Loading...
HomeMy WebLinkAboutOWTS Design129 CAINS LANE CARBONDALE,CO A1623 97C-.3C9.5259 CARI-A. OSTBE RG@GMAI L. COM rit,:t r't'r(' ('( rNr{t'r.'l't \'(; October 22,2421 Project No. C1668 Sam and Barbara Jurmu keranen barbara@hotmail.com Subsurface lnvestigation and Onsite Wastewater Treatment System Design 5-Bedroom Residence TBD Scutter Lane, Tract I Garfield County, Colorado Sam and Barbara, CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system (OW|.S) design for the subject residence. The 35.52-acre property is located outside of Rifle, in an area where OWTSs are necessary, Legal Description: Section: 28 Township: 5 Range: 92 A PARCEL OF LAND SITUATE lN THE NE1i4 & SE1/4 OF SECTION 28 CONT. 35,52 AC. +1., BEING MORE PARTICULARLY DESCRIBED PER SPECIAL WARRANTY DEED RECEPTION NO, 954022. Parcel lD: 212728400389 SITE CONDITIONS The properly is currently undeveloped. A 5-bedroom residence is proposed. The residence will be served potable water from a cistem that will store hauled water. At this time, no well is proposed, lf a wellwill be drilled in the future, the well must be at least 50-feet from the septic tank and at least 100-feet from the soil treatment area (STA). A dry gulch runs to the south of the proposed residence. The proposed STA must be at least 25-feet from the dry gulch. The proposed STA location has an approximate 9-10 percent slope to the southwest. The area is vegetated with sparce native grasses and sage. There should be no traffic or staging of material over the future STA site to avoid compaction of soils prior to construction of the STA. SUBSURFACE The subsurface was investigated on September24,2021by digging two soil profile test pit excavations (Test Pits). A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.l I Carla Ostberg holds a Certificate of Attendance and Examination from the CPOWVisual and Tactile Evaluation of Soils Training. Page 2 The materials encountered in Test Pit #1 consisted of light brown clay loam to a maximum depth explored of 8.0-feet. No bedrock or groundwater was encountered. The materials encountered in Test Pit #2 consisted of light brown clay loam to a maximum depth explored of 8.0-feet. No bedrock or groundwater was encountered. A sample of the soils was taken from Test Pit #1 at 3-feet þelow grade. Soil structure grade was moderate. The soilformed a ball and a ribbon 1 to 2-inches in length before breaking. Soil structure shape was blocky and consistence was firm. Soil texture was both gritty and smooth. STA sizing is based on Soil Type 3, Clay Loam with moderate structure grade. A long term acceptance rate (LTAR) of 0.35 gallons per square foot will be used to design the OWTS. Test Pit &'f I .t I ..1 Sieved sample t Ribbon 1-2 inches Page 3 hr,".,,",, u backfill it', DESIGN SPECIFICATIONS Desion Calculations: AverageDesignFlow=TSGPDx2people/bedroomx3Bedrooms+150GPD14tt'andSthbedrooms)=600 GPD LTAR = 0.35 GPDISF 600 GPD / 0.35 GPD/SF x 1.2 (gravity beds) x 0.7 (GeoMatrM with 6" sand) = 1440 SF :.