Subsurface lnvestigation and Onsite Wastewater Treatment System Design
2-Bedroom Additional Dwelling Unit (ADU)
1800 Black Diamond Mine Road
Garfield County, Colorado
Eric,
CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system
(OWTS) design for the subject residence. The 4O-acre property is located outside of Glenwood Springs,
in an area where OWTSs and wells are necessary.
LegalÐescription: Section: I Township: 7 Range: 89 SWSW 40 ACRES
Parcel lD: 2395-093-00-010
SITE CONDITION$
A 4-bedroom, single-family residence presently exists on the southern portion of the property. The
residence is served by a separate OWTS.
A 2-bedroom additionaldwelling unit (ADU) is proposed on the northern portion of the property. This
area is greater than 1000 feet from the existing residence.
The ADU will be served by a private well located on the northern portion of the property. The well is
greater than 5O-feet from the proposed septic tank and greater than 100-feet from the proposed soil
treatment area ($TA).
The proposed STA location is between the proposed ADU and existing driveway. The area has a natural
slope to the northwest but had been filled previously and has now been graded to create a level area for
the $TA. Vegetation including native grasses and trees had been removed at the time of our site visit.
The proposed ADU location índicated on the plans are not the result of a survey.
There should be no traffic or otaging of material over the future STA slte to avoid compaction of solle
priorto construction of the STA.
ç
Page2
SUBSURFACE
The subsurface was investigated on Septembêr 15 by digging three soil profile test pit excavätions (Têst
Pits). A visual and tactile soll analysis was completed by Garla Ostberg at the time of excavation.r
The materials encountered in Test Pit#1 consisted of medium brown clay loam a maximum depth explored
of 6.0-feet wlth a root zone at approximately 2,S-feet below current grade which we believe indicates
previous native grade prior to fill being placed in this area. No bedrock or groundwater was encountered.
The materialg encountered in Test Pit #2 consisted of medium brown clay loam a maximum depth explored
of 8.0-feet with no rootzone oþserved- No bedrock or groundwater was encountered.
The materials encountered in Test Pit #3 (in the area of the foundation) is documentêd by Kumar and
Associates report dated $eptember 27, 2021, Proiect2l-7-751 (enclosed).
A sample of the soils was taken from Test Pit #1 below the rootzone. Soil structure grade was moderate
The soil formed a balland a ribbon I to 2-inches in length before breaking. Soilstructure shape was
blocky and consistênce wâs friable. Soil texture was both gritty and smooth.
STA sizing is based on SoilType 3, Clay Loam with moderate structure grade. We are proposing a
pressure-dosed, over-excavated, unlined sand filter with a minimum of 2-feet of Secondary Sand filter
material to accommodate the space available for the proposed STA. A long term acceptance rate
(LTAR) of 0.65 gallons per square foot will be used to design the OWT$'
l; *#Tl¡ . :,' '
ãç"¡.*' l-'
' Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Msual and Tactile
Evaluation of Soils Trainfng.
e.*rÉ
i{ }{
.$#
Test Pit #1 (arrows indicate root zone)
Page 3
Test
Sieved sample Rlbbon between 1 and 2-inches in length
Page 4
View of graded area
DESIGN SPEGIFICATIONS
Qgsion CalcFlatio.ns:
Average Design FIow = 75 GPD x 2 people/bedroom x 2 Bedrooms = 300 GPD
LTAR '. 0.65 GPD/SF
300 GPD / 0.65 GPD/SF = 461.5 SF
The neuv OWTS design is based on 2-bedrooms. An average daily wastewater flow of 300 GPD will be
used.
For the purposes of this OWTS design, Benchmark Elevation has been established as Finished Floor of
the ADU as 100'. The sewer line willexit the ADU at approximately g8'. CBO lnc. should be notified of
any discrepancies or problems with grade elevations of proposed components during installation of the
OWTS.
*Elevations are based upon standard
installation due to site conditions.
installation practices. Component elevations may change during
The 4-inch diameter, SDR-35 sewer line exiting the residence must have a double-Sweep clean out and a
minimum 2o/o grâde to the septic tank.
