PROPOSED ONSITE WASTEWATER SYSTEM DESIGN AND INSTALLATION. SEE SHEET 04 FOR DETAILED PLAN AND PROFILE OF SEPTIC FIELD. SEPTIC LEACH FIELD SHALL NOT BE LOCATED WITHIN 100 FEET OF ANY WELL. CONTRACTOR SHALL VERIFY LOCATION OF ANY NEARBY WELLS PRIOR TO CONSTRUCTION. SEPTIC LEACH FIELD AND OWTS COMPONENTS SHALL FOLLOW GARFIELD COUNTY TABLE 7-2 SETBACKS AS WELL AS SETBACKS FROM EXISTING OWTS LEACH FIELD(S) ACCORDING TO STATE REGULATIONS. NO ALTERATIONS SHALL BE MADE TO THE DESIGN PLAN WITHOUT CONSENT FROM THE P.E. INCLUDING THE LOCATION OF COMPONENTS AND LEACH FIELD. IT IS RECOMMENDED THAT A FENCE/BARRIER AROUND THE TREATMENT AREA BE INSTALLED TO PREVENT NEGATIVE IMPACTS FROM VEHICLES AND/OR LIVESTOCK. NEW ENENENENENEENNNNENEENENEENNEE CASTAASALEEELLEEECO. RD. 2441C O . R D . 2 4 5 CO. R D. 2 2 6 CO. RD. 243C O . R D . 2 4 5 CARLOS D .SE R RANOCARLOS D .SE R RANO52048 FIELD LAYOUT AND SECTION VIEW 04 © 2021 ENGINEERING LOCAL XPERTS, LLC: A SHAW RESIDENCE ONSITE WASTEWATER SYSTEM PROJECT NAME: 10/29/21 SUBMITTAL JOB #: 100189 PROFESSIONAL SEAL: DATE:DESCRIPTION: COPYRIGHT Phone: 719.308.9146 www.elxsoco.com Hablamos Español PROJECT LOCATION: 1773 CO. RD. 241 NEW CASTLE, CO SECTION A-A SCALE:1"=2' EX. SLOPE DUE SOUTHEAST BERM WITH DRAINAGE SWALE RECOMMENDED FOR UPSTREAM SIDE, MIN. 2% LONGITUDINAL GRADE ALONG FLOW LINE RECEIVING SOIL - SEE PROFILE PIT EVALUATIONS REPORT/LETTER FOR INFORMATION [SANDY LOAM; STIFF, SLIGHTLY MOIST, REDDISH BROWN; MODERATE BLOCKY STRUCTURE; USDA SOIL TYPE 2 (LTAR=0.60), 0.5' - 8.0' DEPTH FROM EX. GRADE] LEVEL 9' BED WIDTH A A NNSEE SHEET 03 FOR SITE PLAN 5 CHAMBERS/ROW SEE STANDARD TREATMENT AREA CROSS SECTION A-A DETAIL BELOW EX. LATERAL SLOPE (SOUTHEAST) LONGITUDINAL SLOPE TO BE RELATIVELY FLAT, CHAMBERS TO BE INSTALLED FLAT. MUST MEET MIN.&MAX. BURY DEPTHS. 1-1/2" DIAMETER SCH. 40 PVC PIPE MANIFOLD 1-1/2" DIAMETER SCH. 40 PVC PIPE FROM DOSING/PUMP TANK INSPECTION PORTS TO BE INSTALLED AT EACH CORNER OF THE BED, DETAIL ON SHEET 05 20.00' TOTAL BED LENGTH (NOT INCLUDING END CAPS) 9.00' BEDWIDTH FLUSHING VALVES EA. ROW, SEE DETAIL SHEET 05 10'5'0' 1"=10' AIR RELEASE VALVE (AT HIGH POINT) *EXCAVATE BED PERPENDICULAR TO SLOPE SEPTIC LEACH FIELD PLAN VIEW SCALE:1"=10' ~6" OF EX.ORGANIC TOPSOIL ORENCO 6403 AUTOMATIC DISTRIBUTION VALVE WITH ACCESSIBLE VALVE BOX 1-12" SCH.40 PVC LATERAL PIPES WITH 532" ORIFICES EVERY 4' IN 12 O'CLOCK POS. (FIRST ORIFICE CENTERED ON FIRST ROW OF CHAMBERS), THIRD ROW ORIFICE IN 6 O'CLOCK POS. WITH SPLASH SHIELD INSTALLED MIN. 6" TOPSOIL WITH NATIVE GRASS APPROVED SOIL FOR COVER ( EXCAVATED NATIVE SOIL, USDA TYPE 2) SCARIFY BOTTOM OF BED AND ELIMINATE BUCKET SMEAR ON ALL EXCAVATION OF SIDE WALLS PRIOR TO PLACING CHAMBERS CARLOS D .SER R ANOCARLO S D .SER RANO52048 12" 34"EFFECTIVE LENGTH 48" PRESSURIZED PIPE DRILL POINTS LOCATIONS (2 PLACES)18" 13" 33" FRONT VIEW QUICK4 PLUS ALL-IN-ONE PERISCOPE (360° SWIVEL) 12.7" INVERT SIDE VIEW 8" INVERT 6" 5"9" 3 E DETAILS 05 © 2021 ENGINEERING LOCAL XPERTS, LLC: A SHAW RESIDENCE ONSITE WASTEWATER SYSTEM PROJECT NAME: 10/29/21 SUBMITTAL JOB #: 100189 PROFESSIONAL SEAL: DATE:DESCRIPTION: COPYRIGHT Phone: 719.308.9146 www.elxsoco.com Hablamos Español PROJECT LOCATION: 1773 CO. RD. 241 NEW CASTLE, CO 4" DIA. SCH. 40 PVC PIPE WITH REMOVABLE CAP MIN. 6" ABOVE FINISHED GRADE. DRILL MIN. OF FOUR - 1/8" DIAMETER HOLES ABOVE GRADE TO ALLOW SYSTEM TO VENT. INSTALL PER CHAMBER MANUFACTURERS RECOMMENDATIONS. EFFECTIVE WIDTH=36"CARLOS D .SER R ANOCARLO S D .SER RANO52048