- -, d The new OffiS design is based on s-bedrooms. An average daily wastewater flow of 600 GPD will be used. Page 4 For the purposes of this OWTS design, Benchmark Elevation at grade 5800' 6' has been established as 100'as the Main Level Finished Floor (FF). The Lower Level FF is 90' 9 718" at elevation 5791'3718'. Thesewerlinewill existtheresidenceatapproximatelySS'9718" (5789'3718"). CBOlnc.shouldbe notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. *Elevations are based upon standard OWTS installation practices. Component elevations may change during installation due to site conditions. The sewer line exiting the residence must have a double-sweep clean out and a minimum 2% grade to the septic tank. An additional clean out is required for every 1O0-feet of sewer line, The elevation of the sewer line existing the residence requires the septic tank be pushed further from the house to allow a shallow tank installation, with no more than 4-feet of cover or the septic tank lid. The system installation must include a 15OO-gallon, two-compartment poly lnfiltrator@ septic tank with an effluent filter on the outlet tee. Any state-approved poly septic tank or concrete Valley Precast septic tank may be substituted. Risers must bring the manhole lids to grade for access. lf more than one riser is added to the septic tank, an extension handle must be installed on the effluent filter. Effluent will gravity flow to a distribution box, and then to two 1Q' x72' GeoMatrM beds. The distribution box must be accessible from grade and must have flow equalizers, or similar product, installed on each outlet pipe in the distribution box to assure equal flow to each bed. Each bed must have a minimum of 6-inches of sand filter material placed in each over-excavation. Sand filter material must be clean, coarse sand, all passing a screen having four meshes to the inch. Ïhe sand must have an effective size between 0.15 and 0.60 mm. The uniformity coefficient must be 7.0 or less, Material meeting ASTM 33, for concrete sand, with three percent or less fines passing 200 mesh sieve may be used. A gradation of the sand media must be submitted to this office prior to obtaining the sand. Three 39-inch wide GeoMatsrM will be placed on top of the sand filter material on each bed. A 4-inch diameter perforated pipe will be placed down the center of the GeoMatrM, under the top layer of fabric. Each bed will have a total of 216linear feet of GeoMatrM and 720 square feet of infiltrative area for a total of 432linear feet of GeoMatrM and 1440 square feet infiltrative area. All material associated with the GeoMatru installation must be proprietary products associated with the GeoMatrM, including the geotextile fabric. Manufacturer instructions must be followed regarding installation of the GeoMatTM. There must be at least 6-feet of undisturbed soil between each bed. lnspection ports must be installed at the front corners of the bed to the side of the GeoMatrM and the end inspection ports will þe tied onto the end of the lateral. Ports may be cut to grade and placed in sprinkler boxes for access. There shall be no cobble-sized (<2,5") or greater rock in final cover over the GeoMatrM. OWTS Component Minimum Elevation Primary Tank lnlet lnvert (max burial depth to top of tank 4') Approximate horizontal distance 123' I min.2o/o fall / min. 30.75" fall Distribution Box Approximate horizontal distance 37' / min, 1o/o fail I min.4.625" fall lnfiltrative Surface (shallow installation 2 recommended) Approximate horizontal distance to furthest lateral 33' / min. 1o/o tall / min. 4.125" lall Page 5 COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area. CBO lnc. must approve alternative components prior to installation of the OW[S. Requests must be submitted, in writing, to our office for approval prior to installation. Component technical data sheets are available upon request. Construction must be according to Garfield County On-Site WastewaterTreatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. INSTALLATION