The system installation will include a 100O-gallon, two-compartment Valley Precast concrete septic tank
with an Orene@ Biotube Pump Vault and an Orenco@ PF3005 pump in the second compartment of the
septic tank. The floats should be set to dose approximately 70 gallons each pump cycle, allowing
approximately 3 gallons of drain back afrer each pump cycle. A pump curve is enclosed. The control panel
for the pump must be located within line of sight of the septic tank. lfle recommend Valley Precast out of
Buena Vista be contracted for start-up of the pumping system.
Approximate horizontal distance 5' / min. tall2% I
min. 1.2ð" fall
Primary Tank lnlet lnvert
Approximate horizontaldistance 32' I min 1o/o rise I
min. 4" rise for drain back ¡ntg septic tank
lnfiltrative Surface
Page 5
Effluent will be pumped through a 1.5-inch diameter pump line to a level 1.5-inch diameter manifold. The
manifold will connect three laterals on a 12' x 38.5' bed. A minimum of 2-feet of sand filter material will be
installed ¡n the over-excavated footprint. Sand filter material must be clean, coarse sand, all passing a
screen having four meshes to the inch. The sand must have an effective size between 0.15 and 0.60 mm.
The uniformity coefficíent must be 7.0 or less. Material meeüng ASTM 33, for concrete sand, with three
percent or less fines passing 200 mesh sieve may be used. A gradation of the sand med¡a must be
submittod to this office prior to obtaining the sand.
Laterals must be 1.$inches in diameterwith 5/32-inch diameter orlfices facing down, spaced Z.S-feet on
center. Laterals used to disperse the effluent must be sunounded by washed coarsê screened gravel or
crushed stone, All of the gravel or stone must pass a 2 lz-inch screen and must be retained on at/¿-inch
screen.
Each 1,S-inch diameter lateral must end in a sweeping ell facing up with a ball valve for flushing, Valves
should be placed in a 10-inch sprinkler box for access. Laterals must be covered by a soil separation
fabric and at least 1-foot of topsoil or qther suikble soil able to support vegetatlve growth. lnspec{ion ports
must be placed at each cornor of each bed. Ports may be cut to grade and covered with a valve box for
access.
COlr¡l PONENT SPECIFICATIONS
The component manufacturers are typical of applications used by contractors and engineers in this area.
GBO lnc. must approve alternative components prior to ¡nstallätion of the OWT$. Requests muet
be submitted, in writing, to our off¡ce for approval prior to installation. Component technical data
sheets are available upon request,
Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, the
OWTS Permit provided by Garfield County Building Department, and this design.
Max = 78 gal. (300 GPD x25ø/o +
3 oaldrain back)
Min. 67 gal. (16 gal x 4) + 3 gal
drain back
Dose Range
80 gaflons/dose 3 gallons draln back (27 I 1.5
diameter oumo line)
Dose Setting
10.5' on/off float separationFloat Separation 1000 gallon Z-compartmet Valley
Precast concrete septlc tank
15.4 feet total dynamic head
ITDH}
Pump Criteria 30,5 gallons per minute (GPM)
COMPONENT MANUFACTURER MODEL NO.COMMENTS
$eptic Tank Valley Precast Item # 1000T-2CP-HH 1000-gallon,2-
mmpartment concrete
septic tank with HH pump
Pump Orenco@ PF30051 1 y.HP
120 Volt
Eiotube ProPaK Pump
Packaqe
Orenco@ tsPP3ODD yault, Filter, Gontrol uanel
ldemand dose)
Tank Risers and Lids Orenco@ f,ouþle-walled PVÇ rusers ancl
.ids (24" diameter)
f,rificê Shielde orencoc)42 orifice shields
Flushing Assembly Orenco@ 1.5" diameter (2) 45" or 90' long sweep only
(3 total)
Page 6
IN$TALLATION CONTRACTOR
CBO lnc. expêcts that the installer be experiencèd ãnd qualified to perform the scope of work outlined in this
design. The installer must review this design thoroughly and coordinate with our office in advance of
installation. Any additional conditions in this design or county permit must be completed and documented
prior to final approval of the OWTS installation. Communication between the installer and this office is
expected throughout the installation.
INSTALLATION OB$ERVATIONS
GBO lnc. mu$t view the QWTS during construction. The OWTS observation should be performed before
backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing
slphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours
in advance to observe the installation.
ln an effort to improve the accuracy of the record drawing, we request that the installer provide a
sketch of the lnstallation, Includlng path of the sewer llnçs, water llne lnetallatlon (if appllcable),
septlc tank location, STA location, and measurements from building corners or another fixed
objacts on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design
Packet. Photographs of the installation and final cover are also requested to supplement our installation
documentation.
