HomeMy WebLinkAboutPlansDESIGNS ,,BUILT FROM THE GROUND UP " SUNLIGHT MOUNTAI N SKI AREA I SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO RETAINING WALL (RW) CONSTRUCTION ADDRESSED BY THESE DRAWINGS ARE PART OF A SIGNIFICANTLY IARGER PROJECT BEING BUILT BY THE GENERAL CONTRACTOR, WHO HAS SEPARATELY RETAINEO AN EARTHWORK GRADING CONTRACTOR TO ASSIST IN DEVELOPING THE SITE FOR THE OWNER. THE OWNER HAS RETAINED A PROJECT GEOTECHNICAL ENGINEER TO ADVISE IT ON MATTERS RELATIVE TO CONSTRUCTION AND WHO WILL BE PROVIDING QUALITY ASSURANCE TESTING AND OBSERVATION OF THE RW CONSTRUCTION WORK FOR THE OWNER. OUTLINED BELOW IS A BRIEF SUMMARY OF THE RESPONSIBILITIES OF EACH OF THE PARTIES REQUIRED BY THE RW CONSTRUCTION, AS OUTLINED IN THESE DRAWNGS, TO ENSURE A QUALITY CONSTRUCTION PROJECT: A. GENERAL/EARTHWORK CONTRACTOR SHALL BE RËSPONSIBLE FOR OVERALL SITE GRADING AND STORM WATER CONTROL BEFORE, DURING, AND AFTER RW CONSTRUCTION, UNTIL THE PERMANENT PAVING AND STORM WATER DRAINAGE CONTROLS ARE ALL IN PLACE AND OPERATIONAL. DAMAGE TO EXISTING RW CONSTRUCTION BY POORLY CONTROLLED STORM WATER DRAINAGE SHALL NOT BE THE RESPONSIBILITIES THE RW CONTRACTOR OR RW DESIGNER. B. GENERAUEARTHWORK CONTRACTOR SHALL BE RESPONSIBLE FOR EROSION AND SEDIMENTATION CONTROL, BEFORE, DURING, AND AFTER RW CONSTRUCTION.C. OWNER AND/OR GENERAL CONTRACTOR SHALL PROVIDE SURVEYING SERVICES SUFFICIENT TO LOCATE THE WALL, HORIZONTALLY AND VERTICALLY ON THE SITE FOR CONSTRUCTION PURPOSES.D. GENERAL/EARTHWORK CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A BEARING SURFACE AT THE BOTTOM RETAINING WALL ETEVATION THAT MEETS THE BEARING REQUIREMENTS SHOWN ON THESE DRAWINGS, THE BEARING SURFACE AND ALL AREAS INTO WHICH THE RW CONTRACTOR WLL PLACE AND COMPACT FILL MUST BE CLEARED, GRUBBED AND ALL DELETERIOUS SOILS AND/OR ORGANIC MATTER REMOVED TO PROJECT GEOTECHNICAL ENGINEER'S SATISFACTION, AS PROVIDED IN THEIR DAILY PROJECT REPORTING.E. THE OWNER'S PROJECT GEOTECHNICAL ENGINEER SHALL OBSERVE AND PROVIDE WRITTEN APPROVAL THAT THE "ALLOWABLE' BEARING CAPACIW AT THE BOTTOM RETAINING WALL ELEVATION AND WTHIN THE ENTIRE REINFORCED (GEOGRID) ZONE IN EACH LOCATION MEETS OR EXCEEDS THE MINIMUM REQUIREMENTS SHOWN ON THESE DRAWINGS. THE RW CONTRACTOR WILL NOT BEGIN CONSTRUCTION WITHOUT THE APPROVAL. F. THE OWNER AND/OR GENERAL CONTRACTOR SHALL PROVIDE THE FILL SOILS TO THE RW CONTRACTOR TO UTILIZE FOR RW CONSTRUCTION. THOSE FILL SOILS SHOULD BE TESTED PRIOR TO STARTING RW CONSTRUCTION, AND