CONTRACTOR CBO lnc. expects that the installer be experienced and qualified to perform the scope of work outlined in this design. The installer must review this design thoroughly and coordinate with our office in advance of installation. Any additional conditions in this desígn or county permit must be completed and documented prior to final approval of the OW|S installation. Communication between the installer and this office is expected throughout the installation. INSTALLATION OBSERVATIONS CBO lnc. must view the OWTS during construction, The OWTS oþservation should be performed before backfill, after placement of OWI.S components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should þe notified 48 hours in advance to observe the installation. ln an effort to improve the accuracy of the record drawing, we request that the installer provide a sketch of the installation, including path of the sewer lines, water line installation (if applicable), septic tank location, STA location, and measurements from building corners or another fixed objects on the property. This sketch is most easily provided on Sheet \Iú2,0 of the OWTS Design Packet. Photographs of the installation and final cover are also requested to supplement our installation documentation. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular inigation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owìer of the OWI.S shall be responsible for maintaining proper vegetation cover. COMPONENT MANUFACTURER MODEL NO.GOMMENTS Sept¡c TanK lnfiltrator@ tM-1530-2CP 1 500-gallo n, two-compartment polv septic tank Biotube Effluent Filter Orenco@ Full Size Effluent F¡lter and housino D¡strlbut¡on Box PolyLoK Distribution box, risers, lid, and flow equalizers (6) GeoMatrM GeoMatrix Systems, LLC 432,GeoMalrru 139,, wide sheets) Page 6 OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWIS servicing the property, The property omer is responsible for maintaining service contracts for manufactured units, altemating STAs, and any other components needing maintenance, Geo-fabrics or plastics should not be used over the STA. No heaqy equipment, machinery, or materials should be placed on the backfilled STA, Machines with tracks (not wheels) should be used during construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals þe flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OW[S. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWIS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS, The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high- water conditions and shall be connected to a control breaker separate from the high-water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. LIMITS: The design is based on information submitted. lf soil conditions encountered are different from conditions described in report, CBO lnc. should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, CBO lnc. (,trr, (-* }g't l,.en. g Carla Ostberg, MPH, REHS CBCI lnc.l29CaftB tanôCaröondde, Coþ¡ado 8l 623Phone 970,309.525Scarlaosú€rgârgrmil-comtJurmu ResidenceTr€d I, Scr¡ttgr l"an€Gañleld County, ColoratloProj€ctNurùer C166810tiøîm1br DI)bs CtsOw1.0Shæt10F4NSCAIE: I = sOL{fìItuz=l-ÉIJJfLoÉfLIIlRESIDENCETP1+T}lE LOcATþlì¡ OF PROPOSED hFRO\ÆHENTSSHOWN ARENOÏTHE RE$'LT OFAPROFERTY$AVÉY. lHE LOGATK'I{SÂNEAPPRO'(IIAIE. fT IS THE HOT'EOWilERS I'I,JTY TOEllsuREA¡"! cotr¡'¡n¡cÏoN AltD t[rpRovEt ENT LocATþt{sAREACCURAIE. PROPERTY IJI¡ESÁIüSEIBAC|(D|S¡TA¡.