HomeMy WebLinkAboutOWTS Engineers Report129 CAINS LANE CARBoNDALE,CO A16,23 970.309.5259 CAR t.A. OSTBER G@GMAÍ L. C O M ST'PT IC COF¡SIJL'TIF¡ GI November 2,2022 Project No. C1723 Glynna Baker olvnna@qlynnabaker.com Subsurface lnvestigation and Onsite Wastewater Treatment System Design S-Bedroom Residence 360 Cerise Ranch Road Garfield County, Colorado Glynna, CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 40.748-acre property is located outside of Carbondale, in an area where OWTSs are necessary. Legal Description: Section: 32 Township: 7 Range: 87 Subdivision: CERISE RANCH SUB-DlV. Lot: 52 PHASE 140,748 ACRES Parcel lD: 2391 -321 -02-052 SITE CONDITIONS The property is currently undeveloped. A 5-bedrooms residence is proposed The residence will be served potable water from a community water system. The water line is indicated on the site plan and will enter the residence from the west. The water line will be at least 1O-feet from the septic tank and at least 25-feet from the soiltreatment area (STA). The proposed soiltreatment area (STA) location has an approximate twenty percent slope to the southeast. The proposed area vegetated with native grasses and trees. There should be no traffic or staging of material over the future STA site to avoid compaction of soils prior to construction of the STA. SUBSURFACE The subsurface was investigated on April 26,2022 by digging three soil profile test pit excavations (Test Pits). A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.l The materials encountered in Test Pit #1 consisted of light brown silt clay loam topsoil to 2.S-feet, underlain by tan, dense, calcareous clay matrix with white, angular rock up to 1-foot in diameter (less than 35% volume) to a maximum depth explored of 7.0-feet. No bedrock or groundwater was encountered. ' Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page2 The materials encountered in Test Pit #2 consisted of light brown silt clay loam topsoil to 3.O-feet, underlain by tan, derìse, calcareous clay matrix with less rock than Test Pit #1 to a maximum depth explored of 7.O-feet. No bedrock or groundwater was encountered. The materials encountered in Test Pit #3 consisted of light brown silt clay loam topsoil to 8-feet, underlain by tan, calcareous clay matrix to a maximum depth explored of just below 8.O-feet. No groundwater or bedrock was encountered. A sample of the soils was taken from Test Pit#2 aI approximately 3-feet below grade. Soil structure grade was moderate. The soil formed a ball and a ribbon approximately 1-inch in length before breaking. Soil structure shape was blocky and consistence was firm. Soil texture was both gritty and smooth. A sample of the soils was taken from Test Pit #3 at 3-feet below grade. Soil structure grade was moderate. The soil formed a ball and a ribbon between 1 and 2-inches in length before breaking. Soil structure shape was blocky and consistence was firm. Soil texture was smooth. Kumar and Associates evaluated the soils for the foundation design and documented their findings in a report dated July 21,2021, Project No.21-7-249. A gradation was performed on a sample from Boring 1 at 8' and 13' below grade. The gradation results were as follows: 22o/o Gravel 31% Sand 47% Silt and Clay Based on this our observations of the soils in the three test pits and Kumar's gradation, STA sizing is based on Soil Type 2A. A long term acceptance rate (LTAR) of 0.5 gallons per square foot will be used to design the OWTS. Soils transition to a deeper (silt clay loam) topsoil horizon further down the hill to the southeast. The infiltrative area must be installed on the tan, calcareous clay matrix horizon, no deeper than 4-feet below native grade. L:-.,- -l ?--¡ ñ:4-vtew ut te!'t rtls Page 3 Test Pit #1 Test Pit #2 Page 4 Test Pit #3 backfill Sieved sample from Test Pit #2 Ribbon approx. f -inch in length Page 5 Sieved sample from Test Pit #3 View of Test Pits Ribbon between 1and2 inches Test Pit #1 Backfill Test Pit #2 _t Page 6 Test Pit #3 View of all Test Pits DESIGN SPECIFICATIONS Desiqn Calculations: Average Design Flow = 75 GPD x 2 people/bedroom x 3 Bedrooms + 150 GPD (4th and 5n bedrooms) = 600 GPD LTAR = 0.5 GPD/SF 600 GPD / 0.5 GPD/SF x 1.0 (gravity trenches) x 0.7 (chambers) = 349 5t The new OWTS design is based on 5-bedrooms. An average daily wastewater flow of 600 GPD will be used. PageT For the purposes of this OWTS design, Benchmark Elevation has been established as 6560' 7 /o" as Finished Floor (FF) elevation of the lower level. CBO lnc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. *Elevations are based upon standard OWTS installation practices. Component elevations may change during installation due to site conditions. Minimum grade refers to piping between components. The 4-inch diameter SDR-35 sewer line exiting the residence must have a double-sweep clean out and a minimum 2Yo grade to the septic tank. The system installation must include a 1500-gallon, two-compartment lnfiltrator@ poly septic tank with an effluent filter on the outlet tee. Risers must bring the manhole lids to grade for access. lf more than one riser is added to the septic tank, an extension handle must be installed on the effluent filter. Effluent will gravity flow to a distribution box, and then to five gravelless chamber trenches. The distribution box must be accessible from grade and must have flow equalizers, or similar product, installed on each outlet pipe in the distribution box to assure equal flow to each trench. Each trench will consist of 14'Quick 4' Standard Plus lnfiltrator@ chambers for a total of 70 chambers and 840 square feet of infiltrative area. There must be at least 4-feet of undisturbed soil between each trench. Soils transition to a deeper (silt clay loam) topsoil horizon further down the hill to the southwest. The infiltrative area must be installed on the tan, calcareous clay matrix horizon, no deeper than 4-feet below native grade. lnspection ports must be installed at the beginning and end of each trench. Ports may be cut to grade and placed in sprinkler boxes for access. COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area. GBO lnc. must approve alternative components prior to installation of the OWTS. Requests must be submitted, in writing, to our office for approval prior to installation. Component technical data sheets are available upon request. Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. OWTS Gomponent Minimum Elevation Primary Tank lnlet lnvert Approximate horizontal distance 27' I min.2% fall I min. 6.75" fall Distribution Box Approximate horizontal distance 25' I min. 1% fall I min. 3.125" fall lnfiltrative Surface Approximate horizontal distance to furthest trench 44' I min. 1o/o lall / min. 5.5" fall GOMPONENT MANUFACTURER MODEL NO.COMMENTS Septic Tank nfiltrator@ Item # 1530-2CP 1500-gallon, 2- :omoartment seotic tank Risers and Lids Orenco@ Double-walled PVC ¡isers and lids Effluent Filter Orenco@ 4-inch diameter Full size Distribution Box Polylok Distribution box, lids, rises, and (5) flow equalizers chambers lnfiltrator@ standard Plus 70 'Quick 4' Page 8 INSTALLATION CONTRACTOR CBO lnc. expects that the installer be experienced and qualified to perform the scope of work outlined in this design. The installer must review this design thoroughly and coordinate with our office in advance of installation. Any additional conditions in this design or county permit must be completed and documented prior to final approval of the OWTS installation. Communication between the installer and this office is expected throughout the installation. INSTALLATION OBSERVATIONS CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours in advance to observe the installation. ln an effort to improve the accuracy of the record drawing, we request that the installer provide a sketch of the installation, including path of the sewer lines, water |ine installation (if applicable), septic tank location, STA location, and measurements from building corners or another fixed objects on the propefi. This sketch is most easily provided on Sheet W2.0 of the OWTS Design Packet. Photographs of the installation and final cover are also requested to supplement our installation documentation. