HomeMy WebLinkAboutOWTS Designl � 1-
/ /'� 5495
0*1
J r
r L
{ __4L
r
l 1 L7 1 i
1
1 55p1. '
I �
1 II i l
1 �
'y DWELLING FF EL=5509.0± f 1
{ I I
' INSTALL TWO-WAY CLEANOUT W/
RISER & CAP USE SCHD-40 OR
4" PVC SEWER PIPE @ 2%,
USE SCHD-40 OR 5DR-35
4" PVC SEWER PIPE TANK
INLET INV IN @ EL=5505.0±
INSTALL 2-COMPARTMENT 15O0-GALLON CONCRETE SEPTICTANK
(VALLEY PRECAST ITEM # 15OOt-2CP-HH) INSTALL WITH (2) 24" DIA. BY 24" DEEP RIBBED
PVC RISERS W/ LIDS AT THE SURFACE. INSTALL ORENCO SIMPLEX EFFLUENT PUMP
ASSEMBLY. (PVU57-1819-L) W/P300511 PUMP), W/ 1.25" DISCHARGE ASSEMBLIES.
1.5" PRESSURE EFFLUENT PIPE
OUTLET INV IN @ EL=5504.8±
1.5" TRANSPORT PIPE TO TEE CONNECTION
ON MANIFOLD AT HEAD OF THE TRENCHES 01
RECOMMENDED LOCATION OF OWTS PUMP CONTROL BOX
INSTALL PUMP CONTROL BOX IN LINE OF SITE WITH TANK
ELECTRICIAN TO PROVIDE CIRCUITS & WIRES FOR PUMPS & CONTROLS TO
CONTROL PANEL. ELECTRICIAN TO CONFIRM WIRE GAUGE SIZE &
COORDINATE INSTALLATION WITH PUMP SUPPLIER/ INSTALLER. 2
1 112" PVC SCHD-40 PERFORATED PIPE DISTRIBUTION LATERALS.
DRILL 5/32-INCH DIA. ORIFICES ON 3' CENTERS ALONG PIPE. (TYP.)
ORIENT ORIFICES UPWARD BETWEEN FIRSTAND LAST THAT WILL
BE ORIENTED DOWNWARD TO ALLOW LATERAL TO DRAIN. -
INSTALL SNAP 1.5" PVC DISTRIBUTION MANIFOLD (TYP.)
DISTR LATERAL ABSORP SURF EL=5505.0±
INSTALL4" RISER PIPE INSPECTION PORTAT
HEAD END OF EACH CHAMBER TRENCH (TYP.)
PRESSURE DOSED SAND FILTER TRENCH ABSORPTION/TREATMENT FIELD
INSTALL 525 SF OF SAND FILTER MEDIA IN 4 TRENCHES X WIDE BY 44' LONG. INSTALL
40 L.F. OF CHAMBER UNITS OVER THE 24" DEPTH OF SAND FOR USE AS SPRAY SHIELDS
THE SYSTEM SHALL BE PLUMBED FOR EQUAL PRESSURE DISTRIBUTION ACROSS THE
FOUR TRENCH'S PERFORATED DISTRIBUTION LATERALS. THE TOP OF SAND LAYER IN
EACH TRENCH SHALL BE INSTALLED ON LEVEL GRADE.
THE BOTTOM OF EACH TRENCH TO BE EXCAVATEDTO A MAXIMUM AVERAGE DEPTH OF
49INCHES BELOW THE EXISTING SURFACE GRADES, WITHIN THE NATIVE SANDY LOAM
SOILS & BACKFILLED WITH 24" OF CONCRETE SAND. A MINIMUM 12-INCHES OF COVER
TO BE BACKFILLED OVER THE TOP OF THE CHAMBER UNIT SPRAY SHIELDS.
1500 Galion Top team - ZCP
13W-2CP-M with Nigh Need Pump
Top
view
• �� • 7e arn: =rn•b. - 8.W0 •SI
gAtww l IF
>r'fJYl1i1YY�
a vre
7�
• .1 1. a eeeAl�a �I�,.ly pd j
den Ilh. w• t 20 ma I 4
rrwwa - -
..