REVEGETATION REQUIREMENTS
An adequate layer of good quality topsoll capable of supportlng revegetation shall be placed over the entire
disturbed area of the OWT$ installation. A mixture of native grass seed that has good soil stabilizing
characteristics (but without taproots), provides a maxlmum transpiration rate, and competes well with
successional species. No trees or shrubs, or any vegetation requiring regular irrìgation shall be placed over
the STA. Until vegetation is reestablished, erosion and sediment control measurês shall be implemented
and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation
@ver.
OPERATION INFORMATION AND TI/IAINTENANCE
The property owner shall be responsible for the operation and maintenance of each OWTS servicing the
property. The property owner ís responsible for maintaining service contracts for manufactured units,
alternating STAs, and any other components needing maintenance.
Geo.fabrics or plastics should not be used over the $TA. No heavy equipment, machinery, or materials
should be placed on the þackfilled STA. Machines with tracks (not wheels) should be used during
construction of the STA for better weight distribution, Livestock should not graze on the STA. Plumbing
fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a
running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA.
lf an effluent filter or scroen has been installed in the OWTS, we recommend this fltter or screên be cleaned
annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals be
flushed annually, or as needed.
The homeowner should purtp the septic tank every two years, or as needed gauged by measurement of
solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not
be placed into the OWTS, Grease should not be placed in household drains. Loading from a water softener
should not be discharged into the OWTS. No hazardous wastès should be directed into the OWTS.
Mechanical room drains should not discharge into the OWTS, The OWTS is engineered for domestic waste
only.
PageT
ADDITIONAL CONSTRUCTION NOTËS
lf design includes a pumpr weep holes must be installed to allow pump lines to drâin to mlnimize risk of
freezing. The pump shall have an audible and visual alarm notification in the event of excessively high-
water conditions and shall þe connected to a control breaker separâtê from the high-water alarm breaker
and from any other control sy$tem circuits. The pump system shall have a switch so ths pump can be
manually operatêd.
Excavatlon equipment must not drive in the excavation of the STA due to the potential to compact soil,
Extensions should be placed on all septic tank components to allow access to them from existing grade.
Backflll over the STA must be uniform and granular with no material greater than minus 3-inch.
LIMITS:
The design is based on information submitted. lf soil conditions encountered are different from conditlons
described in report, CBO lnc. should be notified. All OWTS construction muet be according to the county
regulations. Requirements not speclfied in this report must follow applicable county regulations. The
contractor should have documented and demonstrated knowledge of the requirements and regulations of
the county in which they are working. Licensing of Systems Contractors may be required by county
regulation.
Please call with questions.
Sincerely,
CBO lnc.Reviewed By:
(n r, tt* ttvtót'tg
Carla Ostberg, MPH, REH$Romeo A. Baylosis, PE
'. 10-31-2021
I
(J 6
l I
38S?3 añ.