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing fìxtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned onn¡ lallrr nr ac naarlar{ lf fha ôl^/Te ¡anoiafc nf a nraccr rriza¿.| nr ¡mn cr¡cfam r^râ rô^^mmanÀ tlra lafarala harÙro(ù vr q ¡/r99svrr49v yvrrrlJ 9rùlvrrr, YYg r9vvrrilrr9rrv lr19 lq(grqro wv flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OWTS, Grease should not be placed in household drains, Loading from a water sofiener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. Page9 ADDITIONAL CONSTRUCTION NOTES lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high- water conditions and shall be connected to a control breaker separate from the high-water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. LIMITS: The design is based on information submitted. lf soil conditions encountered are different from conditions described in report, CBO lnc. should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, CBO lnc. &rj,[a- tstfung Carla Ostberg, MPH, REHS /-/CBO lrc.129 Cains LaneCarbordale, CDlorado 81 623Phone 970.309.5259caf ia.ostberg@gmail.æmIFOR PRINTING ON 1 1' X 17' PAPER.360 Cerise Ranch RoadGarfield County, ColoradoProjectNumber: C1723Baker/Obleski ResidenceDale: 11!O2n022Designed by: CBODrawn by: DDw1 .0Sheet I 0F 4L=fi,=4sLsTji3EXTSTTN6CIZüÆUJ,AYTTLAT 5JNffiSCALE: 1 = 50'=0" CBO lnc.129 Ca¡ns LaneCarbondale, Colorado 81 623Phone 970.309.5259ærla.ostberg@gmail.æmu"""---- 6560'71', >5-BEDROOMRESIDENCELOWER LEVEL FF360 Cerise Ranch RoadGarfield County, ColoradoProjectNumber: C1723Baker/Obleski ResidenceDate: 1110212022DrawnDesignedby:by: CBODDSheet 2 0F 4w2.0N4' DIA SDR.35 SEWER PIPE WTH CLEANOUTMIN 2% FALL TO TANKSCALE: '1" = 20L0"------TWO.COMPARTMENTSEPTIC TANK WTH EFFLUENT SCREEN- - WATER LINE4'DIA SDR-35 SEWER LINE TO STA(MrN. 1% FALL TO STA)---t9?-DISTRIBUTIONBOXWITH ACCESS AT GRADE--t----1p--/-\.4" DIA SDR-35 INSPECTION PORTATBEGINNING AND END OF EACH TRENCH-¿¿"¿+,.4' DIA SDR-35 SEWER L¡NE TO EACH TRENCH(MlN. 1olo SLOPE TO TRENCH)a'aat'QUICK4' CHAMBER TRENCHES.5 TRENCHES WITH I CHAMBERS PER TRENCHFOR A ÏOTAL OF 70 CHAMBERS AND 840 SF.t--------_rP2-'6550TP3+-ttt'\------___¡r65110''---------t-¿-- CBO |rc.l29Ca¡ns LaneCarùondale, Colorado 8l 623Phole 970.309.5259cãla.ostberg@gmail.comÇ4' DIA SDR-35 DISTRIBUTIONLINE TO EACH TRENCH(MtN_ 1% SLOPE TO TRENCH)INFILTRATÐREND PTATE'outcK-4'4" DIA SDR-35EFFLUENTPIPE FROMSEPTIC TANKCHAMBÊR (4 x 3')NOTE: INFILTRATIVEAREA TO BE INSTALLED ONCALCAREOUS CLAY MATRIX HORIZONDISTRIBUTI.]N BOX W|THDIA SDR-35AI GRADEINSPECTIONPORT4' maxLSOILz',PLACED IN4'TOP PORT CFCHAMBER ENDPLATESLIMITEXCAVATION'QUICK-4'SCARIFYCHAMBER (4' x 3')nÁ sDÊ-35 TNSPECïONDIA SDR-35 DISTRIBUTIONPORT AT EEGINIÚNG ANDEND OF EÂCH TRÉNCHPIPES TO ADDITIONALTRENCHES(5 TOTAL TRENCHES)ÃCHAMBER TRENCH SECNON\rr--ïÌræF¡NISHED GRADESMALL VALVE COVERBOX OR IRRIGATIONVALVE BOX AT GRADE24'MtN.BOX AND COVER BRICUGHT TO GRADECONCRETE LID-1\CAP OR THREADEDCLEANOUT ASSEVBLY4" DIA SDR-35 SEWER LINE(MtN 2olo SLOPE TO TANK,MIN. 19lO TO STA)Fll.¡SHEDGRADECOMPACTBASE TO SUPPORTBOX4" PVC PIPE CUTTOFITSCREENEDUSE I-IOLE SAVYTOCUT THRUTCPOFOR SAND FORBEDDING3" MlN.BAFFLE ORANGLED PIPETO BE USEDEND8'MlN.AT INLET/lINSPECTON PORT IN CHAMBER\:/ ror D $G/.\ DISTRIEUÎON BOX DET\9r-Er1AIL,I 4 CI-IAI¿BERS PER TRENCHOUTLETSoooo l[=Baker/Obleski Residencel}a.c¡: 11roz2o22lo""¡sn"o ov' caolDrawn bv: DD360 Cerise Ranch RoadGarfield County, ColoradoProjectNumbec C1723w3.0Sheet 3 0F 4 CBO lnc.129 Ca¡ns Lanecarbondale, Colorado 81 623Phone 970.309.5259ærla.ostberg@gma¡l.com5.BEDROOI' RESIDENCE75 GPD x 2 PERSONS/BEOROOM x 3 BEDROOMS + 150 GPD (4th and sthBEDROOMS)WASTEWATER FLOW = 600 GPDSTA TO WATER COURSE50,STA TO WELL100'STATO HOUSE20'44'.SEPTIC TANKTO WATER COURSE50'NI/ASÊPTIC TANK TO WELL50'N/AHOUSE TO SEPTIC TANK5',13'OWTS COMPONENTS ANDPHYSICAL FEATURESMINIMUM RËQUIREDSETBACKAPPROXIMATE PROPOSEDSETBACKTANK:MIN.15OO GALLONSUSE 1sOO,GALLON, TWO-COMPARTMENT POLY SEPTIC TANKSOIL TREATMENT AREA (STA):LONG TERM ACCEPTANCE RATE (LTAR) = 0.5 GAU SFCALCULATED STA = C/LTAR - 600 / 0.5 = 12OO SFGRAVITY, TRENCHES = 1200 SFX 1.0 = 1200 SFCHAMBERS = 1200 SF x 0.7 = 840 SF / 12 SF / CHAMBER = 70 CHAMBERSFIVE GRAVELLESS CHAMBER TRENCHES,I4 'OUICK 4' CHAMBERS IN EACH ÎRENCHTOTAL 70 'OUICK 4' CHAMBERSSOIL PROFILE TEST PIT NO. 1SOIL PROFILE TEST PIT NO. 2SOIL PROFILE TEST PIT NO. 301LIGHT BROWN SILT CLAYLOAM TOPSOILLIGHT BROWN SILT CLAYLOAM TOPSOILLIGHT BROWN SILT CLAYLOAM TOPSOIL2JSLIP-ON PVCTAN, DENSE, CALCAREOUS CLAYMATRIXW|TH WHITE, ANGUI.AR ROCKAPPROX. 1.FOOT IN DIAMETERTAN, DENSE,CALCAREOUS CTAY MATRIXDO NOTGLUE4INSUTATEDTRACER WIREFINISHED GRAOEIFIUô4" DIASEWER L¡NE7II10NO GROUNDWATER OR BEDROCK ENCOUNTEREDDURING EXCAVATIONTAN, DENSE,CALCAREOUS CLAY MATRIXTO TANKASOILS LOG\7LEGEND?s s¡lt dayaloam top$il€lcareous clay matrixrãCLEAN OUT DETAII\r,---æBaker/Obleski Residence360 Cerise Ranch RoadGarfield County, ColoradoProjectNumber: Cl723Dale: 111O212O22Designedby: CBODDDrawnby:w4.0Sheet 4 0F 4 þ tGrtiffififfiffii':,Íñ** An Employcc Ouncd Gompony 5020 County Road 154 Glenwood Springs, CO 81601 phone: (970) 945-7988 fax: (970) 945-8454 email : kaglenwood@kumarusa,com www.kumarusa.com Office Looations: Døwø (HQ), Pa*er, Colorado Springs, Fort Collins, Glenwood Springs, and Sunmit County, Colorado SUBSOIL STUDY FOR FOUNDATION DESIGN PROPOSED RESIDENCE AND ADII LOT 52, CERISE RANCH 360 CERISE RANCH ROAD GARFIELD COUNTY, COLORADO PROJECT NO.2t-7-249 JULY 2t,2021 PREPARED FOR: GLYNNA BAKER P.O. BOX s748 FRTSCO, COLORADO 80443-5748 elvnna@elvnnabaker.com TABLE OF CONTENTS PURPOSE AND SCOPE OF STUDY PROPOSED CONSTRUCTION SITE CONDITIONS........ SUBSIDENCE POTENTIAL FIELD EXPLORATION ......... SUBSURFACE CONDITIONS FOUNDATION BEARING CONDITIONS DESIGN RECOMMENDATIONS .................... FOUNDATIONS FOUNDATION AND RETAINING WALLS FLOOR SLABS....... UNDERDRAIN SYSTEM SITE GRADING........ SURFACE DRAINAGE PAVEMENT SECTION LIMITATIONS...... FIGURE 1 - LOCATION OF EXPLORATORY BORINGS FIGURE 2 - LOGS OF EXPLORATORY BORINGS FIGURE 3 - LEGEND AND NOTES FIGURE 4 - SWELL-CONSOLIDATION TEST RESULTS FIGURES 5 and 6 - GRADATION TEST RESULTS TABLE 1- SUMMARY OF LABORATORY TEST RESULTS _1- 1 a-L- a-J- ..............-2 - _?- _L- _5- 4 4 6- 6- 7^ _7 - .