1erR AYrd dlh 'lratrr yrbr to blip
w «Hlr-sr k'q galbn rIM
• F�ter• I.n Y eYe�
.1s LTbi1-OE M r�,Yrt[ �� 7E{'MMI.Yn
I.• �Ia CMWH. !ra•1 PW>M 1M•r .... YM
• � o Pr •wvt.a " �1 ice/
iFr of /�r
• i• Yvdnym awr aAih IYMM G�W ../�Y�
RLLOWA61F BURY
Te ) Tr
nlnr 1119E -
c-c r-a
r - r .• - o• Section
View
+AM
La taleffd_ da-i
• o9,ww r.Wrrn [wnw p•nK
L uv s .cei_ I�.r! OMMo-,. HH CepraAx "e� Wel�rl
15• Lmp S' 1•W IrNI CN LIN5 waln " of - Sld 151- Some LW Tm 1a 1
`6 Ede• F 1 N' as erT' 1W W Se 1= qA M7 W 15 9d NM I� 111M - 149M na
WioMID v�$T Imo. ALLEY 19 si 9i6
� wis■.wc +wrw.�
Muo■a Vista, cow
I �J
ELEC. RICAL SUPPLY V
TO ONTROLPANE
I NSTALE WIRES INC
Z0.0' 55fl8
h
l
_ CFOTI
- )(EtxfL - -
- bWT5 COMPONENT LOCATIONS
TO BE VERIFIED BY
CONTRACTORS -AN D_fiAk6ff*TTr
SSB6�
� a _ I.•r
1 ~
UIT
ma l
ELD PA TIAL ENVELOPE n
6" WATER LINE SLEEVE W/
SEALED CAPS BOTH ENDS i
j n _ l
rI A " IJIA. IRR. VAL BOX & EXTEND RISER W/ LID MI x `
Z" ABO FINISH GRADE P. EACH ROW END) x P
_- xEL
07 - XEL
INSTALL 1.5" FLUSH BALL VALVE ON END N LATERAL.
INSTALL ASSEMBLY B SPECTION PORT (TYP. END EA. ROW)
.�®:Ialii111I111111I11I1111111111111111I1
•
�
IIIi11i1i11i1111i1iIIi1Iil1I11111111i1i1
IIIi11i1111iilIIIIi11i11111I1111111111i1
IIIIIIi1111i1I11I1I1111111111111111111i1
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
IIIi11i11I1i1I1111i11i11111I1111111111i1
wm,IIIIIIIIIil1I11111I11111II11Il11II1I1
ifl:litIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
IIIIIIIII1IaIIIIIIIIIIIIIIIIIIIIIIIIIIII
IIIiIIIIIIlIliii;lIIIIIIIIIIIIIIIIIIIIIIII
�IIIIIIIIIIIIIiiI11f111IIIIIIIIIIIIIII
I�iiil"�Ii11IlIIIIIIIIIIIII11iIIIIIIIIIIIII
IIIi11i11fii11II11I11i11I1Ii1111111111i1
-
IIIi11i1111i11I11111111Ii11I1111111111i1
.IIIIIIIIIIIIIIIIIIIIIi111111I111�1111111I1
IIIi11i11I1i1111111i1i1I111I1►11111111i1
IIIIIIIIIIIIIIIIIIIIIll1I11►i1111111I11I1
wm{■IIiIIIIIIIIIIIIIiIIiIiI�l■1�IIIIIIIIIIII
IilIi11:1111I111111I11I1111l11►�IIICIIIIII
IIIIIIIIIIIiiii9alIIIIIIII11Ii1I►�IICIIIII
.IIIIIIIIIIIIIIIIIii:ilIIIII1111►111�11I11I1
IIIi11i1111i111111111.IIlIIIIIii111iIa1i1
IIIIIIIIIIIIIIIIIIIIIIIiriIIIIIII1aI11II1
IIIIIIIIIIIIIIIIIIIIIIIIIIIi�IIIIII►li1�I1
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIii11IIIl11►►1
-
IIIIIIi11I1����1i11i11111I11111111�1IS1
IIIi11I11I1i■I�Ii11i11I11I11111111I11�
-
ww■wweww■Iw■����0l�wew•�s���w�■■■��II11�
::::::::::
■■�■
m�■i11I11I11i11111111111I1
Vw
_
",_a� ,Crd� .."•':.�E�:�n �- ;:tom,,. 7e-� ..m„ ,.,...