PERIODICALLY THROUGHOUT THE PROJECT, TO ENSURE THEY MEET THE SPECIFICATION OUTLINED HEREIN. RW CONTRACTOR WILL NOTIFY THE OWNER'S GEOTECHNICAL ENGINEER AND/OR THE GENERAUEARTHWORK CONTRACTOR WHEN A CHANGE IN FILL SOIL APPEARANCE, CONSISTENCY, OR GRADATION LOOKS TO BE DETRIMENTAL, OR HAS REASON TO BELIEVE THE SOIL BEING PROVIDED DOES NOT MEET THE PROJECT SPECIFICATIONS. HOWEVER, THE OWNER'S GEOTECHNICAL ENGINEER SHALL BE RESPONSIBLE FOR DETERMINING WHETHER THE FILL MATERIALS MEET AND ARE PLACED ACCORDING TO THE SPECIFICATIONS IN THESE DRAWINGS.G, THE OWNER AND/OR OWNERS REPRESENTATIVE SHALL BE RESPONSIBLE FOR CONTRACTING THE SPECIAL INSPECTOR AND OBTAINING SUFFICIENT DATA THROUGHOUT THE RW CONSTRUCTION TO SATISFY THE REQUIREMENTS OF THE LOCAL GOVËRNING AUTHORITY TO SECURE APPROVAL OF THE RETAINING WALL CONSTRUCTION AND BY PERFORMING THE DUTIES OUTLINED IN SPECIFICATION 8.0. SHEET INDEX SHEET DESCRIPTION TITLE SHEET CONSTRUCTION NOTES CONSTRUCTION NOTES WALL LOCATION PLAN VIEW WALL 1 ELEVATION WALL 2 ELEVATION WALL 3 ELEVATION WALL SECTION A-A WALL SECTION B-B CONSTRUCTION DETAILS RW-1.0 RW-2.0 RW-2.1 RW-3.0 RW4.O RW-4.1 RW4.2 RW-s.0 RW-s.1 RW-6.0 191 8/6/23 vit -E!t Fi ÉEJ E-!=J l¡lg¡ Ft HFIF: IgJ FA =ffi-Hl.gñ.F+ *.L!¡ tgEI= EL ctl Kc¡Imñ¡ I4lE¡IE¡cl E CJ -b -¡+l -Ètrt II --b I¿vit II.Xn 7 6 à 4 2 I 0 06 AUG 2023 RELEASED FOR CONSTRUCTION CF CF BD THIS DRAWING IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY. ANY PARTY ACCEPTING THIS DOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSED TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS @ 2023 Geowall Designs, LLC.No.Date R€v¡s¡on Drawn Design Check Signatuß Stons 211 30lh Sl., Græley, CO 80631 (970) 351,0270 M.signeturestone,com Sales: Seth Clârk (970) 539-2201 sclark@signâlureslone.com TITLE SHEEÏ 06 AUG 2023 N.T.S Titl6: Daler Scalel SEGMENTAL RETAINING WALL PLANS Projecl No: 23SS1014 Shæt No: RW-í.0 SUNLIGHÏ MOUNTAIN SKI AREA - SEGUNOO LIFT TERMINAL GLENWOOD SPRINGS, CO 9i:.10i.1 r 90 \\'\\'\\'.(il:o\\ r\ t.t.¡)l:sl(;Ns.('o\.f ,BL]ILT FROM THE GROLJND UP' ItlN: l5{¡i ( l-lIl:l{OÀl) l:. l}tilì\SVlt.l-l:. ñ1h 55-ì17 ( O: I S50 \\'()Ol)l\4ooll l)lìl!l: Stl ll l, l0l. l\loNt li\11:l\ L ( o ll0 I 12 EnBsrcNS= -- 7 CONSTRUCTION NOTES ïitle: þ 5 4 5 SUNLIGHT MOUNTAIN SKI AREA SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO SEGMENTAL RETAINING WALL PLANS 1 CF CF BDRELEASED FOR CONSTRUCTION006 AUG 2023 N.T.S. Scâlo:Shæt Noi RW-2.0 I,f) MA BACKFILL SOILS 1.'1.1 REINFORCED FILL 1 MATERIALS SHALL BE APPROVED IN WRITING BY GEOWALL DESIGNS AND THE OWNER'S REPRESENTATIVE AND SHALL MEET THE STRENGTH REQUIREMENTS AS DEFINED IN SECTION 6.0. THE REINFORCED BACKFILL MATERIAL SHALL MEET THE FOLLOWING GRADATION: SIEVE SIZE PERCENT PASSING314" 75-100o/oNo.4 30-50%No.50 15-50%No.200 5-35% PLASTICITY INDEX (PI) LESS THAN 4 THE PH SHALL BE BETWEEN 3 AND 9. 