Pump $election for a Pressurized $ystem. $tngle Family Residence Project
1800 Black Diamond Mine Road
Parametere
Dischargo Assembly Size
Transport Length
Transport Pipe Clâgs
Transport Line Síze
Distributing Valve Model
Max Êlêvation Lift
Man¡fold Lenolh
Manlfold Plpe Cla6ô
Man¡fold Pìpe Size
Number of LsterâlE per çoll
Latêral Length
Lateral Plpe Clasg
Leteral Plpè Eize
Orifice S¡z€
Orifics Spacing
Residual Heád
Flow Meter
'Add-on' Fríction Lo$es
incheÉ 300
250
Ctlculat¡ons
M¡nimum Flow RâtÊ per Or¡fice 0.68
ñumber of Orilic€s psr Zoñe 45
Totål Flow RateperZone 30.5
Number of Laterals per Zone 3
o/o Flow Difierentisl lsULâst Oriflce 0.8
fransport V€locity 4.8
100
Ftict¡onal Head Losses
50
1.25
31
40
1.50
Nono
2
I
40
1.50
3
36.5
40
1.50
5132
2.5
5
Nono
0
f€et
feet
feet
inches
inches
feet
¡nches
incheB
feet
f€ot
¡nches
feet
200
gpm
gpm
ç/a
fps
oolÀ
3êt-doo
(,,
c
adË*ô
s
Ê
0
fs€t
feet
féet
fget
feet
fset
f€et
150
0
PumpData
5 10 15 20 26
Net Discharge {gpm)
30 35 40
Loss through Dlscharge
Losg in Trånsport
Loss lhÌough Vatve
Loss in Mân¡fold
Loss in Laterals
Loss through Flowmêter
'Add{n' Friction Losses
Pipe Volumes
6.5
1.7
0.0
0.1
0.1
0.0
0.0
VÖl oi Trânsport Line
Vol oi Manlfold
Vol of LalerâlE per Zone
Total Volumê
3.3
0.8
11.6
15.7
gals
gáls
gals
gåls
Mlnimum PumÞ
FF3005 High Heåd Effuenl Pûmp
30 GPM, ,'i2HP
11512?0V 1Ø 6AHz,200V 3ø 60Hz
PF3007 High Head Effuent Pump
30 GPM,3/4HP
230v 1ø 60Hz,20o/4,60v 3ø 6OHz
PF3010 High Head Effuent Pump
3O GPM, 1HP
230V fø 60H2,200/460V 3Ø 60Hz
PF3015l'ligh Head Eñuent Pump
30 GPM, 1.1/2HP
230v 1ø 60Hz,2QOl23f,l460Y 3Ø 6oHz
Design Flow Rate
Tolâl Pynamic He6d
30.5 gpm
feet15.4
@ClnerrcoliYSì¡1:r*ìijt@
Iì
1
Sysìern Curve: -
Pump Curve:'-"
Pump Optimal Range: -
,ft
Opârstlng Point: v
o
Dêsign Po¡nt:
DRAWINGS MTISTBE USED INCONJUNCTION WITH DESIGÍ\¡LËTTER DATÊD 1ON7NÙ2130'Access EasementReception No. 844565Fenceroad centerlineCBO lnc.129 Cains LâneCabondde, Colorado t1623Phone 970.3095259carla.ostberg@gma¡l.comGravel DrivewayLINEÏPSTA1- JÈıIIIt/ìSTE PLANz-BEDROOMTllE LOCATiO|{ OF PROPOSED TMPRC}l¿Êlvl€lfIS S{OIVN ^RÉI\loT THE RËS¡,,LT OF A PROPERTY SURVEY" lHÊ LOCAIþNSARÊ APPROXMATE, IT IS 1IIE TIOT,EOII'II.IERS, ÐUfY TOE¡.¡SI'RE AIL CONSTRUCÍION ANÐ IMPROVEÍ{E}IT LOCATIONSARE ACCI RATE. PROFERTY Lll-GSÆ{D SETBACKû|STÁNCESSHC{,T"O SÊ CONFIRMED PRIOR TO ÊXC'qVÀIION. SCALEDFOR PRlNflN6 O{i¡ 11'X 17'P¡cPËR.PondConklin ADU1800 Black Dlamond ùEnê RoadGarfieb County, ColoedoProjedNumber: C167210fi7rm21Drawnby: DDÞy: CBOþy: RBw1.0Sheet 1 0F 4Centerline of 20'WideHoly Cross Electrical AssociationRíght-of-Way EasementBook 498, Page 574SCALE: I - 50':{'Nì