COUNTY GIS AERIAL PROPERTY MAP
6" VALVE BOX
4" INSPECTION PORT
EXTEND 4" RISER PIPE
MIN, 3" THROUGH END
CAP OR CHAMBER PRE
FORMED PENETRATION
SECURE WITH SCREWS
THROUGH PENETRATION
FLANGE INTO PIPE
QUICK-4 INFILTRATOR
OR EQUAL Bi0 DIFFUSER
CHAMBER
INSPECTION PORT CONNECTION DETAIL
CROWN FIELD TRENCH TO SEED AND MULCH FINISH TOPSOIL SURFACE
DIVERT SURFACE WATER MAINTAIN SUITABL VEGETATIVE COVER
\\\ H
EXISTING GRADE € �.
UNDISTURBED EARTH ` 24'
SCREENED BACKFILL
NATIVE SOIL
INFILTRATING CHAMBER UNIT ( SPRAY SHIELD) \
QUICK-4 OR ARC-36 BIO DIFFUSER - CUSTUME PERFORATED PRESSURE PIPE
- WITH ORIFICES AT 12 O'CLOCK. SECURE
PRESSURE DISTRIBUTION PIPE CONNECTED _ PIPE WITH PUSH IN STAPLES
THROUGH END CAP TO CUSTOM PERFORATED
DISTRIBUTION LATERAL PIPE INTERMITTENT SAND FILTER LAYER EFFECTIVE
USE CONCRETE SAND-ASTM-33
MACHINE SETTLE AND LEVELTOP SURFACE
SCARIFY/TILL BOTTOM SURFACE AND
EXCAVATION SIDE WALLS NATIVE LOAMY SAND SOIL
NOTE:
THE INTERMITTENT SAND FILTER TRENCH MUST BE LEVEL. INSTALL CHAMBERS
WITH INLET AND END CAPS OVER SAND LAYERT FOR USE AS SPRAY SHEILDS.
INSTALL INDIVIDUAL DISTRIBUTION LATERALS TO THE HEAD OF EACH CHAMBER
TRENCH FROM A MANIFOLD CONNECTING EACH CHAMBER ROW. CUSTOM
PERFORATED PIPE TO BE LAID ON TOP OF THE SAND LAYER WITH ORIFICES
ORIENTED UPWARD EXCEPTTHE FIRST AND LAST ORIFICESTO BE ORIENTED
DOWNWARD. INSTALL A4" VERTICAL INSPECTION RISER FROM THE MOLDED
END CAP CUTOUT ON THE LAST CHAMBER IN EACH ROW. INSTALLA BALL VALVE
ATTHE END OF THE DISTRIBUTION LINE ACCESSIBLE FROM THE INSPECTION
PORT TO ALLOW FLUSHING OF THE LINE. THE VALVE IS CLOSED FOR NORMAL
OPERATION.
PRESSURE DOSET INTLRffITTENT SAND l IZTER
EREYVCH I1 / [. HAlYl EER SPWA i SHE1 L.DS
MURRAY OWTS DESIGN CALCULATION
The proposed residential structure has 3 bedrooms. The OWTS is designed for a maximum
4-bedroom capacity to serve potential future needs. Therefore based on the total peak design
capacity the maximum residential population is 7 persons.
From County adopted State Regulation 43, Design Flow Criteria: Minimum population is based on 2
persons per bedroom for the first 3 bedrooms = 6 persons and 1 person per bedroom for each
additional bedroom. Therefore: design population is 3 bedrooms x 2 persons+ 1 bedroom x 1 person
= 7 persons total.
Gallons per day per person =75 gal/person/day, No peaking factor
Design capacity = Max. Design flow (Qd)galIonsjday = (# of people) x (avg.
flow)gal/person/day.
+ -
Desi n flow Qd - 7 75 - 525 d
Q p g g
Septic Tank Design: 2-Day detention time = 525 x 2 = 1,050 gallons required.
Use a minimum 1,250 gallon two -compartment primary septic tank or for pressure dosed system
use a minimum 1,500 gallon two -compartment tank with a bio-tube high head pump dosing
assembly.
