HomeMy WebLinkAboutSoil and Foundation Investigation 04.29.2022LKP Engineeringo fnc.
CIVIL/GIIOTECHNICAL
¡ili
SOIL AND T'OUNDATION INVESTIGATION
F'OR A
BARN/T{ESIDENCE
LOT 3-40 FA_IRVIEW RD, SrLT
3207, tAR #542
PIN 245s02200038
GARFIELD COUNTY, COLORADO
PROJECT NO. 223606
APRIi,
rl'j
29,2022
PREP{h$b ron,
AARON BORAH
P.O. BOX 1194
GYPSUM, CO 81637
ikwk4@hotmail.com
iiirt,ti
llir'l
r{i i
,ililÏ'
P.o. Box 724,Eagle, co 81631 Tel. (9i20,ù 390-0307 www.LKpEngineering.com
"' .;' .: .
TABLE OF'CONTENTS
EXECUTIVE SUMMARY
SCOPE OF STUDY
SITE DESCRIPTION
PROPOSED CONSTRUCTION .......
FIELD INVESTIGATION
SUBSURFACE SOIL AND GROUNDV/ATER CONDITION ...
F OLTNDATION RECOMMENDATI ONS
SLAB CONSTRUCTION ....r....,........
RETAINING V/ALLS
UNDERDRAIN SYSTEM........
SITE GRADING AND DRAINAGE
LAWN IRRIGATION...............
F'IGURES
LOCATION SKETCH
AREA MAP.
SUBSURFACE EXPLORATION LOGS.......
SV/ELL-CONSOLIDATION
GRAIN-SIZE DISTRIBUTION.
PERIMETER DRAIN DETAIL,.
....FIGURE NO. 3
.....FIGURE NO. 4
......FIGURENO. 5
2
2
2
J
J
J
4
4
5
5
6
6
7
.DRAWING NO. 1
.DRAWING NO. 2
.FIGURE NO's l-2
LKP Engineering,Inc.
EXECUTIVE SUMMARY
The proposed bamlresidence should be supported with
conventional type spread footings, designed for an allowable soil
bearing pressure of 2000 psf. They should construct the footings
on the undisturbed silty to sandy clay to silty-clayey sand. see
f,'oundation Recomm endations.
SCOPE OT'STUDY
This report presents the results of a subsurface Soil and Foundation Investigation for a
proposed residence to be constucted on Lot 3-4, Fairview Rd, Silt,3207 CR #342, pIN
245502200038 (address not assigned yet), Garfield County, Carbondale, Colorado. The purpose
of the subsurface soil and foundation investigation was to determine the engineering
characteristics of the foundation soil and to provide recommendations for the foundation design,
grading, and drainage. Geologic hazard studies are outside of our scope of services.
SITE DESCRIPTION
Lots 3 and 4 are 74.3 acres land on Fairview Drive, off of County Road #342, Silt,
Garfield county, colorado. The building site for the proposed bamlresidence is on a meadow.
Vegetation within the proposed building site consisted of grass. The topography within the
selected building area (where the two test pits had been dug prior to our site visit) is relatively
flat' Drainage is to the north and east. Fairview Drive runs along the eastern property line. To the
north and south of the eastern half of the lot are existing residences. The surrounding land to the
northwest, west and southwest is vacant. The subject property is also vacant.
LKP Engineering,Inc.
4
I.OUNDATION RECOMMENDATIONS
The proposed residence should be supported with conventional type spread footings,
designed for an allowable soil bearing pressure of 2000 psf. They should construct the f.ootings
on the undisturbed silty to sandy clay to silty-clayey sand.
The completedfoundation excavation should be observed and/or tested by the
undersigned engineer to veri/y that the soil conditions encountered during construclion ure as
anticipated in this report.
We recommend a minimum width of 16 inches for the continuous footings and2 feet for
the isolated flcoting pads. Continuous foundation walls should be reinforced top and bottom to
span an unsupported length ofat least 10 feet.
The proposed foundation should be set at a minimum depth of four lèet below the
finished grade or at the minimum depth required by the local building code. The foundation
excavation should be free from excavation spoils, frost, organics and standing water. We
recommend proof'-rolling of the foundation excavation. Soft spots detected during the proof-
rolling, should be removed by overexcavation. Any overexcavation within the proposecl
lbundation should be backfilled, in 8 inches loose level lifts and compacted to l00o/o of the
maximum dry density and within 2 percent of the optimum moisture content as determined in a
laboratory from a Standard Proctor test (ASTM D-698). A structural fill, placed under ftrotings
shoultl be tested by a qualified professional.