|CESSHOIJI¡ BE COÍ*FIRIIÊD PRORTOÞ(cåVAÏq{. SCAIEOF()RPfilifrNc Ot{.lt.x l7 PAPERQnrG{4.c¡,ßSTA2t)DRAWNGS MIJT}TBE USED INCONJUNCTION UNTH TES|GNLETTER DATED IÜ212V1rãS¡lE PLANl'-S+ BM 100' FF MAIN LE:VEL 5800'0" FF LOWER LEúEL 9{I8f.57s1'3Y 4' DIA gDR.gı SEWER PIPÊ WITH CLEANOUT MIN 2% FAIL TO TANK N 4¿¡r, CLEAN OUT {MlN. ErúERY 100' OF SEI1\'ER L|NE)SCALE:1". 20'{" TWO-COMPARruENT SEFTIC TANK WITH EFFLUENT SCREEN 4'DIA SDR€5 PVC SEWER LINE (MtN. 1% FALL TO D.BOX) DISTRIBUTION BOX WTH ACCESS AT CRADE #/d/s/6/.' TPl 4' DIA SDR€5 SEWER LINE TO EACH I.ATERAL (MrN. 1% SLOPE) + ¡[" DIA sDR-35 INSPECTION PORT AT FRONT CORNERS DRY GULCH 2 25'MrN TO OULCH 3 SHEETSOF39"GEOMAT il tN Beo CONFIGURATION oEoMAT ÎM FABRtc ovER 4' LATERAL 4' DIA PERFRATËD PIPE TATERAL PI¡CED ON TOP OF GEOMAÎIM TWO (2) GRAVTTY GEOMAT 't2 X 72' BEDS WtrH e OF SAND ON BASE WTH 3 ROWS OF 3S" GEOMAT. DEPTH OF BED TO REMAIN SHALLOW, APPROXIMATELY 2' BELOW GRADE. 4' DIA SDR.35 INSPECTION PORT AT END OF EACH IâTERAL CBO lnc. 129 Colß Lånê Corbondale, Colorado 81 ô23 Phone 970.309.5259 aârlã,osþ€rg@gmâi l.com Jurmu Resldencs Trad 8, Scuttcr Lanc Gãrfisld County, ColoÌado PruJectNumb€l: C1668 Oale: ßn212O21 D€E¡gnod by: CBO Drawn by; ÞD w2.0 Shset 2 0F ¡t C8O lnc.l2gcetls t-tloCûüqld€le, Cdora(þ816ãìFhmê 970-S¡9.5¿50øh.o3iùorg@mdl.comilOTE: f SA¡\D ON BASÉ OF 1ûXU BEDDEFÍH OF BEDTC' REIIAIN STIÁLLOVT',APPROXMATELY? BELOWGRADEDtsfRBt txt{¡ccEssÀf GRÁ¡tÈ/ß DTASI'R.SsII{SPECTICN PORT AT END OFE¡CH LAIERALEFFI¡.,CIÍT PFE FROfl.SEPÍICIAM(4'D|ASOR-i5¿T T'TA PERFRATED P['Ê l.AlËRALFIACËD ONTOP OF GEOI,IATITÍOAI}DITIOI{ALBEDGÊOIIAÎT FÂ8Rlc O'ER4TI.A'TERALINSPËCT¡CI.¡ FORT AT FRONTCORIERSOFBEDRCNN'S OF Sf GEOIIATillN BED COòtFGInAlþlì¡,â\GEdaAT PL¡ l\!,__-__------.rñÊFiffiM¡fEFEüqttttfti|lmCo$rFá¡b¡+'D¡ir$uübn Pip.t¿þfibæTrðffdsdlr8r sAt¡D39irËcútüilRríwææ=O-t5-OEd¡troilrcoEFrctrs7¡srcmsgtmrÈoseÊ_<otlyErEcÐb/â\GEOI|AT SÉCÌ10{\rt-TE/5rSfA SECII(I¡\gr______---.rffEJumu ResidenceTraclS, Scr.ftbrLaneGarHCoulft,CobråeProje.tNurnöer: C1668balø: ßfÐ.2o21k**o*""olOrawn* OOw3.0Sìfþet3 0F 4 CBO lrE,129 Cahl8 LdreCarbonddo, ColoÎådû 81623Ptsl€9703æ.5259carh.o6tbor!@m,il.cqlrDESIGN$ðEDROOT REEþEHCE75 GPDr 2 PERSOI,|S'BEDROOM x3 BEDROOT¡|S + 150 GpD (¡tTHAlüsfHBE:DROOTTS) = 600 GPDWASTEIYÂTER FLOllt = @ GFDIANK:MlH. 15{'0 GALLOÍ{SIJSE IsOOGAT.LON, T1VO4OMPARTIIENI CONCRFÍE SEPNC îAIffBOX AI{D Cô\ÆR BRûJGüIT TO GRAD€SOIL ÎRËATilEìfT ARÊA (STA}LOÈ{GTERM ACCEFÍANCÊ RAÌE (LTAR) Ê 035 cl4lrSFCåLCUI¡{GD STA = O,LTAR = 500/035 = l7l4 SFGRAVIÎY BEDS = I7I¿I SF X 12 _ 2fFI¡ SFGEOilAT= ã157 SFX0.7= l,l40 SFTITO BEÍ'S, EACI.I IÛ X U WMI THREE 3g WTE GEOI'ATS ON EACH BED432 LNEAR FÉET OF 3S GBONIATCOT{CREÍEBAFFLEORAÀGI.ED PIPETOBEUSEDATINLETSOIL PROF¡LE IEST PIT l,þ. ISOIL PROFILE TEST PTTNO.2/ì DSIRIBTJIION B()X DFTAIL\!r--fffúELIGHT BROVIN CI.AY IOAMLIG'}ITBÑVTNCI¡Y LOAMsltPot{ PvcSFRINKLERV^LIÆBOXATGRADEDONOTGI-UEFINISI{ED GRAÐE,{.lNsrrEgltoìt P|PENO GROUNDWA'ÍER OR BEDROCK ENCOU{IEREDUJRNG Ð(CAVANONSTAlt¡t'DlAHorE DRILLED|NTOïVþS|DESOF PpËFORì'EÑNLATK'N(BELryY9-PONCAP)l¡lEDlA/ãsots LoGlér---rrE/âINSPECTIOIìI PfrÏ DETA¡L\9t---r3EOIJTLETSooooLEGEÌrlDfløtlmJurmu ResidenceTrå(i8, SqrtþrLånêælrt Cor$ty, CdoradoPrþiNurùen C1668w4.0Sh6€t+tn¡l G)qPublic'hêt""' Garfield County, CO 81ó50 2019Total Actual Value Overview Ê Legend {...j Parcels Roads Parcel/Account Numbers Highways s LimitedAccess - Highway Major Road Local Road Minor Road Other Road Ramp -- Ferry Pedestrian Way Owner Name lJ Lakes&Rivers - CountyBoundary Line $1,950 Last2Sales Date Price 6/27/202t $125,000 6/8/202t $O Account R084óó7 Physical 0 Number Address Parcel Number 2L27284@389 RIFLE Acres 3ó OwnerAddress JURMU,SAMUEL K& BARBRA LandSqFt O D TâxAreâ O2l ó99 BRISTLECONEWAY 2019Mill Levy ó7,8830 SILTCO 81652 Date created: 77/7/2021 Lest Date Uploaded: tll 1lñ21 2:O7:54 AM Deveroned bv¡[.) Ð."