Hello Colleen,
Regarding the Architectural Scope comments below:
L. Crawlspace Access Panel. We will be using a Fire - Rated prefab access panel. I have attached the cut sheet for
it. lt is installed on the outside of the 5/8" Type X Gyp Bd, with the flange on the garage side, and opening into
the garage.
2. No mechanical or equipment to be installed in the crawlspace.
3. No mechanical or equipment to be installed in the attic.
Please let me know if you need additionalinformation
Terri
Terri Montoyo Architects LLC
970 3t9.4305
tmarchitectl lc@gmoi l.com
----- Forwarded Message ---
From : Col leen W rth <cwi rth@g arfie ld-cou nty. com>
To: uriel.mellin@hotmail.com <uriel.mellin@hotmail.com>; Brian Kurtz <kurtzengineer@yahoo.com>
Sent: Thursday, July 6,2023a|O2:00:28 PM MDT
Subject: BLRE-06-23-8168 Caleta Construction LLC - 84 Cliffrose Way
BLRE-06-23-8168 Caleta Gonstruction LLC -84 Cliffrose Way is
UNDER REVIEW
Courtesy Message for Uriel M. and Brian K. --
I am currently reviewing the house plans for 84 Cliffrose Way, Lot 43, Pinyon Mesa PUD and have
just a few questions or comments to be addressed before the building permit can be released.
1
MISSING GEOTEGHNIGAL REPORT:
A review of the geotechnical report is required pursuant recorded plat note #8 prior to releasing the
issued building permit.
Unfortunately, no geotechnical report was found in the building application packet
Please submit an electronic copy of HP Geotech report 107-0921dated January 7, 2008 as
referenced by Brian Kurtz on structural sheet S-1.
Email the geotech's report to cwi rth@qarfield-cou nty. com
ARCHITECTURAL AND SCOPE GOMMENTS:
RE: Crawl space access panel
Sheet A2 Main Level Floor Plan shows an opening between the garage and the adjacent crawl space
under the homes main stairs.
Architect labels "24x24 crawl space access panel thru wall"
This access panel will need to comply with 2015 l.R.C. Section R302.5.1 . Opening Protection
Openings ... shall be equipped with solid wood doors not less than 1 3/8 inches in thickness, solid or
honeycomb-core steel doors not less than 1 3/8 inches thick, or 2O-minute fire rated-doors, equipped
with a self-closing device.
CORRECTION:
1. Provide clear detail for proposed access panel.
RE: Crawl spaces and Attic areas
2 Will any mechanical appliances or equipment be installed in the crawl space? lf so,
then provide equipment type and location.
3. Will any mechanical appliances or equipment be installed in attic spaces? lf so, then
identify equipment type and proposed location.
Provide written response via email to cwirth@qarfield-county.com.
No email contact information for Terri L Montoya was included in the application packet, please
forward this correction letter to the Architect of Record.
2
711218,1:1OPlú 21'x2{ -Fre Raüed l¡çr¡ædAæssDuritr Fhæp
ES
ACCESS
DQERS
ût&E-ob-d3- 8/óg
ú atf -888-575-24t7
Keynrord(s) or Eem #q
ll HoME
FIRE-RATED
wAus
24'' X24'' - FIRE.RATED INSUTATED PANET WITH FTANGE
A,oh,'ù aTfl?/
I qf,a a¿¿¿E-g
e/(tfiAak
30h
fr$e//t¡w.bestaoæssdæe -æ¡n'Çx-24áp-r¿þúi¡tsuhedæ-dær-rúdrlaruB/1t13
7t12EB,4:lAPlt 21' x 21' - Fr¿ Rabd lnsr¡l¡bd Acccss Dær wiü¡ FlsnSB
24" X^24" . TIRE.RATED II{SUIATED PAI{ET WIIH TI.AIIGE
I
-
ir,
-I
,ì.
BA-PF|-24-24
2{ widex24" high
68 Reviews |lJ esx A eucsroN
t-l--.rrì -ì1 i1..''r-T! l¡r,"-'ì'lì'rì'-JJ r'r-J', lTl ,'i,il-.1
Þ
rth
i
I
THE BA-PFI SERIES
!l
il|.
I
É wnrre A REVTEw
htÞc/lrww.betaccosed ære.ø¡nl1l4-x&4{re-nbúinculaied<mdær+Íüdangs/?/13
7112Í8,4:1OPlú
SKU:
Avcilobilitp
DoorSize:
SxS lnch
2f|x3ú
BA-PFI-24-24
ln Stock
24 vøde x 24 high
Itxlt ltx?2
24" X,24" . FIRE.RATED II{$ULATED PAI{EI WIIH TIAIIGE
2t x 24' - Ftrc Ræd lns¡¡hd Aoæss Dc uffi Flangp
l4xl4 l{x2t l6"xl6' l8'xl8' 22x2t
2tx4{ 3O'x3O' 3tx?t 3ô'x36' 48'x48.
