HomeMy WebLinkAboutState Final Electrical Inspection Report
COLORADO STATE ELECTRICAL BOARD
1560 Broadway, Suite 1350
Denver, CO 80202
Inspection Report
Date Inspected: 05/10/2022
Permit #: 913503
Permit Holder: REEVES AND SONS ELECTRIC ANDREW REEVES PO BOX 1198 SILT 81652 Phone: (970) 876-0545 Fax: Email: kamehl@reeveselectric.com
Site: 003 St Finnbar Farm Carbondale, Garfield County,
Owner: Barrett Cyr
Status: Partial Inspection Type: Final NEW RESIDENTIAL
Inspector: Norman Feck 303-869-3442
Corrections:
1) 110.7, 210.70A2(2) Demonstrated the front porch lights now work. Back porch lights don't work
(grill ones are ok).
2) Blinds not installed. If this becomes the last correction item, this permit may be closed with a note
saying to obtain a permit for the mororized shade work.
3) 314.25 Floorbox covers back-ordered due to covid.
4) 200.6A, 310.6A Grounded conductors # 6 or smaller shall be continuous white or gray. They may
have three white or gray continuous stripes on other than green insulation. At hot tub hook-up.
5) 300.12 Raceways shall be mechanically continuous between boxes, fittings, and enclosures. At hot
tub hook-up.
Comments:
The linked image cannot be displayed. The file may have been moved, renamed, or deleted. Verify that the link points to the correct file and location.