-8- _l - Kumar & Associates, lnc. @ Project No. 21-7-249 PURPOSE AND SCOPE OF STUDY This report presents the results of a subsoil study for a proposed residence and ADU to be located at Lot 52, Cerise Ranch, 360 Cerise Ranch Road, Garfield County, Colorado. The project site is shown on Figure 1. The purpose of the study was to develop recommendations for the foundation design. The study was conducted supplemental to our agreement for geotechnical engineering services to Glynna Baker dated March 5,2021. We previously conducted a geotechnical review of the subject site for driveway and utilities and presented our findings in a report dated March 17,2021, Project No.2l-7-249. A field exploration program consisting of exploratory borings was conducted to obtain information on the subsurface conditions. Samples of the subsoils obtained during the fîeld exploration were tested in the laboratory to determine their classification, compressibility or swell and other engineering characteristics. The results of the field exploration and laboratory testing were analyzed to develop recommendations for foundation types, depths and allowable pressures for the proposed building foundation. This report summarizes the data obtained during this study and presents our conclusionso design recommendations and other geotechnical engineering considerations based on the proposed construction and the subsurface conditions encountered. PROPOSED CONSTRUCTION The proposed main residence will be a two or three-story structure over a walk-out basement level with an attached garuge. The proposed ADU will be a one or two-story structure over a walk-out basement level. Ground floors will be slab-on-grade. Grading for the structures is assumed to be relatively minor with cut depths between about 5 to l0 feet. An asphalt paved driveway is proposcd to acccss thc proposed building sites from the southwest and along the existing rough graded road from Cerise Ranch Road. We assume relatively light foundation loadings, typical of the proposed type of construction. If building loadings, location or grading plans change signifîcantly from those described above, we should be notified to re-evaluate the recommendations contained in this report. SITE CONDITIONS The subject site is currently vacant, There is a rough graded road that accesses the builcling area along the southcm property line from Cerise Ranch Road and clirnbs up around to the north Kumar & Associates, Inc. @ Project No. 21-7-249 -2- along the western property line. Topography at the site consists of hillside terrain with slopes around 10 to 20 percent in the area of the proposed driveway, residence, and ADU. Slopes of up to about 60 percent are present on the lot north of the building areas not planned for development. Vegetation at the site consists of native grass and weeds, sage brush, juniper, and pinon. SUBSIDENCE POTENTIAL Bedrock of the Pennsylvanian age Eagle Valley Evaporite underlies the subject site. These rocks are a sequence of gypsiferous shale, fine-grained sandstone and siltstone with some massive beds of gypsum and limestone. There is a possibility that massive gypsum deposits associated with the Eagle Valley Evaporite underlie portions of the lot. Dissolution of the gypsum under certain conditions can cause sinkholes to develop and can produce areas oflocalized subsidence. During previous work in the area, several sinkholes were observed scattered throughout the Cerise Ranch development. These sinkholes appear similar to others associated with the Eagle Valley Evaporite in areas of the lower Roaring Fork River valley. Sinkholes were not observed in the immediate area of the subject lot. No evidence of cavities was encountered in the subsurface materials; however, the exploratory borings were relatively shallow, for foundation design only. Based on our present knowledge of the subsurface conditions at the site, it cannot be said for certain that sinkholes will not develop. The risk of future ground subsidence in the development area of Lot 52 throughout the service life of the proposed residence, in our opinion, is low; however, the owner should be made aware of the potential for sinkhole development. If further investigation of possible cavities in the bedrock below the site is desired, we should be contacted. FIELD EXPLORATION The field exploration for the project was conducted on June 17, 2021. Six exploratory borings were drilled at the locations shown on Figure 1 to evaluate the subsurface conditions. The borings were advanced with 4 inch diameter continuous flight augers powered by a track- mounted CME 45 drill rig. The borings were logged by a representative of Kumar & Associates, Inc. Samples of the subsoils were taken with I% inch and 2 inch I.D. spoon samplers. The samplers were driven into the subsoils at various depths with blows from a 140 pound hammer falling 30 inches. This test is similar to the standard penetration test described by ASTM Method D-1586 The penetration resistance values are an indication of the relative density or consistency of the Kumar & Associates, lnc, o Project No. 2l-7-249 4-J- subsoils. Depths at which the samples were taken ancl the penetration resistanoe values are shown on the Logs of Exploratory Borings, Figure 2. The samples were returned to our laboratory for review by the projeot engineer and testing. SUBSURFACE CONDITIONS Graphic logs of the subsurface conditions encountered at the site are shown on Figure 2. In the area of the proposed main residence and ADU (Borings 1-3), the subsoils consist of up to Yzfeet of topsoil overlying up to 5 feet of sandy silty clay underlain by basalt boulders, cobbles, and gravel in a sandy silt matrix down to the maximum depth explored of 19 feet. Drilling in the coarse granular soils with auger equipment was diffrcult due to the cobbles and boulders and drilling refusal was encountered in the deposit at a depth of 18 feet in Boring 2 and 6Yz feet in Boring 3. In the area of the proposed driveway (Borings 4-6) the subsoils consist of 3 to 4 inches of road base overlaying slightly sandy clayey basalt gravel cobbles and boulders. In Boring 4, about 4Yz feet of sandy clay and silt was encountered between the road base and the clayey gravel. Laboratory testing performed on samples obtained from the borings included natural moisture content and density, Atterberg limits, and gradation analyses. Results of swell-consolidation testing performed on a sample of the sandy silt matrix material, presented on Figure 4, indicate moderate to high compressibility under conditions of loacling and wetting. Results of gradation analyses performed on small diameter drive samples (minus l%-inchfraction) of the coarse granular subsoils are shown on Figures 5 and 6. The laboratory testing is summarized in Table l. No free water was encountered in the borings at the time of drilling and the subsoils were slightly moist. FOUNDATION BEARING CONDITIONS The subsoils encountered on the lot generally consist of basalt gravel cobbles and boulders in a sandy silt matrix. The upper silt and clay soils are low density and are typically known to be compressi'oie when wetteci uncier ioaci. Lightiy ioacieci spread fbotings can be used for support of the proposed residence provided that a risk of settlement and distress is acceptable to the owner. Rcmoving the silt and clay soils and placing the footings on a depth (typically 2 to 3 feet) of compacted structural fill could be used to reduce the risk of settlement. Kumar & Associates, lnc. o Project No. 2l-7-249 -4- DESIGN RECOMMENDATIONS FOLINDATIONS Considering the subsurface conditions encountered in the exploratory borings and the nature of the proposed construction, we recommend the building be founded with spread footings bearing on the natural granular soils, beneath the upper fine-grained soils or compacted structural fill placed on the natural granular soils. The design and construction criteria presented below should be observed for a spread footing foundation system. 