Sub Surface Conditions and Testing
A subsurface soil investigation and site assessment was performed by Sopris Engineering in on
February 4, 2022. The soils in the proposed field envelope area were sampled and characterized by
application of the USDA visual/tactile soil texture method analysis from samples in shallow hand dug
excavations and nearby embankment cuts. The shallow soils in these excavations were sampled,
observed and tested at 1, 2 and 3 foot depths.The soils below nil to 3 inches of topsoil consist of
medium dense gravelly sandy silt loam with scattered cobbles to 3 feet below the surface.
Two profile pits were excavated on site in support of the foundation design nearthe northwest and
southeast corners of the proposed building envelope. The medium dense soils observed from 1 to 7
feet in the NW test pit consists of loamy sand to sandy loam with some gravels. The medium dense
soils observed from 1 to 7 feet in the NE test pit Consists of sandy silt loam with some gravels and
cobbles. The primarily Type 2 soils in both pits have rock content less than 35%.
The native soils sampled from 1-3 feet below the surface near the proposed field are characterized
as a soil type 2 soil consisting of slightly gravelly sandy silt loam texture with moderate granular
structure containing approximately 30% rock content. This soil has an effective loading rate for
conventional soil treatment of 0.6 Gal/S.F./day for a level 1 conventional treatment system. The
equivalent percolation rate is assumed to be 10-20 minutes per inch. The soils become increasingly
rocky at depths below 5.5 feet. Soils below 5.5 feet are characterized as a USDA rocky soil R1 type 2
consisting of dense rocky sandy loam texture of granular structure with approximately40% rock and
gravel being less than 3/4 inch and containing less than 20% cobbles and small boulders in the sandy
loam matrix. In order to provide optimal treatment with respect to soil conditions, a pressure dosed
STA utilizing a 24-inch depth of filter sand media will be installed to provide for an enhanced
treatment level TL-3 system. No free water is expected to be encountered within the field
excavations. Groundwater levels are expected to be below 6 feet from the existing surface grades.
Additional observations and soil evaluation will be performed during construction prior to placement
of the distribution and sand filter media materials, by Sopris Engineering in the area of the proposed
treatment/absorption field and tank to inspect the soils and and provide installation guidance . The
soils will be further observed to determine the presence of any unsuitable soil or other Conditions in
orderto assist the contractor in installing the design material in the in -situ native soils. If any
adjustments to design or installation recommendations are necessary notice will be made to County
EHD and applicable revisions to design/Construction plans and report will be submitted. All
conditions and installations will be included in the As -Constructed documentation.
Sand Filter Trenches Treatment Unit/ Absorption System Design
The treatment/absorption field is designed based on utilizing the effective Long Term Acceptance
Rate (LTAR) for an intermittent sand filter treatment system utilizing pressure dosed distribution
laterals in trenches and gravelless Chamber units as spray shields.. The new treatment system will
consist of a fully pressure dosed sand filter treatment System with a 24-inch layer of filter sand
(ASTM-33, "washed ASTM-33 Concrete sand") in individual trench configuration.
Long Term Acceptance Rate (LTAR)
Considering the application of the new state regulation 43:
Receiving septic tank effluent, the treatment level for intermittent sand filters is considered TL3 for
the minimum 24" depth of treatment media with the upper infiltrative surface being at least 4-feet
above a limiting layer;
Maximum hydraulic loading rate forTL1 effluent applied to "Secondary Sand Media" in an unlined
sand filter is 0.8 gal./sq.ft./day, or the long term acceptance rate of the receiving soil Type 2 and or
R-1 forTL3 (1.1 gal./S.F./day) (Table 10-1 &10-1A) whichever results in the larger area.
The maximum Loading rate is therefore 0.8 gal./sq.ft./day
Loading factors; (Table 10-2, pressure dosed trench application = 0.8 }
A(sf) = Qd x LF1 = A = Area;
LTAR LTAR = 0.8 Gal/S.F./dayfor 2nd sand, ASTM-33, " Concrete sand"
Qd = flow (gal/day) = 525 gpd
LF1=0.8 pressure dosed trenches
A (sf )= 525 gpd x 0.8 = 525 S.F.