1.1,2 REINFORCED BACKFILL AND RETAINED SOIL/FILL MATERIALS SHALL BE FREE OF EXCESS MOISTURE, ROOTS, MUCK, SOD, SNOW, FROZEN LUMPS, ORGANIC MATTER OR OTHER DELETERIOUS MATERIALS. ALL ROCK PARTICLES AND HARD EARTH CLODS SHALL BE LESS THAN FOUR INCHES IN THE LONGEST DIMENSION. REINFORCED BACKFILL MATERIALS WHICH DO NOT MEET THIS CRITERIA SHALL BE CONSIDERED UNSUITABLE AND REMOVED. 1.1.3 DRAINAGE FILL AND RETAINED SOIL 2 SHALL CONSIST OF CLEAN CRUSHED STONE' CRUSHED GRAVEL, OR CRUSHED RECYCLED CONCRETE MEETING THE FOLLOWING GRADATION TESTED IN ACCORDANCE WITH ASTM C-136: 2.0 TECHNICAL REOUIREMENTS 2.1 THE OWNER'S REPRESENTATIVE OR GRADING CONTRACTOR SHALL SUBMIT TO GEOWALL DESIGNS THE GRADATION AND STRENGTH PARAMETERS OF THE REINFORCED BACKFILL MATERIAL, RETAINED SOIL/FILL AND FOUNDATION SOIL, FOR APPROVAL PRIOR TO PROCEEDING WITH CONSTRUCTION. WORK SHALL NOT PROCEED UNTIL THIS SUBMITTAL IS APPROVED BY GEOWALL DESIGNS. PRIOR TO CONSTRUCTION OF THE WALLS, THE GRADING CONTRACTOR SHALL CLEAR AND GRUB THE REINFORCED BACKFILL ZONE AREA, REMOVING TOP SOILS, BRUSH, SOD OR OTHER ORGANIC OR DELETERIOUS MATERIALS. ANY UNSUITABLE SOILS SHALL BE OVER-EXCAVATED, REPLACED AND COMPACTED WITH REINFORCED BACKFILL MATERIAL TO PROJECT SPECIFICATIONS OR OTHERWISE DIRECTED BY THE OWNER'S GEOTECHNICAL ENGINEER' THE GEOTECHNICAL ENGINEER SHALL CONFIRM THAT THE SITE HAS BEEN PROPERLY PREPARED AND THE DESIGN PARAMETERS IN SECTION 6.0 ARE APPROPRIATE PRIOR TO FILL PLACEMENT. A WRITTEN CONFIRMATION SHALL BE PROVIDED TO GEOWALL DESIGNS PRIOR TO FILL PLACEMENT, F|LL SHALL BE PLACED lN HORIZONTAL LAYERS NOT EXCEEDING 10" (lNcHES) lN UNCOMPACTED THICKNESS FOR HEAVY COMPACTION EQUIPMENT. FOR ZONES WHERE COMPACTION IS ACCOMPLISHED WITH HAND OPERATED EQUIPMENT, FILL SHALL BE PLACED IN HORTZONTAL LAYERS NOT EXCEEDING 6', (INCHES) lN UNCOMPACTED THICKNESS. ONLY HAND.OPERATED EQUIPMENT SHALL BE ALLOWED WITHIN THREE FEET OF THE BACK FACE OF WALL FACING. FILL MATERIALS SHALL BE PLACED FROM THE BACK OF THE FACING UNITS TOWARDS THE ENDS OF THE GEOGRID TO ENSURE FURTHER TENSIONING OR AS DIRECTED BY THE MANUFACTURER. TESTING METHODS AND VERIFICATION OF FILL SHALL BE COMPACTED AS SPECIFIED BY PRoJECT SPEC|F|CAT|ONS OR TO A MTN|MUM 95% (98% MINIMUM FOR WALLS EXCEEDING '10 FT) oF THE MAXTMUM DRy DENSITv AND WtTHtN +l-2% oF THE OPTIMUM MOISTURE CONTENT IN ACCORDANCE WITH STANDARD PROCTOR (ASTM D698). MATERIAL SPECIFICATIONS AND COMPACTION TESTING IS THE RESPONSIBILITY OF THE OWNER'S REPRESENTATIVE. 