1) Footings placed on the undisturbed natural granular soils or compacted structural fill should be designed for an allowable bearing pressure of 2,000 psf. Based on experience, we expect initial settlement of footings designed and constructed as discussed in this section will be about 1 inch or less. If the bearing soils were to become wetted, additional settlement up to around 1 inch could occur depending mainly on the depth and extent of wetting. 2) The footings should have a minimum width of 20 inches for continuous walls and 2 feet for isolated Pads. 3) Exterior footings and footings beneath unheated areas should be provided with adequate soil cover above their bearing elevation for frost protection. Placement of foundations at least 36 inches below exterior grade is typically used in this area. 4) Continuous foundation walls should be heavily reinforced top and bottom to span local anomalies such as by assuming an unsupported length of at least 14 feet. Foundation walls acting as retaining structures should also be designed to resist lateral earth pressures as discussed in the "Foundation and Retaining Walls" section of this report. 5) The topsoil, fine grained soils and any loose or disturbed soils should be removed and the footing bearing level extended down to the relatively dense natural granular soils. The exposed soils in footing area should then be moistened and compacted. 6) A representative ofthe geotechnical engineer should observe all footing excavations prior to concrete placement to evaluate bearing conditions. FOUNDATION AND RETAINING WALLS Foundation walls and retaining structures which are laterally supported and can be expected to undergo only a slight amount of deflection should be designed for a lateral earth pressure Kumar & Associates, Inc. o Project No. 21-7-249 -5- cotllputed on the l:asis of an equivalent fluicl unit weight uf at least 50 pclfor backfill consisting of the ort-sitc soils. Cantilevered retaining structures which are separate from the residence or ADU and can be expected to deflect sufficiently to mobilize the full active earth pressure condition should be designed for a lateral earth pressure computed on the basis of an equivalent fluid unit weight of at least 45 pcf for backfill consisting of the on-site soils. Backfill should not contain organics or rock larger than 6 inches. All foundation and retaining structures should be designed for appropriate hydrostatic and surcharge pressures such as adjacent footings, traffîc, construction materials and equipment. The pressures recommended above assume drained conditions behind the walls and a horizontal backlìll surfaoe. The buildup of watu bchind a wall or an upward sloping backfill surface will increase the lateral pressure imposed on a foundation wall or retaining structure. An underdrain should be provided to prevent hydrostatic pressure buildup behind walls. Backfill should be placed in uniform lifts and compacted to at least 90% of the maximum standard Proctor density at a moisture contçnt near optimum. Backfill placed in pavement and walkway areas should be compacted to at least 95Yo of the maximum standard Proctor density. Care should be taken not to overcompact the backfill or use large equipment near the wall, since this could cause excessive lateral pressure on the wall. Some settlement of deep foundation wall backfill should be expected. even if the material is placed correctly, and could rcsult in distrcss to facilities constructed on the backfill. The lateral resistance of foundation or retaining wall footings will be a combination of the sliding resistance of the footing on the foundation materials and passive earth pressure against the side of the footing. Resistance to sliding at the bottoms of the footings can be calculated based on a coefficient of tiiction of 0.40. Passive pressure of compacted backfill against the sides of the footings can be calculated using an equivalent fluid unit weight of 350 pcf, The coefficient of friction and passive pressure values recommended above assume ultimate soil strength. Suitable fäctors of safety should be included in the design to limit the strain which will occur at the ultimate strength, particularly in the case of passive resistance. Fill placed against the sides of the footings to resist lateral loads should be a granular material compacted to at least 95%o of the maximum standard Proctor density at a moisture content near optimum. FLOOR SLABS The natural on-site soils, exclusive of topsoil, are suitable to support lightly loaded slab-on-grade construction with a risk of settlement if the bearing soils are wetted. To reduce the effects of Kumar & Associates, lnc. o ProJec{ No. 21-7-249 -6- some differential movement, floor slabs should be separated from all bearing walls and columns with expansion joints which allow unrestrained vertical movement. Floor slab control joints should be used to reduce damage due to shrinkage cracking. The requirements for joint spacing and slab reinforcement should be established by the designer based on experience and the intended slab use. A minimum 4 inch layer of free-draining gravel should be placed beneath basement level slabs to facilitate drainage. This material should consist of minus 2-inch aggregate with at least 50oá retained on the No. 4 sieve and less than 2o/o passing the No. 200 sieve. All fill materials for support of floor slabs should be compacted to at least 95o/o of maximum standard Proctor density at a moisture content near optimum. Required fill can consist of the on- site soils devoid of vegetation, topsoil and oversized rock. UNDERDRAIN SYSTEM Although free water was not encountered during our exploration, it has been our experience in the area that local perched groundwater can develop during times of heavy precipitation or seasonal runoff. Frozen ground during spring runoff can create a perched condition. We recommend below-grade construction, such as retaining walls, crawlspace and basement areas, be protected from wetting and hydrostatic pressure buildup by an underdrain system. The drains should consist of PVC drainpipe placed in the bottom of the wall backfill surrounded above the invert level with free-draining granular material. The drain should be placed at each level of excavation and at least I foot below lowest adjacent finish grade and sloped at a minimum l%oto a suitable gravity outlet. Free-draining granular material used in the underdrain system should contain less than 2o/o passingthe No. 200 sieve, less than 50% passing the No. 4 sieve and have a maximum size of 2 inches. The drain gravel backfill should be at least lYzfeet deep and covered with filter fabric such as Mirafi 140N or 160N. An impervious membrane such as 20 or 30 mil PVC should be placed beneath the drain gravel in a trough shape and attached to the foundation wall with mastic to prevent wetting of the bearing soils' SITE GRADING The risk of construction-induced slope instability at the site appears low provided the buildings are located as planned and cut and fill depths are limited. We assume the cut depths for the basement levels will not exceed one level, about l0 to 12 feet. Fills should be limited to about 8 to 10 feet deep, especially at the downhill side of the residence or ADU where the slope steepens. Embankment fills should be compacted to at leastg5Yo of the maximum standard Kumar & Associates, lnc. @ Projec't No. 21-7-249 -7 - Proctor density near optinrum moistule contçrrl. Prior to fïll placcment, the subgrade should be carefirlly preparecl by retnoving all vegel"al,ion and topsoil and compacting to at least 95% of the maximum standard Proctor density. The fill should be benched into the portions of the hillside exceeding 20Yo grade. Permanent unretained cut and fîll slopes should be graded at 2 horizontal to I vertical or flatter and protected against erosion by revegetation or other means. This office should review site grading plans for the project prior to constçuction. SURFACE DRAINAGE The following drainage precautions shoulcl be observed during construction and maintained at all times after the residence and ADU have been completed: 1) Inundation ofthe foundation excavations and underslab areas should be avoided during construction. 