ü,gpif, çr 10nU21,10:04 AM Summary AECoünt P¡rcd Ptoparty Addrc¡s l¡t¡l Dascrlptlon Adcs Lend SqFt TaxAre¡ MlllLã,y SubdM¡lon qPublic.net - Garfleld County, CO - Pmperty Record Card: R084667 tÐqPublic.net''' Garfield County, CO RO8Æ67 2t272840¡0ß9 ,RIFLE,CO 8tó50 S€ctioil 28 Torvnshlpr 5 Range; 92 A PARCEL OF LAND SITUATE I N THE NE1/4 & SEU4 OF SECÍ ION 28 CONT. 3552 Ac' +/-, BEING MORE PARTICUTARLY DESCRIBED PER SPECIALWARRANTY DEED RECEPTION NO, 95¡1022. 35.52 ACRES 35.52 0 2t 67.8830 VlewMap Owner JURMU, SAMUEL K & BARBRA D ó99 BRISTLECONE WAY srLlco81ó52 Land Unltlyp€GRAZ|NG |-AND-AGRTCULTURAL - 4147 (AGRTCUITUnRL PROPETTY) 0squ¡rc Frrt ActualValues Arr¡rscdYc¡r L¿ndAcbal lmpro\æmcntActuâl Tot¡lActu¡l Assessed Values A¡¡c¡¡edYear LandA¡sgssed lmprovementA3s$sed TotalAssrssed Click here tovlew the tâx information forthis Transfers S¡lêD.tc Dtcdlypé 612U2O21 SPECIALWARRANTYDEED 6181202I STATEMENIOFAUTHORIW u8t202! DECTARATTON ANNOA, SPECIALWARRANTYDEED 4I7I2O2I EASEMENT 1I29I2OT9 BARGAINANDSALÊDEED U2SI2OI9 EASEMENT U2312O19 EASEMENT U2SI2OL9 EASEMENT U18I2OL9 SÍATEMENTOFAUTI{ORITY UU2OL9 STATEMENTOFAUTHORITY t0/L812o78 QUTTCIATM DEED IULAI2OTS WARRANTYDEED totlßtzot8 QUlrcLArM DEED toltB/zotÛ qulTcrArMDEED \OIT7/2OT8 STATEMENTOFAUTHORITY x)zt $1,9s0.00 $o,æ st9s0.0o 202L $570.00 $o.00 s570.00 TaxHistory An enor has oca¡rred while trylngto dlsplaythls paÈ of tùe pâgê, Wg apologlze for arry ¡ncorilreniênce. ReeptlonNumber 9s832ó 9579t3 95TTÆ 95{0.22 9s4ot4 917053 977059 9t7058 9L7057 91ó80ó 9t6tt3 913181 913779 ,13t76 9t3174 973775 Eod<-Pa¡c Sah Prlcc $125,000 $o $o $o $o $o $o $o $o $0 $o $o $tóo,ooo $o $o $o https://qpublic.schneidercorp.oom/Application.aspx?ApplD=1O38&LayerlD=22381&PegsTypelD=4&Pagelp=g{{/!Q='1168726837&KeyValue=R084667 1n 10122f21,10:û4 AM qPubllc.net - Garfield County, CO - Propefi Record Card: R084667 1017712018 10lLsl20t8 tott5t20',8 tottot20t8 701?/201a slslzots 5tu20t4 312012009 1ULl120n,8 8t2U2æ7 8t2U2ú7 8l,,uM7 7læt2@7 3t25t2c0,S 3f25t2ú3 5lt4t2ú2 5/10t2cF,2 tot24t2æ7 51L4t7997 uzat9a2 8123t1e82 5t24tt9B2 4/161L973 tagu969 STATEMENTOFAUTHORITY BARGAIN AND SAIE DEED SIATEMENT OF AI.ITFIORITY SÍATEMENTOFAUTHORITY QUITCLAIMDEED PERSONAL REP DEED BARGAINANDSAIE DEED EASEMENT STATEMENTOFAUTHORITY QUTTCLAtM OEED BOUNDARY LINE ADJUÍ MENT BOUNDARY LI NE ADJUSTMENT QUITCLAIM DEED QUITCI.AIMDEED WARRANÎYDEED qUlTCIAIMDEED WARRANÏYDEED WARRANTYDEED WARRANTYDEED WARRANTYDEËD WARRANTYDEED RESOLUTION WARRANTYDEED STATEMENTOFAUTHORITY 913773 913782 9L3177 973178 973L72 862624 848905 765336 759725 73r915 7319t4 73t9L2 731913 625142 62514t ó03341 óo3340 59L749 510781 33tO18 33901ó 328092 258065 913183 1458-198 L458-L95 735+775 t35+774 1302.480 1025-555 0621.0615 oó21-0ó09 0óm-01ó2 w3-oín s75,000 $25,000 $o so $o $o $o $0 $o $o $o $o $o $o $o $o $o $o $o $o So $o $72,5æ $ó4,ooo No dat¡ ¡v¡ll¡blc fbrthefollowlm modulerr Bulldlngs, Photos, SketcheÉ. r r:riltrrl i;r ¡,,.r:l r.it :,,1:ti Ussr.-P"rive-cvl:ekv Ç"Ð.?R.Priv.açy_-tÍçlice l-as!-ÞåUUp!sa*"-L0.le4æ4-12:3-4:X1Al4 tt ¡ i' t' ", ".:'", i. :r ,.'.'i, : r: .i ì .' 6TÐ,"1'pp;,4çt https;//qpubllc.schneidertorp.com/Appllcation,a6px?ApplD=1O38&LayerlD=22381&PageTypelD;4&Pagelp=g{{/ffQ={/68726837&Kswalue=R08,4667 U2