0.8 Gal/S.F./day
Excavate four 44' long by T wide trenches to a maximum N depth below finish grade. Backfill with
24-inches of ASTM-33, Concrete sand. Install a custom perforated 1.5-inch distribution lateral on top
of the sand layer in each trench and Cover with 8 Arc-36 biodiffuser chambers per trench for use as
pressure dose spray shields, as delineated on the plan.
The treatment field will be installed with a total of 4 perforated distribution laterals pressured dosed
bythe high head pump assembly in the second compartment of the the septic tank through a
transport pipe connecting to a common 1.5" manifold pipe with connections to head of each trench
distribution lateral. The septic tank effluent will be equally dosed through each individual 1.5"
custom perforated pressure distribution lateral running the length of each trench centered on top of
the sand filter material. Each trench will be constructed with 24-inches of washed filter sand below
the Chamber spray shields.
TESTING. INSPECTIONS AND CONSTRUCTION MANAGEMENT
1. ADDITIONAL ASSESSMENTS AND RECOMMENDATIONS WILL BE MADE BY THE ENGINEER
DURING INITIAL STAGES OF CONSTRUCTION TO VERIFY ASSUMPTIONS MADE FORTHE OWTS
DESIGN INCLUDING VERIFY THE AND STAKING OUTTHE LOCATON OF THE SEWER PIPING, PUMP
AND ENGINEERED FIELD.
2. PRIOR TO CONSTRUCTION OF THE PERMITTED SYSTEM THE ENGINEER SHOULD BE CONTACTED
BY THE PROJECT MANAGER/CONTRACTOR WELL IN ADVANCE TO PROVIDE ADEQUATE TIME TO
DISCUSS THE SYSTEM COMPONENTS WITH THE CONTRACTOR, ANSWER QUESTIONS, RESOLVE
ANY CONFLICT ISSUES AND SCHEDULE INSPECTION SITE VISITS BASED ON CONSTRUCTION
PROGRESS. A PRE-OWTS CONSTRUCTION MEETING WITH THE ENGINEER, SUPPLIER, THE
CONTRACTOR, ELECTRICIAN ANDTHE QUALIFIED INSTALLER 15 ESSENTIALAND REQUIRED PRIOR
TO INSTALLATION OF THE OWTS COMPONENTS. PRE CONSTRUCTION CONSULTATION
INSPECTIONS AND STARTUP BY QUALIFIED SERVICE PROVIDER.
3. REGULATIONS REQUIRE THATTHE DESIGN ENGINEERS OF RECORD PERFORM SITE INSPECTIONS
OF THE PERMITTED SYSTEM DURING CONSTRUCTION AND PROVIDE "AS -CONSTRUCTED"
DOCUMENTATION OF THE INSTALLED SYSTEM TO THE THE COUNTY LPHA AFTER
CONSTRUCTION IS COMPLETE. THE ENGINEER SHOULD BE CONTACTED AND NOTIFIED OF THE
CONSTRUCTION SCHEDULE TO PERFORM TIMELY INSPECTIONS PROVIDE DIRECTION TO
CONTRACTOR REGARDING THE INSTALLATION OF THE OWTS COMPONENTS AND AT LEAST48
HOURS PRIOR TO FINAL BACKFILL OF COMPONENTS.
4. THE COUNTY ENVIRONMENTAL HEALTH DEPARTMENT SHOULD BE CONTACTED AT LEAST 48
HOURS PRIOR TO FINAL BACKFILL OF COMPONENTS TO PROVIDE ADVANCED NOTICE OF
CONSTRUCTION SCHEDULE IN ORDER TO PERFORM A FINAL INSPECTION OF THE IN PLACE
COMPONENTS. The Garfield County Contact is: Ted White, P.E., Environmental Health Specialist
II I.Garfield County Public Health; twhite ftarfield-county.com, 970-945-6614 x 8106 (main
office) or 970-230-2442 (mobile)
S. CONTRACTOR SHOULD DISCUSS ISSUES REGARDING SPECIFICATIONS, INSTALLATION AND
OPERATION OF OWTS MECHANICAL SYSTEMS AND CONTROLS WITH THE MANUFACTURERS
REPRESENTATIVE AND/OR THE ENGINEER.