2) Exterior backfill should be adjusted to near optimum moisture and compacted to at least 95%o of the maximum standard Proctor density in pavement and slab areas and to at least 90Yo of the maximum standard Proctor density in landscape areas. 3) The ground surface surrounding the exterior of the building should be sloped to drain away from the foundation in all directions. We recommend a minimum slope of 12 inches in the first 10 feet in unpaved areas and a minimum slope of 3 inches in the first 10 feet in paved areas. Free-draining wall backfill should be covered with filter fabric and capped with about 2 feetof the on-site soils to reduce surface water infiltration. 4) Roof downspouts and drains should discharge well beyond the limits of all backfill. 5) Landscaping which requires regular heavy irrigation should be located at least l0 feet from foundation walls. PAVEMENT SECTION We understand asphalt pavement is proposed for the driveway. Traffîc loadings for the driveway were not provided but are assumed to be relatively light with occasional truck traffîc and typical ^f +Lo +.'-- ^f ,{^.,^l^-*^-+ \I/^ ^^^--*^ *1-^ ,^^--- --- ---1 --,:rr r- i r ¡. iivr r¡rw rJpw vr uv v vrvpurçrrL. vv ç ilJJurlrç ruç lJ¿lvgrilçIrt wlll De placeq gssgntrally aftgr all construction truck traffic has been completed. The subgrade soils encountered at the site are generally low plasticity sand, silt and clay with gravel and scattered cobbles which are considered a fair support for pavement sections with a Hveem stabilometer 'R' value of 15. Imported tìll will be needed for the roadway construction. The imported soil should be a sand and gravel material with a minimum Hveem stabilometer'R' value of 50. Based on our Kumar & Assoclates, Inc, o ProJect llo. 21.7-249 -8- experience, an l8 kip EDLA of 10, a Regional Factor of 2.0 and a serviceability index of 2.0, we recommend the minimum pavement section thickness consist of 3 inches of asphalt on 6 inches ofbase course on 8 inches ofsubbase. The asphalt should be a batched hot mix, approved by the engineer and placed and compacted to the project specifications. The base course should meet CDOT Class 6 specifications. The subbase should meet CDOT Class 2 speciflrcations. All base course and required subgrade fill should be compacted to at leastg5%o of the maximum standard Proctor density at a moisture content within 20á of oPtimum. Required fill to establish design subgrade level can consist of the on-site soils or suitable imported granular soils approved by the geotechnical engineer. Prior to fill placement the subgrade should be scarified to a depth of 8 inches, adjusted to near optimum moisture and compacted to at least 95Yo ofstandard Proctor density. In soft or wet areas, the subgrade may require drying or stabilization prior to fill placement. A geogrid and/or subexcavation and replacement with aggregate base soils may be needed for the stabilization. The subgrade should be proofrolled. Areas that deflect excessively should be corrected before placing pavement materials. The subgrade improvements and placement and compaction of base and asphalt materials should be monitored on a regular basis by a representative of the geotechnical engineer. Once traffic loadings are better known, we should review our pavement section recommendations. LIMITATIONS This study has been conducted in accordance with generally accepted geotechnical engineering principles and practices in this area atthis time. We make no warranty either express or implied. The conclusions and recommendations submitted in this report are based upon the data obtained from the exploratory borings drilled at the locations indicated on Figure 1, the proposed type of construction and our experience in the area. our services do not include determining the presence, prevention or possibility of mold or other biological contaminants (MOBC) developing in the future. If the client is concemed about MOBC, then a professional in this special field of practice should be consulted. Our findings include interpolation and extrapolation of the subsurface conditions identified at the exploratory borings and variations in the subsurface conditions may not become evident until excavation is performed. If conditions encountered during construction appear different from those described in this report, we should be notified so that re-evaluation of the recommendations may be made' Kum¡r & Acsociateg, lnc, o Projec{ No.21-7-249 -9- This roport has been preporcd for the exchrsive use by our client for tlesign purposes. we are not responsible for technical interpretations by others of or¡r information. As the project evolves, we should provide continued consultation and field services during construction to review and monitor the implementation of our recommendations, and to verify that the recommendations have been appropriately interpreted. Significant design changes may require additional analysis or modifications to the recommendations presented herein. We recommend on-site observation of excavations and foundation bearing strata and testing of structural fill by a representative of the geotechnical engineer. Respectfully Submitted, Kumnr & Associ¡t.r, hr., { Robert L. Duran, P.E. Reviewed by: Steven L. Paw RLDlkac cc: Compass LLC-ScottDeWind@) JVA - J.R. Spung Kumar & Associates, lnç. o Project No. 21.7.249 E LOT 52 4O.748! ACRES \""*,"..,,""* -#v,iå'"y,11" rum,acßà/ 'eM@'ÆÆNr -. 1I- - ---¿ I - 66"' _ - sd5-I -r Ëi ri I I ¡I I i 1 I 1 I 1 1 I BORING 3 itl NOßn{ scuoÙ 32 25.42', 6 E*r vre co '. Ícfou 2s I ì I ! I I i{)l 5T I r1r i 5.ì CEßIsE 8lr'.NCIl ROAD 1:-tu9708'æ\ CH-75.57' f ilÌT' 5+ I ì 100 APPROXIMATE SCALE-FEEÏ Fig. 1LOCATION OF EXPLORATORY BORINGS21 -7 -249 Kumar & Associates Fig. 2LOGS OF EXPLORATORY BORINGSLOT 52 CERISE RANCHKumar & AssociatesWC=5.6+4=22-2OO=47EORING 1EL. 6545'EORING 2EL. 6555'BORING 5EL. 6570'EORINGEL. 55f17'EORING 5EL. 6¡f87'BORING 6EL. 6,155'oÂr')trft:9?"'ft,",,,,Wr*,"(1)t¿)ffiffi'v"HW*Yro49/1213/ 1211/ 12so/ 450/5+4=39-200=35Pl=7A-4 (o)+4=48-200=25LL=21Pl=3A-r-b (D)IIÊ1072/ 12WC=2.910DD= I 03-2OO=7417/12t550/sl550/62020I uarN RESTDENcEADUDRIVEWAY21-7-249 I N LEGEND (4)BASE COURSE, THICKNESS IN INCHES SHOWN IN PARENTHESES TO LEFT OF THE LOG ñ TOPSOIL; SILT AND CLAY, SANDY, FIRM, SLIGI{TLY MOIST' TAN, ROOTS. CLAY AND SILT (CL-ML); SANDY, STIFF, SLIGHTLY MOIST' TAN BASALT GRAVEL, COBBLES, AND BOULDERS (GC_ML); IN A SANDY SILT MATRIX, MEDIUM DENSE TO DENSE, SLIGHTLY MOIST, TAN. F:Z lr{î1 lo.l:'r.1lz3 BASALT COBBLES AND BOULDERS (GC); CLAYEY, SLIGHTLY SANDY, DENSE, SLIGHTLY MOIST' GRAY TO TAN. DRIVE SAMPLE, 2-INCH I.D. CALIFORNIA LINER SAMPLE I DRTVE SAMptE, 1 S/9-INCH l.D. SPLIT SPOON STANDARD PENETRATION TEST ,^T". DRIVE SAMPLE BLOW COUNT. INDICATES THAT 49 BLOWS OF A 14o-POUND HAMMER+r/ t¿ FALLTNG 30 TNCHES WERE REQUIRED TO DRIVE THE SAMPLER 12 INCHES. f nnncrrclL AUGER REFUSAL. NOTES 1. THE EXPLORATORY BORINGS WERE DRILLED ON JUNE 17,2021 WITH A 4-INCH_DIAMETER CONTINUOUS-FLIGHT POWER AUGER. 