CBOlrc,129 Cains LanêCarbondale, Cdorado 81 623Phone 970-309.5259cãla.osÉb€rg@gmail.corßTP2INSPECTION PORT ATCORNERS OF BEDSALE: l'= 20'.0'TP1FLUSHING VALVE ATEND OF EACH LATERAL20'12'x 38.5 PRESSURE DOSED, OVER-EXCAVATED,UNLINED SAND FILTER(MtN.2'ASTM C-33 CONCRETE SAND)(3) 1.5" DIA SCH-40 PVC LATERALSw&" DtA oRtFfcEs FActNG DowN,COVERED WITH ORIFICE SHIELDS1.5" DIA SCH-40 LEVEL MANIFOLDBM1FF1.5" DIA SCH-40 PUMP LINE.(MrN 1olo R|SE TO DRA|N BACK TO TANK)4'DIA SDR-35 SEWER PIPE.:]WITH DOUBLE-SWEEP CLEANOUT(MrN 2% FALL TO TANK)1 OOO.GALLON, 2.COMPARTMENT VALLEY PRECASTCONCRETE SEPTIC TANK WITH AN ORENCO PUMPPACKAGE IN THE SECOND COMPARTMENT.RISERS AND LIDS TO GRADE.2-BEDROOM ADU5'TPConklin AtlU1800 Blac¡( D¡amond Mine RoadGarfiekl Cûmty, CobradoPtc*rcl Number; C1672DaÞ: 1gl17l2ù21D€síglsdRwbwedby cBObÊ REDDDrawnby:w2.0Shæt2 OF 4
CBOIæ.129 Caiß LâneCaÈo¡daþ, Colorado 81623Phorre 970.309.5259carÞ.ostberg@gnail,comi? x 38-5' PRÊSSURE DOSED UNLlliF0sÂño FILTER (MrN. Z ASTM C-33coNc*ETE SANO)WÍrH ruFrËE 1.5"DtA SCf-¡40 PVC I-ATËRALS Wñt1 5¡32DrA oRlRcEs (wlÍH oRtFtcE SFilELD)FAC'{GOOWNAT2.S O.C.f .Y DTA SCI+40 PLS¡|P LINE$rlN 1% DR 'INBACK TO IANN:)1,5' ûlA SCH-4û LEVEL Íì¡|ANIFOLOFINISHED GRADEEIIO EACH LATERAL IN A 90" LO¡¡GSWEEPF.IG ELL FACNG UP WITH ÂBÂLLVALVE IiI A VAIVE BOXACCESSIELE ATGRÂЀ24" MrN.4" DIA SÐR-35 SÊl¡l/ER Lltl€(MlN 2% SLOPE rO ÌANK)I'{SPECTION PC'RT AT ËJ.cHCORNEROFÉEDORSAM) FORBEODIXG3" MtN-rMtN"//ISATTD FILTER PLAN\¿¡-------rFæ¡/ã IRENCH DETAIL\tt--rrrræf.5¡ D¡A SC$40PVCVALVESfflÐlAvALvE BOXWIH SECURËD ¡.JO1.5" PVC SLIP X MÂLEPIP€ TT,¡REÀDADAPTERWþAPI.5'DIAB¡d.LVALVEl|!'lH 5'3? DlA ORIFICËS FACINGDOW!\¡ AT 2.5 0.C. SISTÀLLORiFICE SHIELDS ON E]ACHORIFICEPORTATEÀCHCORNERFABRICON GRAVËLsAFrofBMIro'sEcomKs0EFFEffi SEcO.15-ùS musffiffiF@T<¡x Êrcs P^ssrc ffi 8ÉiÈg.o@AVEL F'ITER fi4EUAÀrF.t. 6-tNcH€s UNDÊR LÂTERAI,SMIN. ?.INCIIÊS ÕVER LATÊRALSÕ'XJ/1,""ror.r.u""*":å,iËåtri^H:J3"t.5" DtA SCH-40 PVCIONGSWEEP9C ELB@V1.5" ÐlA Sclt-4o PVCLATERAL/âSAM) ñLlm SECnoN\gr'-FiE/ FLUS}IING VALV€ DET¡\¡L\lr----'sndæ1'l't0LH¡N.Conklin AIIU1800 BlackDiarnond Mine RoadGarfield County, CdorâdoProlrct Number: C16?210t1712021by: CBOby: RBb)4 DDw3.0Sheet 3 0F 4