SLAB CONSTRUCTION
The natural on-site soils, exclusive of topsoil and organics, are suitable to support lightly
loaded slab-on-grade construction. The subgrade ftrr the slab-on-grade construction should be
proof compacted to detect and remove soft spots. They should backfill overexcavated soft spots
and other underslab fill with the on-site soil, free from topsoil and organics, or other suitable
material, compacted to a minimum of 95 percent of the maximum standard Proctor density
(ASTM D-69S). Suitable material should be free from topsoil, organics and rock fragments
P.O. Box 724,F,aglo, CO 81631 Tel. (970) 390-0307 rv"l,ryrv.I,KÎliJrqingoJ,inF'conr.
5
greater than 3 inches.
The concrete slab should be constructed over a -inch layer of clean gravel consisting of
-314 inch gravel with at least 50% retained on the No. 4 sieve and less than 3 percent passing the
No. 200 sieve.
They should reinforce the concrete slab-on-grade and score control joints according to
the American Concrete Institute requirements and per the recommendations of the designer to
reduce damage due to shrinkage. The concrete slab should be separated from the foundation
walls and columns with expansion joints to allow þr independent movement without causing
damage.
RNTAINING \ilALLS
Foundation walls retaining earth and retaining structures that arc laterally supported
should be designed to resist an équivalent fluid density of 60 pcf fbr an "at-rest" condition.
Laterally unrestrained structures, retaining the on.site earth, should be designed to resist an
equivalent fluid density of 40 pcf for the "active" case.
The above design recommendations assume drained backfill conditions and ahorizontal
backfill surface. Surcharge loading due to adjacent structures, weight of temporary stored
construotion materials and equipment, inclined backfill and hydrostatic pressure due to
undrained backfill should be incorporated in the design. They should try to prevent the buildup
of hydrostatic pressure behind the retaining wall.
Passive earth pressure of360 psfcan be used for the lateral pressure against the sides of
the fbotings. Resistance to sliding at the bottom of the footings can be calculated based on a
coefficient of friction of 0.5. Undisturbed soil or a structural fill compacted to 100 percent of the
maximum dry density and within 2percent of the optimum moisture content will be usecl to
resist lateral loads at the sides of the footings.
UNDERDRAIN SYSTEM
To reduce the risk of surface water infiltrating the foundation subsoil, we recommend
P.o. Box 724,Eagle, co 81631 Tel. (970)390-0307 www.LKpEngineering.com
tt:|l1l'/ /. t'{ )i' | )M (iitrt¡{!11, tl{)ttt}lV l.;l¡{, l.-Xl}lrrr{}t
I.t
j
I,t
t¡:'i¡'':
l.: :¡ r
",7
1.?t ) ,:
'¡ ¡r t:,
lllr::1ll "Í ¡.,
l¡1+ il,,.J
SITE
Õ
o
É.
=u
É.
atL
| í{"
i i z .';"!;ì ¡.1,r j!ri'
l*r*--.ffi:::::-Hti t :ittlÀ
{,:urfirkl t utnt.l Garfleld County Colorodo Land Explorer
T
AREA MAP
22-3606
-1"=2miLKPEngineering, Inc.
P.0. Box 724, Eogle, CO 81631
Tel
clvrllcEo'rEcHNIcÁr
comJ90-0307 www.LKPEn
LOTS 3 & 4, SECTION 2, T8S, R83W, 6TH P.M.