6. OUR DESIGN AND RECOMMENDATIONS ARE BASED UPON OUR EVALUATION OF THE EXISTING
AND PROPOSED SITE CONDITIONS, THE PREVIOUS PERMIT DOCUMENTS, THE DEVELOPMENT
PLANS AND INFORMATION SUPPLIED TO US BY OTHERS. IF DEVELOPMENT PLANS OR SITE
CONDITIONS ARE FOUND TO BE DIFFERENT FROM CONDITIONS ASSUMED OR INDICATED, WE
SHOULD BE NOTIFIED TO EVALUATE ANY EFFECT ON THE PROPOSED OWTS.
8. CONTRACTOR SHOULD REVIEW ANY CONDITIONS ON THE ISSUED PERMIT AND COORDINATE
WITH THE ENGINEER REGARDING CONSTRUCTION OF THE SYSTEM. IF YOU HAVE ANY QUESTION
OR NEED ANY ADDITIONAL INFORMATION, CALL THE ENGINEER, PAUL RUTLEDGE, SOPRIS
ENGINEERING, 9707040311.
GENERAL NOTES:
1. THE OWTS AS SHOWN ON THE PLAN AND DETAILS WERE DESIGNED BY SOPRIS
ENGINEERING.
2. THE PROPOSED LOT CONDITIONS BY SOPRIS ENGINEERING AND CLIENTS.
3. THE EXISITNG LOT CONDITIONS PER COUNTY GIS DATABASE, AERIAL MAPPING,
LIDAR TOPOGRAPHY AND SURVEY INFORMATION BY SURVCO, INC.
4. PRIMARY OWNER NAME & ADDRESS: MURRAY, EDWARD & CHERRI
PO BOX 551
NEW CASTLE CO 81647
"Eddie Murray" Eemurray@teampsm.CGms
970-948-1429 mobile
5. LEGAL SUMMARY: LOT 13, RAPIDS ON THE COLORADO.
6. SITE ADDRESS: 331 RAPIDS VIEW LN, NEW CASTLE CO. 81647
7. PARCEL NUMBER: 218104307013
S. CONTRACTOR:
9. GARFIELD COUNTY PERMIT #: SEPT-06-22-7597 ISSUED 06-24-22
ONTS SYSTEM NOTES
1. ALL MATERIALS AND INSTALLATION SHALL CONFORM TO STATE AND COUNTY ON51TE
WASTEWATER TREATMENT SYSTEM (OWTS) REGULATIONS.
2. ALL SEWER LINES TO BE 5DR-35 OR SCHEDULE 40 P.V.C. PIPE UNLESS NOTED
OTHERWISE.
3. INSTALLA TWO-WAY CLEAN OUT ON THE SERVICE LINE FROM THE BUILDING.
4. THE SEPTIC TANK SHALL BE INSTALLED LEVEL ON COMPACTED EARTH. INSTALL
WATERTIGHT RISERS AS NECESSARY TO BRING ALL REQUIRED ACCESS POINTS TO THE
FINISHED SURFACE GRADE. BACKFILL WITH SUITABLE NATIVE SOIL FREE OF BOULDER
AND ROCK IN EXCE55 OF 3" DIAMETER.
5. A SANITARY BAFFLE TEE IS REQUIRED ON THE SEPTIC TANK INLET AND SECOND
COMPARTMENT INLET. INSTALL THE INLET AND OUTLET TEES PLUMB AND IN A
POSITION TO ALLOW EASY INSPECTION AND MAINTENANCE OF TANK FROM THE
TANK RISERS.
6. THE SEPTIC TANKS SECOND COMPARTMENT WILL BE EQUIPPED WITH A BIO-TUBE
FILTER. THE FILTERS SHOULD BE INSPECTED EVERY SIX MONTHS. THE EFFLUENT
FILTERS SHALL BE MAINTAINED AND CLEANED WHEN THE TANK IS PERIODICALLY
PUMPED OR AS NECESSARY. INSTALL A SUITABLE EXTENSION ON THE FILTERS WITH
A HANDLE TO BE WITHIN 6" BELOW THE ACCESS LID.