CBOkrc.129 Ca¡ns laneCarbondde, Cobrado 81623Ptþne 970.309.5259cdlå, ostbef g@gmail.comDESIGN2€ErrROOüAfX,(75 GPD x 2 PÊRSONS/BEDROOM¡2 B€DROOMSIÌ¡íÂSTEWATER FLOVr, : 300 GPDSTA TO WA"TER C€IJRSÊ50'N/ASTATOWEtr10û17ESTA TO HO{TSË202VSEPIIC TANK TO WA'ÊR COURSE50'NASEPTIC TAl\lKÍO I¡'gI5û186'HOUSÉ TO SEPTIC TAI{(5'5'OWIS COMPOlttEtlfrS ANDP}IYSICAI FEATTIRESMI.lttltuM RÊO{JIREDsËÎßÀckÁFPROXli,lAlË PROPOSEDSÊIBACKVALVEsleq¡ PVcBOX ATGRAOËDONOTGI.UEFINISHED EN¡OEeIT(9PËCTIOT{ P¡PETÀ¡{}iMIN- IOOO GALLONSUSÊ IOOùGALLON, TWo.COil¡PAR'IMENÍ CO¡¡CRËTÊ SEPTIC TANKWNH PUMPING SYSTEM IN 2NO COMPARTIIENÍSOIL TREATI\,ENT AREA (STA):LONG lÊRM ACCÉPTAI{CE RAIE {LTAR} r 0.65 G.¡U SFCALCULÀTED STA = Q/LTAR = 300 / 0.65 : 46 1 .5 SFPRESSURE DOSEÐ, OVER.EXCAVA'IED, Ui{JNEÐ SAND FILTER12 X 38.s',fXA HOTã DRILLEDsrAINTOTWO SOE$ OF PÞEFORìJçT¡T¡IATþN(BELOW SLtÊ ON CAP)ÌúÊD[AA INSPSC'IION PORT DETAI.\rr--ffirErSOIL PROFILE IEST PIT NO. 1SOIL PROFILÊ TEST PIT NO.2SOff- PROFIIE TËST PIT NO. 3012467IIloCLAY LOAI\¡I FILLROOTZONE OASÊR\¡ËÐMÊDIUI' EROWN CL,ÀY LOAMMÊÐIUM BRÛWNCLAY LOAMSLIP-ON PVCOONOTGLUÊMÉDIUM BROWN CLAYLOAMINSULATÊDÎRACERWREFSqSHED GRADELreÊNDþl ø.*FX ot*SEWER LINENO GROTJNÐWATËR OR BEDROû( ENCOUNIERËDDURING EXCAVATION//ìCI.EÁNOUT ffiTAlLS/ãSolLS LOG\rr--.........TrEnGonklin ÀÐU1800 Bhck Dlamond Mine RoodGadield County, ColoradöPtoþt Numbei: C1672Oale: 1fr1172ç¿1Desþned by: CBOReviev'/ed by; RBDrawnby: DDw4.0Sheet 4 0F ,l
10117¡21,8:48 AM
Summary
Account
Percel
Property
Address
Legal
Dorcript¡on
Acr€s
!åñd SqFt
TâxAreâ
Mill Levy
Subdlvision
Assessed Values
Assoss€d Yeår
Lãnd Assessed
lmprovement Assessed
TotalAis€ssed
Tax History
TaxYear
Taxes Billed
R0700tr2
239509300010
18OO BLACK DIAMOND MINE RD, GLENWOOD SPRINGS,
co 81ó01
Soction: 9Townshlp: 7 Range:89 SWSW4O ACRES
qPubl¡c.nèt - Garfield County, CO - Property Record Card: R070012
G)qPublic.net'* Garfi eld County, CO
40
0
t28
62.7430
V¡ewMäp
Owner
CONKLIN, ËRIC & MICAH
18OO BLACK ÞIAMOND MINE ROAD
GIÊNWOODSpR|NGS CO81óO1
Land
Unltlpe SINGIE ÊAM.RES.-LAND - 1112 (RESIDENTIAL PROPERTYI
Squ¡r€Feêt 0
Buildlngs
Bulldlng #
Units
BulldlngType
Âb¡tract Codes / (Property TVpël
Archltecturaf Style
Stor¡è¡
Främe
Actual Veår Bu¡lt
BaBêmentArêâ
Flnish Basement Area
Gro$ lvingAree
TotälHeatod &Ft
8èdrooms
Bâths
Heatlng fuêl
HaâtlntType
AirConditlonlng
Rooflypê
RoofCover
Actual Values
Asse3sêd Yèâr
Lând Actual
lmprovementActual
TotalActual
It
SFR
SINGLE FAM.RËS.IMPROVEMT'.12 12 (RË5IDËNTIAL PROPERTY)
1.SIRY/BSM
7
WOODFRAME
7990
7,20e
1,209
1,149
2,358
4
2.75