FAIRVIEW ROAD
COUNÏY ROAD NO. 342
GARFIELD COUNTY, COLORADO DRAWING NO.:
2
Test Pit f IDATE OBSERVED: APRIL 23,2022
ELEVATON:
DEP'IH
FEET
s
Y
M
B
o
s
A
M
P
L
E
DESCRPNON OF MATERIAL
AND SAMPLE LOCANON
LABORATORY
TEST RESUL'IS
REMARKS
Topsoil wÍth roots
Dark brown, blocky cloy over siltS4
sondy clay, moist
Light brown, silty-cloyey sand
MC=772
106,6 pcf
18.7 Z
_f0
_20
5
Bottom of Pit ot I feet Ground Water
Encountered
f - Eulk SampleDD - Natural Dry Denslty (pcf)MC - Naturol Moisture Content
-2O0 - Percent Passlng No. 200LL - Lìquìd LìmìtPl - PlosticÍty lndex0W - Ground water
(E)
Sìeve
LEGEND:
tr - 2-lnch O.D. Colifornla Lìner Sample
22-3606
TKP ENGINEENING, INC.SUBSUNFACE DXPTORATION tOG
1
Test PÍt f 2DATE OBSERIED: ApRtL 2J, 2022
ELEVATION:
DEPTH
FEET
s
Y
M
B
o
s
A
M
P
L
E
DESCRPNON OF MATERIAL
AND SAMPLE LOCANON
LABORATORY
TEST RESULTS
REMARKS
Topsoil with roots
Dork brown, blocky cloy over silty,sandy clay, moist
Light brown, sitty-cloyey sand
_10
_15
_20
5
Bottom of Tes Pit at 5 feet Ground Water
Encountered
200
trt
DD
MC
LL
PI
GW
(ß)
Sleve
LEGEND:
- 2-lnch O.D. Callfornla Ltner Sample- Bulk Sampte
- Naturol Dry Denstty (pcf)
- Noturol Molsture Content- Percent Passing No. 2OO- Liquid Limtt- Plosticlty lndex- Ground woter
22-J606tKP ENGINEERING, INC.SUBSURFACE EXPTORATION I.,OG
2
3
2
0
c.9
(DcU
,ï*
-l
-2
-3
bS
-4
-5
-6
-7
-8
-to
-fi
-9
5
4 lll
lll
llt
lll
lll
lll -!l
MOVEMENT WHEN WETTED UNDER
CONSTANT PRESSURE OF IOOO PSF
ll
lt
ll
ll
ll
ll
ll
ll
llil I0.1 1.0 100
APPLIED PRESSURE - ksf
Somple of : Llght brovn, sttty Ctdy
Notural Dry Unit Weight = -î06.6
Noturol Moìsture Content : lg,7
from:Tcst Plt I at B'pcf
percent
IJP Englnctlng, lnc,
P7taÌúcr No.:
22-3606
-12
Swell - Consolídation Test Results
3
oîo2030IG40È50$dq60 .b\F70sEO90100o.o0'lo.oa,FRØl: Test Pît I at I feetHWRatÆfRo.1 0.o5m ,Ø,,.þ nU.S STAilDARÐ .sEl,tf ¡V{¿r&æS31 6 8r0 ,,1 tc z) æaæ1 0.5105Sond: 82.52rã alU.S STATIDARD WE OFETf,NO IN NC'Tã56 1 3 2rtA I stoo 50100500908070I$60s$u,q€+oFS .ro20to0il\\t\\\\\il.IilililSllt or ClayfînemedíumSandcoargeGravelfinecoots'e ICobblesFïnes: î7.52Descrþtion: Sitt¡rclayey sondGravel: OZMoísture Content: 7.72r$rosogsìf)$IaNÞØ*qIPà
Þ
ÞÞ
.Þ.
Þ
Þ Þ
ôÞ
'Þ
\¡
S
ðÈ\a
\-!o
L¡_
Þ
Þ
ÞÞ
AWAY FROM BUILDING
BACKFILL WITH A MINIMUM
OF ONE FOOT OF RELATIVELY
IMPERVIOUS SOIL
TER FABRTC (MtRAF|
140N OR EQUTVALENT)
3/4-INCH DIAMETER, COARSE,
CLEAN CRUSH ROCK
30 MIL MINIMUM THICKNESS,INCH DIAMETER PERFORATED PIPE SLOPED TOPLASTIC LINER, GLUED TO TH A DAYLIGHT LOCATION AWAY FROM THE
FOUNDATION AT 1/4-INCH PER FOOT FOR
FLEXIBLE AND 1/8.INCH MINIMUM FOR RIGID PIPE
FOUNDATION WALL
PERIMETER DRAIN
22-3606
scALE; N.T.s
É
LOTS 3 & 4, SECTION 2, TB$, RB3W, 6TH P.M
FAIRVIEW ROAD
COUNTY ROAD NO.342
GARFIELD COUNTY, COLORADO
LKP Engineering, Inc.
cryIL,/GEoTECHMCAL
Tel
P.0, Box 724, Eogle, CO 8'1631
390-0307