7. THE CONTRACTOR SHALL ENSURE THAT THE SEWER LINES, SEPTICTANK AND RISERS
ARE WATERTIGHT. ALL PLUMBING FIXTURES AN D OWTS COMPONENTS SHALL BE
INSTALLED AND MAINTAINED TO AVOID SURFACE OR GROUNDWATER FROM
ENTERING THE SYSTEM AND TO PREVENT LEAKAGE FROM THE SYSTEM. IN-HOUSE
PLUMBING FIXTURES SHALL BE MAINTAINED TO PREVENT EXCESS WATER FROM
ENTERING THE SEPTIC SYSTEM.
8. THE DIMEN51ON5 AND NOTES SHOWN ON THE PLAN INDICATE MINIMUM AREA,
LENGTH, WIDTHS AND SEPARATION DISTANCES FOR THE ABSORPTION FIELD
COMPONENTS.
9. THE ABSORPTION /TREATMENT TRENCHES SHALL BE EXCAVATED TO LEVEL GRADE IN
NATIVE EARTH. THE BED BOTTOM AND SIDEWALLS SHALL BE SCARIFIED AND/OR
RACKED IF SMEARING OCCURS. IF EXCESSIVE LARGE COBBLES OR BOULDERS ARE
ENCOUNTERED IN ANY PART OF THE EXCAVATION OVER 6" FROM THE PROPOSED
TRENCH BOTTOM SURFACE, OVER EXCAVATE AND BACKFILL WITH SAND.
10. THE DISTRIBUTION PIPE LATERALS AND CHAMBER SPRAY SHIELDS SHALL BE
INSTALLED LEVEL OVER THE SPECIFIED DEPTH OF FILTER SAND WITH A MINI MUM
COVER OF 10 INCHES NOT TO EXCEED 24 INCHES.
11. SAND FILTER MATERIAL MUST BE CLEAN, COARSE SAN D, ALL PASSI NG A SCREEN
HAVING FOUR ME5HE5TO THE INCH. MATERIAL MEETING ASTM 33, FOR CONCRETE
SAND.
12. THE CHAMBER SPRAY SHIELDS WILL BE BACKFILLED WITH EXCAVATED MATERIAL
VOID OF ROCKS, THE BACKFI ILL MATERIAL SHALL NOT EXCEED 2 1/2" DIAMETER AND
SHALL BE PLACED TO AT LEAST 4 INCHES ABOVE THE TOP OF THE FIELD. A MINIMUM
2" DEPTH OF TOPSOIL IS TO BE PLACED ABOVE THE BACKFILL TO THE SURFACE & RE
VEGETATED.
13. THE TREATMENT ABSORPTION FIELD MUST BE GENERALLY MARKED ATTHE FOUR
CORNERS WITH INSPECTION PORTS. THE FIELDS MUST BE PROTECTED FROM
VEHICULAR TRAFFIC.
14. THE TRENCH ABSORPTION/TREATMENT FIELD SURFACES MUST BE SLIGHTLY
MOUNDED TO DIVERT SURFACE DRAINAGE AWAY FROM THE FI ELD.
15. THE TREATMENT FIELD SHALL BE INSTALLED PER THE REQUIRED SETBACK
DISTANCES:
10 feet from any property line.
25 feet from any potable water supply line.
MI N. 10 feet from any occupied dwelling.
100 feet from any well, spring or cistern.
50 feet from any stream or water course
EFFLUENT DISTRIBUTION SYS M NOTES
1. FILTERED EFFLUENT WILL DISCHARGE TO THE TRENCH LATERALS VIA A SI MFLEX HIGH
HEAD PUMP BIOTUBE DISCHARGE ASSEMBLY TO A COMMON MANIFOLD ATTHE
HEAD OFTHE STA TRENCHES THAT CONNECTS TO THE DISTRIBUTION LATERALS.