GA5
HOTWATER
NONE
GABLE
PRËFAB MET
2020
$2,s58.04
2ù21
$17s,000.00
ç3e2,5ÆÐ0
$5ó7,5¡lO.0O
202t
$12,510,00
$28,070.00
$40,580.00
2019
$2,5e2.72
20.20
$180,000.@
s390.2é0.00
9570AéO,@
2020
$12,870,00
$2/,e00.00
$¡to,77o.(x)
2018
$2A34.68
20t9
$1to,ooo,Ôo
$390,2ó0.00
$570,2ó0.00
2{79
$72,870.W
$27,900.00
$40,7'0,0ô
20t7
$2,43130
Click here to vtiglrylhçjêlh]lQI4llljg!.]þljbÉparcel oQ lLhe 6arfield Countv Treasurer's website'
Transfers
S¡leDåte DeedType RêcôptlonNumber
9/24/202t EASÊMENT e6443e
6tz4/202t ÊASÊMENT 95880ó
ót24t2o2r EASEMENT 9s880s
Book - Prge P¡ice
$o
$o
$o
Sale
https://qpubtic.schnêidêrcorp.com/Applícation.aspx?þplÞ=1038&LayerlD=22381&PageTypelÐ-4&PagêlD¡9447&Q:210714312&KeyValue=R070012 1t2
19117121,8:48 AM qPublic.nei - Garfield County, CO - Propedy Record Cardl R070012
s/20/2019
5t20/2019
LL/19t2013
2l2gt20o8
70/11./2AO2
70hu2ao2
ran/2042
9/5/2002
8/At9e3
3/13/L989
3/9/7989
3n/1989
9/t4t1987
5/20/1974
BARGAIN ANDSALE DEED
SPECIALWARRANTYDEED
EASÉMENT
GRANÍ DEED
QUITCLAIM DEED
WARRÀNTYDEÊD
POWEROFATTORNEY
POWEROFATTORNEY
QU¡T CIAIM OEED
WARRANTYDEED
QUITCTAIM ÞEED
EASEMENl
WARRANTY DEËD
WARRANTY DEED
92qr3?
ezosæ
9#61.
74,6_7
t??
6126!4
672643
612645
þ!?q42
457303
399.767
39e76P
399768
3858ó5
263093
1396-441
ß96-448
1396-444
7396-434
o87?-0467
075Q-05V2
0750-0576
075t-a374
072Þ0930
0459.0350
$o
$5ó3,000
$Ô
$o
$o
$¿lgz,5oo
$Ô
$o
$o
$55,0OO
$0
$o
$35,000
$47,500
No dâta âvellâble for the followlng modules: Photos, Sketches.
r:l¡¡t'trti Ì:t t*;r: ;lr:Ì:*,::ij.
-u-ssiPrive.cy.B.s-lisv
Ç-Þ-l.B"Plvac-v"J:!s!lçç
!psi-D¡-iE-tlpfp*aJ;.1AKQ9Z\J2:aLO-QAM Vci:rio¡r 2..:¡.1::"1
iJû\;rilled try
ß)fSå,¡'p^'dçl
https://qpublic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD:22381&PageTypelD=4&PagelÞ=9447&Q=210714312&KeWaluê=R070012 212
ÐqPuhlic.ngt'' Garfield County, CO
Overuiew
f
I
Account R070012
Number
Parcel 239509300010
Number
Acres 4
[andSqFt O
TaxArea 128
2019MillLevy 62.7430
Deveroæd bvGì Fsl,¡pldçr
Physical
Address
Owner
Addre¡s
18OO BLACK DIAMOND MINE RD
GLENWOODSPRINGS
CONKLIN,ERIC & MÍCAH
18OO BLACK DIAMOND MINE
ROAD
GLENWOOD SPRINGS CO 81ó01
2019Total Actual
Velue
Legend
Ü Parcels
Roadr
Parcel/Account
Numbers
Highways
- Limited Access
* Highway
'-'MajorRoad
Local Road
* MinorRoad
Other Road
RamP
.-- Ferry
PedestrianWay
Owner Name
r .: Lakes&Rivers
- CountyBoundary
Llne
g567,UD last2SalesDate Price
e/24/2021 $O
6/24/2027 $0
8tóo1
Date ûeeteú 1A/17/2027
LastDate Uploâded: 1O176/202X- 2:04Ð3 AM