2. THE EXPLORATORY BORINGS WERE LOCATED BY PACING. BORINGS 1 THROUGH 3 WERE LOCATED BY SCOTT DEWIND AND BORINGS 4 THROUGH 6 WERE LOCATED BY KUMAR & ASSOCIATES. 5. THE ELEVATIONS OF THE EXPLORATORY BORINGS WERE OBTAINED BY INTERPOLATION BETWEEN CONTOURS ON THE SITE PLAN PROVIDED. 4. THE EXPLORATORY BORING LOCATIONS AND ELEVATIONS SHOULD BE CONSIDERED ACCURATE ONLY TO THE DEGREE IMPLIED BY THE METHOD USED. 5. THE LINES BETWEEN MATERIALS SHOWN ON THE EXPLORATORY BORING LOGS REPRESENT THE APPROXIMATE BOUNDARIES BETWEEN MATERIAL TYPES AND THE TRANSITIONS MAY BE GRADUAL. 6. GROUNDWATER WAS NOT ENCOUNTERED IN THE BORINGS AT THE TIME OF DRILLING. 7. LABORATORY TEST RESULTS: WC = WATER CONTENT (%) (ASTM D2216)I DD = DRY DENSITY (pct) (Asru D2216); +4 = PERCENTAGE RETAINED ON NO. 4 SIEVE (ASTM D6913); _2QO= PERCENTAGE PASSING NO. 2OO SIEVE (ASTM Dl140); LL = LIQUID LIMIT (ASTM D4518); PI = PLASTICITY INDEX (ASTM 04518); A-4 (o) = AASHTo cLASSlFicATloN (GRouP INDEX) (aaslro M 145). Fig. 3LEGEND AND NOTESKumar & Associates21 -7 -249N 2\- lmlon-7-2¿9 Gô#htuIo)IÈCONSOLIDATION - SWELLIttro@o¡À(%)ININot\)ô!Ttrrooooòg åil= Pl') TI' T'I¡o9o¿J..$ (o G).J,o N ãgo@é=óilro tno(¡o=EO.o¡e.ot<N9{utilul\¡oæoÉNqoo_cz>g9rq Etoã.Fs9-2.>og-{å3Fl{<)xåaûg?aiD z.fft{IlÌI5N)I!IN)s(oxc3g)eo(n(t,oo.q¡oo|J)=fÌlrt-I()oz.U)ot-ç7-.1oz.-lrrllJ)-{ÐfÎ(nct-{U)Tl(os I ı a too 90 80 70 00 50 ß so 20 to o 10 20 30 10 50 50 70 ao 90 100 - & H 152 DIAMETER OF IN MI CLAY TO SILT COBBLES GRAVEL 22 % SAND 51 % LIQUID LIMIT PLASTICITY INDEX SAMPLE OF: Vôry Cloyåy Sllty Sond wlth Grovol SILT AND CLAY 47 % FROM: Borlng 1 e 8' & 15' (Comblned) c f Ê t00 90 ao 70 80 50 10 50 20 to o 0 t0 20 JO 10 50 ao 70 80 e0 to0 = 1,75 .125 OF PARTICLES IN MI ta2 CLAY TO SILT COBBLES GRAVEL 39 % SAND LIQUID LIMIT 23 SAMPLE 0F: Very Cloyey Sondy Grovel 25% PLASTICITY INDEX SILT AND CLAY 36 % 7 fh.sr l.!l r.rullt dpply only to lh. sqñplos whlch woro lgslod. Tho lôsllàg report sholl not be rcproducsd, excopl ln full, wlthoul lho wrltlon opprcvql ol Kumor & Astociotos, lnc' Sicv¡ onolysls lcal¡ñg h parfom.d ln occordqncó wlth ASTM 06915, ASTM 07928, ASÍM C15ô qnd,/or ASTM 0tl,l0. FROM: Borlng4@,+' SIEVE ANALYSISHYDROMETER ANALYSIS CgR SQUARE OPENINOS at.r tt^. I t/.. U.S, S1ÀNOARD SERIES ¡3ô aÆ a3ô ¡16 ¡lô ¡a2¿a HRs 7 HRS lYIN ÎIYE RE ÞINGS aôltN taMtN allN I '' I"2. /r ----l--i -___ - I' i.l I I i _l I -lI , , ;-;-;i, ,- -l_ r I r I ¡ l-' I GRAVELSAND COARSE FINE COARSEFINEMEOIUM SIEVE ANALYSISHYDROMEfER ANALYSIS CLüR SOUARE OPENINCS r/^' ./^' I 1/t' u.s. sf ND R0 sERlEs ¡50 f¿o ¡30 ¡la llo ta2¿ HRS 7 HRS TIME READINGS ßoltN !eMtN 4ulN -t-'t:.l :.- -..'.t- I r --- .1,.,..lì ,î - ,..,,1-L ill I I-----+--* i I ---+--*.* I-l -ì i-tit.... ¡l_l GRAVELSAND COARSE FINE COARSEFINEMEDIUM Fis. 5GRADATION TEST RESULTSKumar & Associates21 -7 -249 Ì SIEVE ANALYSIS u.s. HYDROMETER ANALYSTS I HRS 7 HRgt5 utN .¡- tt-ti it ï 7L i, I I 'I I I. f I tl rtl I I I I ãI too 90 ao 70 ao 50 /þ 50 20 to 0 o lo 20 to ,+o 50 60 70 ao 90 100 = P .125 DIAMETER OF PARTICLES IN CLAY TO SILT COBBLES GRAVEL 48 % SAND I tQutD ilMtT 21 SAMPLE OF: Sllty Sondy Grovol 27% PLASTICITY INOEX SILT AND CLAY 25% 3 FROM:Borlng6e4' 1h.3. l.3l rcsulls opply only lo lh. sqmplls whlch vlra lrslrd. fhrlrlllng r.porl sholl nol b! r.produc.d, oxccpl ln full, wllhoul lhô wrllton opprcvol of Kumor & Ar¡oclote¡, lnc.Sl.vc onqlysls l.sflng 13 Þrrfomad ln occordonce wllh ASÍM D6915, ASÌM 07928, ASTM C156 qndlor ASTM Dtl,l0. SAND GRAVEL FINE MEDTUM lCOAnSs FINE COARSE 21 -7 -249 Kumar & Associates GRADATION TEST RESULTS Fis. 6 ç. rcñ$ffiim.miiii;-*TABLE 1SUMMARY OF LABORATORY TEST RESULTSNo.2l-7-249Very Clayey Silty Sandwith GravelSandy Silt and Clay withscattered GravelVery Clayey Sandy GravelSilty Sandy GravelSOIL TYPEAASHTO SOILCLASSIFICATIONA-4 (0)A-l-b (0)7JPLASTICINDEXlolol1247312225ATTERBERG LIMITSIïolLIQUID LIMIT257836PERCENTPASSING NO,200 slEvE25274839('/")SAND('/")GRAVELDEPTHBORINGNATURALDRYDENSTYNATURALMOISTURECONTENT1032.94.8I45.6448 and 13Combined96124 ÍNUE NCRII{ COLORADO LLCfrffil.l*@h¿a d$¡ - *u*ffisr t@''4Ë'RoIEqlG Ðtt#t-+H4-l)Au:l¿l:æi,Þ [ryllSHEETGI.YNNA G. BAKII 6¿ B=F-I M. O3LESKIIMPROVEI\ÆNT & -OFO€IAPÍ{Y SURVÊYto¡ t - cruE uÉ HÆ oNEaouffiGamal) - sÆôFæbilæ'ffiü,ii,.rl'íiiir.r,: I"''fi--:,,:;.rtTRI]E NORTH- coLoRADO-â LAID sURVEYING Af,D MAPPING (O*PÀNYItIMPROVEMENT SURVEY PLATLOT52 - CERISE RANCH SUBDIVISION PHASE 1SECTIONS 29 & 32, TOWNSHIP TSOUTH,RANGE 87 WESTOF THE 6TH PMCOUNTY OF GARTIELD STATE OF COLORADOINtTIGENDn drtu'@4,scÁ¿Ë- r'?ROPERfi D6EIMON.ît]JSURVEY NOTES.II:III:/t,'t'IìISURVEYOPS CERÍIFICA'IIONIL5t)r u¡m6 ¡4.8 HÉú4 O¡ ro 9ñ!ßBú r!@úBMlm aÞ À!E^g.f]'::tE ,zã.-in*iitri' I+,ì Ii.í)¡iJIIiLII tL)'' jI,/"*----¿ILOT 52I ,-.r-.rli:iiÊOAÐ ÇqPuhlic.net"" Garfield County, CO Account ROO7I47 Number Parcel 239t32LO2052 Number Acres 4t LandSqFt 0 TaxArea 084 2019 Mill Levy 80.0500 Physical Address Owner Address 3óOCERISE RANCH RD CARBONDALE BAKER, GLYNNA G & OBLESKI, BERTM PO BOX 5748 FRTSCO CO 80443 2O19Total Actual Value Overuiew Legend I Parcels Roads Parcel/Account Numbers Owner Name fi Lakes&Rivers - county Boundary Line $275,0æ Last2Sales Date Price 7/29/2022 $O 7/29/2022 sO 87623 Date created: 10/24/2022 Last Data Uploaded: 10/13/2022 72:O5:I5 AM Deve roned bv fì .g:åW^¡dçt 1U24122, 12:47 PMSummaryAccountParcelPropertyAddrassl¡sþlDescrlpdonAcresLândSqFtTer(AÌ€aMlllLeyySubdþlslonViewMapOrmerBAKER, GLYNNAG&OBLESKI, BER[ MPO BOX 5748FR|SCOCOS&r43LandUnftType VACANT RES LOTS - 01OO (VACANT LANDISquar€Feet OActualValæsAçsessedYeárLând ActuâllmÞrorænìeßt ActuelIotal AcfualAssessedValusAssessedYearLend AssessedlmprorrementAss€ssedTotål AssessedTax HistoryTa¡(YeerTaxes BilledG)qPuHic.net'" Garfield County, COqPublic.net - Garfield County, CO - Property Record Card: R0071d7MIE¿$275,000.00fo.oo$27s,OOO.æ2m?$79,750.æ$o.ooj79,750ffixnl2VÐ$4,947.72Ræ7T4723913210,20/523óO CERISE RAN(CH RD, CARBONDIALE, CO 81ó23Sect¡on: 32 Townsihip: 7 Range: 87 Subdiv¡s¡on: CERISE RANCH SUB-D|V. Lot 52 PHASE I ¡10.7¿EACRESQ.7ßo8480.0s00CERISE RANCH SUB-DIV.2glzt$27s,0æ.(x)$o.oo$275,(x¡Ofx,2(m$7s,7so.æ$o.ooç7s;r50.æ2019i4,99o..72ñn$225,0æ.00$o.oo$z¡5,(m.(x¡ãJ'IT)$ós¿so.oo$0.00$6s,250.002018t/',81s.A4$ó,384.00http6:#qpublic.schneidercorp.com/Appli<ntion.aspr?ApplD=1o38&LayerlD=22381&PageTypelD=4&PagelD=9447&Q{11687372&Key\lalue=RilO71471t3 10124122,12i47 PMqPublic.net - Garfield Coun$, CO - Property Record Gard: R007147Clickheretoviewthetaxinformationfor this @TransfersSaleDâte DeedTypê712912022 Rightof WayEesement712912022 Agreement4IL2I2O21 SPECIALWARRANWDEED4I7A2O2L PERSONALREPDEED3tt9t2o2r QU|TCIAIM DEED3I!61202A PERSONALREPDEED2t25t2020 LETTERSTAA2O79 DEATH CERTIFICATEe/23t2079 LETTERSU2U2O7A POWEROFATTORNEYUTU2OT& POWEROFATTORNEYAT6/2018 POWEROFATTORNEYAß/2O78 POWEROFATTORNEY219/2OT8 POWEROFATTORNEYU5IÑ!8 POWEROFATTORNEYura2o78 QUlrcLAlM DEED8/31T2@6 EASEMENT5/t7t2co4 oRDEROF INCLUSION312A2@4 INCLUSION!a2a2æ3 oRDEROFINCLUSIONLAIA200,S TNCLUSION9/25/2æ3 CoVENANTS9/312c03 SPECIALWARRANTYDEED8/2012ú3 QUITCLAIM DEED4lu2@7 qulrcLAlM DEEDLATUZW AGREEMENT1U12t2æO CO/ENANTSIU\UNO SUBDIVISION IMPROVEMENTSTAIU2AAO AGREEMENTtolt6lM QUITCLAIM DEED9/2912cßp QUITCLAIMDEED9/2912000 QUITCLAIM DEEDgí28i2c0o WARRANTYDEED9t28t2ffi DEED9IT3I2WO BOUNDARYLINEADJUSTMENT9II3I2úO BOUNDARYLINEADJU5TMENT9/8/M RESOLUTION3I6IM CONTRACTyrz7998 QUITCLAIM DEED9I1,AN997 BOUNDARYLINEADJUSTMENTU2317993 EASEMENTU231L993 SPECIALWARRANTYDEEDA2311993 SPECIALWARRANWDEED\2tr7]1l9g2 DEED713U1992 NOTICE OF LIS PENDENS8/L81t982 QUlrCtAlM DEEDReceptlon Number978301e7p300954303954fi2953019t33293?332929332919543019543009542eJ-9y.2949542969542959542999A27?3950910652490649977643769649970637392éæ6345485792975735475735¿!0573539573505573il257004757æ4457004ó9994C5693495ó93485ó910ó5ó1931525ó545!S3Cé44950844950744950ó4/22AA437552331785Book- PâgeSale Prle$o$o$24'-2û$s7,8oo$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$o$1,s81,ó00$3,26r,000$o$o$o$o$1,ooo$o$o$o$o$o$o$ot589-562t57ó.681155G552r576-6771523-601515-1ó11508-37ót245-4471222-r7221-9427221-9227233-5461222-97æ9-9067æ9-8771209-888tng-8727z)7-3991207-3967æ&2ß7787-94óto69-76103æ35ó08ó7{9s00867-094óæ67494t85G81838-205oóoó{5ó9https://qpublic.schneidercorp.corn/Application.aspf?