2. THE DISTRIBUTION SYSTEM WILL BE INSTALLED TO ALLOW FOR EFFLUENT TO BE
EQUALLY DISTRIBUTED ACROSS THE ABSORPTION SURFACE IN EACH TRENCH VIA
INDIVIDUAL CUSTOM PERFORATED FULL PRESSURE DISTRIBUTION LATERALS
CONNECTEDTOTHE MANIFOLD PIPE ATTHE HEAD OFTHETRENCHES INSTALLED ON
TOP OF THE SAND MEDIA SURFACE ALONG THE ENTIRE LENGTH OF THE INDIVIDUAL
TRENCHES. A BALL VALVE WILL BE INSTALLED ON THE TERMINAL END OF EACH
DISTRIBUTION LATERALCENTERED BELOW AND HOUSED IN A VALVE BOX WITH LID
SET 2" ABOVE SURFACE GRADES.
3. THE MINIMUM SLOPE OF THE TRANSPORT PIPE FROM THE TANK'S DOSING
28377
r�9 07. 2023 ' .
id s• , ... • §
w
d
U
J
J
Z
W
LJJ
Z
(51
f ,Z
W
w
d
Q
m I a_
Z
0
w
Ir
0 I ,r.
Z o
07 00
❑ } ❑ in w
Z
Z
U
it cr 2
❑ ❑ 0
Ln
Z
J
CI'1
U
J
J
c+m
N
LU
-
W 0 r o
F_ C?
N LLI -t r,;
J CD
Z r- C
CD Cn
❑ --- M
�Zr_
o'l0�
o M
IL
0
COMPARTMENT TO THE MANIFOLD SHALL BE INSTALLED AT A MINIMUM 2.5%
Q
UPWARD SLOPE TO ALLOW FOR DRAINBACK TO THE PUMP VAULT.
a
ELECTRICAL NOTES (Typ omw JPuvp Amy
0 <
LJJ
1. AN ORENCO SYSTEMS CONTROL PAN EL5 SHALL BE IN5TALLED BY A ELECTRICIAN IN
Q
COORDINATION WITH THE CONTRACTOR AND THE TREATMENT SYSTEM
SUPPLIER/SERVICE PROVIDER. ELECTRICIAN TO PROVIDE ELECTRIC SERVICE FOR
0
U)
SPECIFIED VOLTAGE RATING OF PUMP(5) AND CONTROLS. THE POWER SUPPLY FOR
0 [�
THE PUMP(S) AND CONTROLS SHALL CONSIST OF A 20 AMP DOUBLE POLE CIRCUIT
FOR EACH PUMP AND 10 AMP SINGLE POLE CIRCUITS FOR CONTROLS. PANELS TO BE
INSTALLED IN LINE OF SITE WITH TANK AND OR PUMP BASINS.
LPL/
w
2i
2. THE ELECTRICIAN SHALL INSTALL ELECTRICAL SUPPLY WIRE IN CONDUIT FROM A
ELECTRICAL SERVICE CIRCUIT BREAKER BOX TO THE EXTERIOR WALL OR REMOTE
i 1
LJJ
Z
w h
0-
SUPPORT MOUNTED ORENCO CONTROL PANEL LOCATED NEAR AND N LINE OF SITE
= 0
W
WITH THE TANK RISERS.
0
0
3. THE SYSTEM QUALIFIED INSTALLER SHALL INSTALL ELECTRICAL DIRECT BURY WIRES
Z J
FROM THE CONTROL PANEL TO THE EFFLUENT PUMP ASSEMBLY'S (IF APPLICABLE)
LJ-J
0
LJJ
JUNCTION BOXES ON THE RESPECTIVE TANK ACCESS RISER. INSTALL COLOR CODED
OR
LABELED WIRES PER CONTROL PANEL DIAGRAM. INSTALL ALL WIRES FOR PUMP(5)
Cn
AND CONTROLS WITH CONDUIT SEAL AT THE SPLICE BOX. ELECTRICIAN TO
COORDINATE W/ SYSTEM INSTALLER. FOR PUMP AND CONTROL INSTALLATION.
❑ <r
INSTALLATION CONSULTATION BY VALLEY PRECAST, INC.
a.VA
w
<
U)
C�
G
J
r
�
V
U)
J
W
�
Z
DATE: 02-23-2023
REVISED OWTS DESIGN/CONSTRUCTION PLAN 03-07-23 JOB NO. 32019.01
G:\2022\32019 Murray-RapidsjCIVIL\Civil DWGsyDE\32619-0E-OWTS-V2 Site.dwg SHEET C1 .0
SEPTIC DOSING TANK DETAIL