Benefrts:
- Quick qnd eosyto ¡nstol¡
- Adds fire sofety feotures to your building in complionce with fire code
- Slows down the spreod of fire for o spec¡f¡ed period
- Sofely ond securely protects building components
- Sturdy ond duroble with odded insulotion
- Contr¡butes to your ob¡l¡ty to och¡eve |"EED certificotion
- Provides eosy occess for hossle-free mo¡ntenonce ond repo¡rs
$g'ß1 $23t.t7
(You sove $92.47 )
A.s knrt as $2'l.6$rno wilh PayPaI- Learn more
l0 x lO'
t x36'24'12Ë 24.x36.
Quontity: < I
GHOOSE A t0GK / IAIGH: (.)
" ti p ningltool key operoted slom lqtch
ffi n Key operoted cylinder slom lotch $40+ 5 doys
ffir 4 Hondle Operoted Slom Lotch $69+5 doys
F.leocl Slom lotch $63+ 5 dovs
tfr$[R
PRICE
lì
tr I Mortise Slom Lotch (no cylinder) $02+S Ooys
htþe/l¡vrrw.Mørs -ø¡nÍ24-x24&ua&insulatedaccese-door-rvih4angBl 3113
7112fä.,4:1OPlt 2t x24' -Fce RaÞd læ¡¡trd Aæ Dær wilh Fl¡¡nSp
I fl Mortise slom lotch (with cylinder) $tz¿+ 5 doys
ADD TO CART
Add to Wish List
DESCRIPT¡ON
PrcductSpecSlÎeet
BA-PFI is our fire-rqted insuloted occess door recommended for instollotion in
fire-roted wolls ond ceilings with o full two ¡nches of thick m¡nerol woo¡ which is
thicker thon most ponels. lt is quick ond eosy to instoll ond feqtures o one-¡nch
flonge ideolfor eosy ¡nstollot¡on on ony surfoce. lf project code requires o fire-
roted occess door for your commerciql building BA-PFI is the right choice!
CONVENIENCE: Accurotely meosured for quick-ond-eosy instollqtion on fire-
roted wolls ond ceilings.
PREVENTIOil: Fire-roted doors help slow down the spreod of o tire tor s limited
time.
EIIVIRONMENTAL IEED V4 compliont - contr¡butes to your obilityto ochieve LEED
certificotion.
HASSIE-FREE: Provides eosy occess for hossle-lree mo¡ntenonce snd protects
building components.
DUÎAHUTY: Solid steel construction odds sturdiness ond durobility to your
commerclol bulldlng.
whychoose BA-PF!?
COMPUAilCE: BA-PFI is one of our most-trusted fire-roted oceess ponels. lt is
specificolly monufoctured to odd fire sofety teotures to your building ín
complionce with fire sofety stondords, As per UL ond NFPA stondords, once the
instollqtion is complete ond the provided springs ore hooked to the bock of the
pone¡, the door will be self-closing ond self-locking.
ÄCa:fsgnlllTV' RÂ-pFl nrnrrir{oc êñerr ñ^nêee fô rrrêña hohind r¡rrnllc nr noilinnc f¡rr
htÞo//hmv.boeúaædæc.ørrrfrì4-x-i244arôbd-¡nsu¡atod€@so"d6r.rilh.fungol
6) oowr¡r-olo
4l1E
7l12t&, 4:1O F1lú 21' x 21' - Fi¡e Rabd lnsuffid Acæss floor wÚrl Fl¡ange
ñvt-Yvttt- ' " ¡ î'l vt 'uvs vvgt vvvvgv ls Itsltv v' vv:¡¡¡ 'Yv rvr
hossle-free mo¡ntenonce, wh¡le sofely ond securely protecting building
components occording to code. BA-PFI con help with your business's progress
toword LEED (Leodership in Energyond Environmentol æsign) certificotion which
con help with tox breoks ond other benefits.
PROTECTIOH: BA-PF¡ protects your gos lines, electricsl wiring plumbing, heoting
ventilotion, ond oir conditioning by helping conto¡n the fre. BA-PFI is built to
withstond the heot from o fire for q certoin omount of time before foiling. Thot
gives time to either control ond put out the fire or help people exit the bu¡ld¡ng.
BA-PFI hos qn octive lotch bolt thot con withstond the pressure thqt o fire con
cquse. Pressure discreponcies cqn force non-lotched doors open, ollowing the
fire to spreod. Access doors con olso hove either outomotic or monuol lotching
mechonisms.
PREI/81{TION: BA-PFI helps to keep oirfrom possing through thot con feed o fire.lt
olso helps to prevent smoke from spreoding.
GETTO KNOW BA-PFI
BA-pFt is monufoctured with o l6-gouge cold rolled steel frome ond o 20-gouge
golvonneoled steel door w¡th 2 inches of minerolwoolfor insulot¡on, lt comes
equipped with o slom lotch qnd continuous piono h¡nge, inside ponel releose,
qnd is finished with DuPont high quolity white powder cooL Fire-roted occess
doors help to reduce the spreod of fire for o limited period.