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=611687372&KeyValue=R0071472t3 10124122, 12:47 PMrol79/L9656t2?/1565u1811937ru16/1925qPublic.net - Garfield County, CO - Property Record Card: R007147VYARRANTYDEEDPAT:NTVÚARRANTYDEEDWARRANTYDEED2320282304227274369311ó370-379367-t4718s-319t12-547$o$o$o$21,WProperty Rebted Public DocumentsClickhere tovie'd Prorcrv Relêted t'uUic DocumentsPhotosNo data avallable for the follorvlng modules: Bu¡ldings, Sl€tches.:.ìi:{il-':.lr:llilo,:,1-,:::l:.i:i"i.:ì{.:itl:¿r -'.:, . I,:.!i,Sg Pnvac-yg.o!cïG.ÞPR"PrLvacv NoësçLestQaqupJaadil9ll2/-292;!Ooå15P¡4 ',¡.r"r::r: i.:ì i:i?¡:iJ,ìls*.r il l).\Sl*å'gt"J,qçrhttps://qpublic.schneidercorp.com/Appliætion.aspx?ApplD=1o38&LayerlD=22381&PageTypelD=4&PagelD=9447&e{11687372&KeyVatue=R0071473/3 Item # It.l53G2CP l53O Gallon Two Gompartment lnflltrato¡Ð Poly Tank o o <Þoé o o <ÞoÉ o o (-o-t It lill I 61 TANKTOP HALF CONTINUOUS ELASTOMETRIC 175.6'TANK INTERIOR SEAM CLIP (86)TOP VIEW ruq{lÆNT DOTYEI(¿10)TANK BOTTOM HALF 24'ACCESSPORT wTH LOCKTNG LID (3) Terú(f¡døßMs O MID-HEIGHT SEAM SECTION DETAIL 4 OUTLETTEE 2/:I TOTALVOL TOTAL VOL ti srDE vtEw SEAM CLIP . Compliont with CSA ond IAPMO Stondords o PVC risers ovoilobleo Secondory sofety screen ovoiloble wíth PVC rîser ¡ Moximum buriol depth is 48" ¡ Minumum buriol depth is 6"¡ Tonk is not roted for vehiculor troffic looding¡ Exteriór of monhole cover includes the following worning: "DANGER D0 NOT ENTER: POISON GASES" LIFTINGSTRAP ffYPrcåL) END VIEW fifrr,rr**',gn' tä¡rÆutwrßrG' WALL 1 SLOTFIBERGLASS SUPPORT Digging Specs 16' Long x 7' Mde 43" below inlet lnvert Dimensions Net Weight Net 1st lnlet 47" Outlet 44" Length 175.6" !rÌdth 61.7" Height 54.5"501 lbs.'1006 gol 503 9ol 1509 9ol W.!.r &Wa¡ffir oS!Éemg o Prcdude Frqresi.zol ffiryer Fæ ftrg) wfin BãEVldb'æ91211 W.btlb: wvrw.uilenr€d.øn Ennft fronüeA@A¡qpnø.ønE PRTCASI,Ine. oserulæ Double Walled PVG Riser & L¡d Options Poly Lid (Static load testod to 5üD lbe)o Skid lesistanoe surfaoeo Available in green. Highest level of UV Proþction induded. lncludes a bam gasketbrairtightand watertight applications. lncludes squaÞ drive scfia,us b disoounage unauthorized erÌty. lnsulation panels achieve R-10 insulation nating 2'ol Standard Orenco @ DuraFibern Access Lids (FLD) Not reæmmended br vehict¡larffic 24'and 30'Diameþæ¡ Solid, resin-infused fiberylass consût¡ction. 20,000{b breaking sûengür. Standard gr€en or brovvn oolorc. Available with orwithout urethane lid gasket. Available with carbon filhation. 4 stainless steel f,athead socket cap scr€ws & hex key wrendr. Insulatsd lids available-? or4' Double Walled PVC Riser . Available ln 24' and 30' Diamebr. Cut to lengür. Sold in +l-2'incrernenbo Must be cut botrveerr ribs tr PRECASI¡Inc. oserylce grot 39r6?ot 2trFoo ru'fl7 P.O.Bq6 Fæ ftro) ç54,'7n BffavlÚe'æ812¡1 WeDclb: wtnv.vdle¡prcd.øn Eml[ fronüækl@nrdhmteø.øn Wúer& Wa¡bwabr o S¡¡stem ¡ Ploducile Residential Biotube' Effluent Filters Applications Our patented* 4-în. (100-mm) Biotube Effluent Filters, Biotube Jr., Biotube Insert Filters, and Biotube Base Inlet Filters are ideal for residential septic tanks and have a lifetime warranty. They prevent large solids from leaving the tank, dramatically improving wastewater quality and extending the life of residential drainfields. 4-in. (100-mm) Biotube Effluent Fiber 4-in. (1 À?-rnrn) Biotube Jr. (4-in. Biotube cartidge auøil- able separateþ as Insert Fiber) T å q .l I :..¡ ld 'r'.+'i ItI f-in. (200-mm) Bøse Inlet Fiher 4-in. (100-mm) Insert Fiher I I l i È :¡ Orenco's saperior efluent filters resht cloging better than all other brands. Our stan- dard, full-sized 4-in. (100-mm) Biotube Effluent Fiber prouides maxirnum long-term protection in a complete pachage, with hoasing. Our 4-in. (100-mm) Biotube Jr., at half the size of our standørd mode l, has more fihering capøcity than the full-sized f'hers sold b1' other manufacturers. For tanþs with existing outlet tees, the Biotube lwert Fiher is id¿al. Andfor low-profile tønþs, therets the Base Inlet Fiber. * Covered by patent numbers 5,492,635 a¡d 4,439,323 To Order Call your nearest Orenco Systems@, Inc. distributor. For nearest distribu- tor, call Orenco at 800-348-9843 or go to www.orenco.com and click on "Distributor Locator," APS-Fr-1 Rev.3.4 @ 11/10 Orenco Systemso, lnc. Standard Features & Benefib . Has 5-10times more flow area than other brands, so lasts many times longer between clean- ings, increasing homeowner satisfa ction . lnstalls in min- utes inside new or existing tanks; extendible tee handle for easy removal 0ptional Features & Benefits . Alarm available,to signal the need for cleaning . Flow modulating discharge orifices available to limit flow rate leaving tank, mitigat- ing surges and increasing retention time . Custom and commercial sizes available . Easyto clean by simply hosing off whenever the tank needs pumping . Removes about two-thirds of sus- pended solids, on average, extending drainfield life . Corrosion-proof construct¡on, to ensure long life ' Lifetime warranty Biotube Filtering Process Effluent from the relatively clear zone ofthe septic tank, between the scum and sludge layers, horizontally enters the Biotube Effluent Filter. Effluent then entersthe annular space between the housing and the Biotubes, utilizing the Biotubes'entire surface for filtering. Particles larger than the Biotube's mesh are prevented from leaving the tank. Orenco S¡rstems* lncorporated ChdngingtheVal tht tl{or ld D o es Wa s îe wt t e rù wwur.otenco.Gom ã_, *-.4ã-r € Nomenclatures 4-in. Biotube Fiher (standard) 04!nFT 4-in. Biotube Effluent Fifter Extendible PVC handle Stainless steel set screws Top seal plate Air Biotube@ filter cartridge Solid base Filter housing It-in. Biotube Jr. Tank wall --r- | options: Blank =M=no options flow modulation plate inslalled float bracket attached Car[idge height: 28" and 36" are standard Housing height: 36" and 44" are standard Filter diameter (inches) W =fitsS = fits Type 3034 outlet pipe Schedule 40 outlet pipe Blank P = 1/S" filtratÌon = 1/l6" filtration Biotube effluent filter serìes f-in. Biotube Fiher (base inletmodel) FTn oS 22-148 0ptions:A = float bracket FS = 2" outlet or¡fice FSO = 2" outlet orifice and overflow plate. Riser wall Base inlet model Cartr¡dge heightr 1 4" slandard Housing he¡ohl: 22" slandard Filter diameter (inches)08=8" Blank = 1/8" filùationP = 1/16" filtrat¡on Biotube effluent filter series - Also available w¡th coupling and sleeve as a "kit": FI-OVERFLoWKIT 4-in. Biotube JÍ. (includes cartridge and housing) FTJ 04 18 0ptions: Blank = no optionslM = flow modulation plale installedA = float bracket attached Carridge height (inches) Filter diameter (inches) W = fitsS = fits Type 3034 outlet tee Schedule 40 outlet tee Blank = 1/8" filtrationP = 1/16" filtration Junior series Biotube effluent filter series 4-in. Biotube Filter lnsert (carridge only) FTi 04 18- -T* rrr,ot'r.o indicates North options Carolina (e.9,, NC regions) W = fitsType3034outletteeS = fits Schedule 40 outlet tee Carûidge height (¡nches) Filter diameler (inches) Blank = 1/8" filÍationP = 1/16" fillration lnsert Biotube effluent filter series Distributed By: POLYLOK DTSTRIBUTION BOX, RtsERS, AND ttD uD.BOX0&UD€OX8 ----22.45'L-D.BOX SEAL (EtERYogodcSwfrH a8ËAt¡) @16"SIDE CUT Ot'T TOACCEPT POLYLOK SEAL NO.3æl TEAROI'ITFOR 4'SDR€sOR scHD-{0 NOT TO SCALE UD.BOX E'RISER ROTOfLOW4' I 6u i t-Il--a'-J @ UD€OX 12'RISER ^/Or 70 SC/qtE POLYLOCK EQUAIJZER.V.ITOTCH'WETR 1 s}IâFE E @SEFr¡VEut{O RIBS PRO\'þE FRIgffT{ FfTF(nÄL.. PIPEID I + 20'GOVER FOR RISER & DAOX ^ro7tros/uE GASKETED SEAL ON LID & RISER VALLEY Wrûcr & Wa¡bwür o Sygtems o Prcducile FrOt 35{76. 