BA-PFI fire-roted occess ponel comes with o one-inch flonge for o quick flush
¡nstollot¡on on ony surfqce. lt is excellent for industriol, commerciol, or residentiol
projects where q fire-roted product ¡s needed by code.
MAXIMUM SIZE FOR VERT|CAI WAll.jS
The moximum size for verticql wolls is 48" x 48" (tZtS mm x l2l9 --), moximum
oreo of 23o4in2, toleronce on height snd width limitotion is 3" (ZO mm) if the oreo
does not excee d 2304 in2.
MAXIMUM SIZE FOR l{ORlZOt{TAt CEIUilGS
The moximum size for horizontol ceilings ls 24 x 36" (OlO mm x 9t4 mm) (ninges
qnd lotches on the side of 36"), toleronce on dimension limitotions is f (20 mm) ¡t
the qreo does not exceed 864 in'z.
Feotures
r 20-Gouge Golvonneol Steel Door
. Ring/Tool Key operoted slom Lotch
r l" Floñgê
htþs:/îfrnv.b€stacæssdoors.wnf¿a*2aÃre+aþúi¡tsuhedæ.doorrvih4arryB"/5t13
7112tâ,4:1OPìû 2tx2t -âte Rabd ln¡uhdÂcæsstt@rwiüt Flange
o Cont¡nuous P¡ono Hinge. 2!l M¡nerolWood lnsulqtion lnside
BA-PFI FIRE.RATING I]{FORMATIOIìI
Fire-rqted trccess doors, for VERTICAL use, ore subiect to the following:
certificotion: uL loB (2009), NreR 2s2(2012), cAN/uLc sl04 (2olo).
Roting Achieved: 3 hours, neutrol/negotive pressure
Moximum size:48" x 48" (tZt9mm x l2l9mm), moximum oreo of 23O4 in2, toleronce
on heightondwidth limitotion is 3'(ZOmm) if theoreo does notexceed2So{inz.
Temperoture rise:250oF (lZl"c) ofter 30 minutes ond 450oF (Zgfc) ofter 60
minutes.
Fire-roted occess doors, for HORIZONTAL use, ore subject to the following:
certificotion: ASTM EIg (20t2), CAru/UlC SlOt (2007)
Roting Achieved 3 hours in non-combustible construction ond I hour in
combustible construction
Moximum size:24X36" (610 mm X 914 mm) (ninges ond lotches on the side of
36"), toleronce on dimension limitotions is 3" (zO mm) if the oreo does not exceed
864 in'z.
Temperoture rise: Wlthin ollowqble per ASTM Ellg ond CAN/ULC SlOl
MOUHNNG CONSTDERATIOìIS:
An occess door thqt m¡ght be good for 60 minutes mounted on flommoble
wooden studs could be good for three hours on o non-flommoble enclosure. The
lotter tokes more time qnd o little more finonciol investment but provides better
sofety ond security in cose of o severeflre event.
I.EED V4 COMPUAilCE
LEED Certificotion USA:
LEED-NC New Construction & Mojor Renovotions
LEED for Schools
LEED-CI Commerciol lnteriors
LEED Certificqtion CANADA:
LEED Conodo-NC New Construction & Moior Renovotions
F¡tÞe:r/*w.berbædoors- ænl2l-x-2$fri*¡rftd.ißublêúroorr+doo¡.ryiür4arup/6113
7112Í|3.,4:lOPlú 2,F x 21' - f:xe Rded lnsubbd Acess Dør with Flarye
LEED Conodo-Cl Commerciol lnteriors
Our world-closs customer serv¡ce teom looks forword to discussing oll your
Access Door needs todoy! Feelfree to contoct us ot l-888-509-2941or by emo¡l
vio info6lbestoccessdoors.com
For more informatbn relevont to BA-m, peose see the folbwing articles:
o A Closer Look ot the Key Differences Between BA-PFl's Models
o Do Fire-Roted Access Doors STOP Fires?
o Discover the Benefits of lnstolling BA-PFl
r BA-PFl Fire-Roted Access Door:Your 5 Questions Answered
sEE BA-pÍl-24-24 H ACTtoil oil YoUïUBE!
How Do I lnstall Fire Rated lnsulated Accer
r
:g;,å;
How Do I lnstoll Fire Roted
lnsuloted Access Doorwith l"
Flang& (The BA PH)
The BA-PFI Fire Rqted occess door ls
insuloted with Z thick m...
t"EÜ
Do Access Psnels Need to Be Fire
Roted? - Fire Rsted Access Door
wlth l" Flonge (et-pfl)
Fire Roted Access Door: The BA-PR
hüps:lffi.bêstacæssdærs.ørnl2tÞx-24ãre-raÞúinsuhled-accese.dær-ríhflarpe/7113
Written responses to items #1 - #3 can be addressed in a written narrative or email reply and stapled
to the issued FIELD COPY.
We will not ask for resubmission of the complete architectural sheets at this time
Thank you,