2tËCoru'317 P.O.Bqæ5 Fæ ff19) gfp{,lttn BãäVlda'æuz11 Wcbûlb: wrrw.udlqprcd.ært Emel[ fronEæk(@Mallqnreca¡t ønÑ PRECAS|f¡rnc. oserulce t, 'l tr =ea!*çffii',' The Ouick4'Plus Standard ChamberINFILTRATOR' water technologies The Quick4 Plus Standard Chamber offers maximum strength through its two center structural columns. This chamber can be installed in a 36-inch-wide trench. Like the original line of Quick4 chambers, it offers advanced contouring capability with its Contour Swivel Connection" which permits turns up to 1S-degrees, right or left. lt is also available in four-foot lengths to provide optimal installation flexibility The Quick4 Plus All-in-One 12 Endcap, and the Quick4 Periscope are available with this chamber, providing increased flexibility in system conf igurations. Maximum Strength Ø7 Quick4 Plus'" Series Ouick4 Plus Standard Chamber Benefits: . Two center structural columns offer increased stability and superior strength . Advanced contouring connections . Latching mechanism allows for quick installation . Four-foot chamber lengths are easy to handle and install . Supports wheel loads of 16,000 lbs/axle with 12" of cover Ouiclr4 Plus All-in-0ne l2 Endcap Benefits: . May be used at the end of chamber row for an inleVoutlet or can be installed mid-trench . Mid-trench connection feature allows construction of chamber rows with center feed, as an alternative to inletting at the ends of chamber rows . Center-feed connection allows for easy installation of serial distribution systems . Pipe connection options include sides, ends or top Quick4 Plus AII-in-0ne Periscope Benefits: . Allows for raised invert installations . 180o directional inletting . 12" raised invert is ideal for serial applications Certified by the lnternational Association of Plumbing and Mechanical Officials (IAPMO) Size 34"Wx53"Lx12"H (864 mm x 1346 mm x 305 mm) Effective Length 48" (1219 mm) Louver Height 8" (203 mm) Storage Capacity 47 gat (178 L) lnvert Height 0.6" (15 mm),5.3" (135 mm), 8.0" (203 mm),12.7" (323 mm) Quick4 Plus Standard Chamber Specifications APPROVED in w 0uick4 Plus" Series =0a,1_ç,#,#" PLUS Ouick4 Plus Standard Chamber 34' 12' 48', EFFECTIVE LENGTH Ouick4 Plus All-in-One 12 Endcap PRESSURIZED PIPE DRILL POINTS LOCATIONS (2 PLACES) 33' FRONTVIEW 18' INVERT SIDE VIEW INFILTRATOR WATER TECHNOLOGIES STANDARD LIMITED WAFRAI{TY (a) Thg structural integrity of each chambgr, endcap and olher accessory manufactured by lnfiltrator ('Units'), when ¡nstalled and operated in a leaohfield of an onsite ssptic system in accordanca wilh lnfiltrator's inslructions, is waranled to the original purchas€r ('Holdet") against defectivs materials and workmanship for one year from the dalE lhal the septic pemit ¡s issued for the sepl¡c system containing thê Units; provlded, however, that ¡f a s€ptic permit is not requir€d by applicable law, th6 waranty period w¡ll begin upon the date that installat¡on of thg septic syslem commences. To gxercise its waranty ñghls, Holder must nol¡fy lnfiltrator in writing at its Corporate Headquarters in Old Saybrook, Connectlcut within f¡fteen (1 Ð days of the all€ged defecl. lnfillrator w¡ll supply r€placement Units for Units delermined by lnfillrator to be covered by lhis Limited Warranty. lnfiltrator's llability spec¡fioally excludes the oost of removal and/or inslallation of the Units. (b) THE LIMITED WARRANTY AND REMEDIES lN SUBPARAGRAPH (a) ARE Ð{CLUSIVE' THERE ABE NO OTHER WARRANTIES WTH RESPECT TO THE UNITS, INCLUDING NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PAFTICUTAR PURPOSE (c) 'lïis Limiled Warranty shall bs void if any parl of lhe chambgr sylem is manufaclured by anyone olher than lnfillralor. The L¡mited Waranly does not extend 1o incidental, consequential, special or indhect damagss. lnñltrator shall not be liable for penalties or liquidat€d damages' including loss of production and profits, labor and mater¡als, overhoad cosls, or other lossos or expenses incuned by the Holder or any third parly. Specifioally excluded from Limited Wananty covôrage are damags to the Units due to ordinary wear and têar, alteration, accident, m¡suse, abuse or neglecl of the Units; thê Units being subj€cted to vehiclo tratfic or olhêr condilions whioh are not permitted by lhe installation instruotions; failure to maintain the minimum ground covers sel forth in the inElallation inslructions; the placoment of improper mater¡als inlo the syslem containing lhe Units; failure of the Un¡ts or the septic system duE to improper siting or lmproper sizing, Excessive waler usage, improper grease disposal, or improper operalion; or any olhor event not caused by lnfiltrator. This Um¡led Wanaßty shall be vo¡d if tho Holder fails 10 comply w¡th all oÍ the terms sêt forth in this L¡miled Wananty. Further, in no event shall lnfillrator be responsible for any loss or damage 1o lhe Holder, the Units, or any third party resultlng from lnstallation or shipmênt, or from any produc't liability claims of Holder or any lhkd party. For this Um¡ted Wananly to apply, thê Units must bs installed in accordance w¡lh all site conditions required by slate and local cod€s; all olher applicable laws; and lnfiltrator's installalion instruclions. (d) No ropresental¡vs of lnf¡llralor has the authority to changg or extend this L¡mited Waranty. No wananty applies 10 any party other than the or¡ginal Holder. The above rgprgsônts the Standard Umited Wananiy offered by lnfiltralor. A limited number of stales and count¡es have diffsreri wananty requiremenls. Any purohassr of Uniîs should contacl lnfiltrator's ConoralE Headquartsrs ¡n Old Saybrook, Conneclicut, prior to such purchase, to oblain a copy of the appl¡cable warranty, and should carefully read that wananty prior to the purchase of Un¡ts. Ouick4 Plus All-in-One Periscope QUICK4 PLUS ALL,IN.ONE PERISCOPE (360'SWVEL) 12.7'INVERT lq I rì.=..:_ii'tr 4 Busin€ss Park Road P.O. Box 768 Old Sâybrook, CT 06475 860-577-7000 . Fã 860-577-7001 1-800-221-4436 www,¡nf i ltratorwater,com IN FILTRATOR' water technologies U.S. Patents: 4,759,6ô1; 5,01 7,041; 5,1 56,488i 5,336,017; 5,401,1 16; 5,401,459; 5,51 1,903;5,71 6,1 63; 5,588,778i 5,839,844 Canadlan Patenls: 1,329,959; 2,004,54¡ Oth8r pat€nts p€ndlng. lnfi ltrator, Equalizsr,Qu¡ck4, and Sld6wnd€r arè reglslarod tEdemarks of lnflltÉtor Water Tæhnologl6 lnffltrator is a reglsteßd tfademark in Fmnca. lnflllrator waterTæhndoglæ is a r€glstef€d tÞd€matk ln Msx¡co, CorÌtour, MlcrcL€achlng,PolyTufi, Chamb€tspac€r, MultlPorl, PoslLock, Qulckcut, QulckPlay, Snaplmk and StÊightLock aË trad€marks of lnflllralo¡ Wat€r Tæhnologi$. Polylok is a tradsmark of PolyLok, lnc. TUF-TITE is a r€glstôr€d trad€mark ol TUF-TITE, lNC. Ultrâ-Rlb ls a lrademark ol IPEX lno. PLUSos 0713 @ 2013 lnffnrâtorWatsr Tæhndogls, LLC' Al rlghts æryed. Print€d in U.S.A Contact I nf iltrator Water Technolog ies' Technical Services Department for assistance at 1-800-221-4436 ¡