2.6.1 WHERE COMPACTION OF STONE BACKFILL CANNOT BE VERIFIED USING IN-SITU FIELD DENSITY TEST METHODS, THE FILL SHALL BE COMPACTED USING APPROPRIATE VIBRATORY EQUIPMENT AS APPROVED BY THE SITE GEOTECHNICAL ENGINEER. THE CONTRACTOR SHALL MAKE A SUFFICIENT NUMBER OF PASSES WITH APPROVED ROLLING EQUIPMENT UNTIL THE SURFACE SHOWS NO VISIBLE SIGN OF FURTHER CONSOLIDATION. THE SITE GEOTECHNICAL ENGINEER SHALL APPROVE MEANS AND METHODS AND VERIFY COMPACTION. WHERE REQUIRED, CAP UNITS SHALL BE PERMANENTLY SECURED TO THE BLOCK UNITS USING AN OUTDOOR CONSTRUCTION ADHESIVE FOR CONCRETE MASONRY OR HARDSCAPES SUCH AS LIQUID NAILS (OR EOUIVALENT). ADHESIVE SHALL BE PLACED PER MANUFACTURERS RECOMMENDATIONS. AN APPROVED SET OF CONSTRUCTION DRAWINGS AND CONTRACT SPECIFICATIONS SHALL BE ON-SITE AT ALL TIMES, DURING CONSTRUCTION OF THE RETAINING WALLS. 2.2 2.3 2.5 2.7 3.0 GEOGRID PLACEMENT 3.1 GEOGRID SHALL BE PLACED AT THE LOCATIONS AND ELEVATIONS SHOWN ON THE CONSTRUCTION DRAWINGS. 3.2 GEOGRID LENGTH SHALL BE AS SHOWN ON THE CONSTRUCTION DRAWINGS. GEOGRID LENGTH IS MEASURED FROM THE FRONT FACE OF WALL UNITS TO THE TAIL OF GEOGRID UNLESS OTHERWISE NOTED. 3,2,1 GEOGRID REINFORCEMENT SHALL BE CONTINUOUS THROUGHOUT THEIR EMBEDMENT LENGTH(S). 3.2.2 GEOGRID SHALL BE PLACED AT THE COVERAGE AS SHOWN IN 6.2.1 3.3 PRIOR TO PLACING FILL, THE GEOGRID MATERIALS SHALL BE PLACED IN BETWEEN BLOCK COURSES. REMOVE GEOGRID SLACK AND ANCHOR GEOGRID PRIOR TO FILL PLACEMENT AND COMPACTION. CONSTRUCTION EQUIPMENT SHALL NOT BE OPERATED DIRECTLY ON THE GEOGRID. A MINIMUM FILL THICKNESS OF SIX INCHES IS REQUIRED FOR OPERATION OF TRACKED VEHICLES OVER THE GEOGRID. TURNING OF VEHICLES SHOULD BE KEPT TO A MINIMUM TO PREVENT DISPLACING THE FILL AND/OR THE GEOGRID. 3.5 GEOGRID SHALL BE ROLLED OUT WITH THE LONG AXIS OF THE APERTURES (MACHINE DtRECTION) PERPENDICULAR TO THE WALL FACE FOR UNIAXIAL GEOGRID. 3.6 A MINIMUM OF 3 INCHES OF FILL MATERIAL SHALL BE PLACED BETWEEN OVERLAPPING LAYERS OF GEOGRID, UNLESS OTHERWISE SHOWN. 4,q çHAÌ,¡_gEs 4.1 NO CHANGES TO THE GEOGRID I.AYOUT, INCLUDING, BUT NOT LIMITED TO, LENGTH, GEOGRID TYPE, OR ELEVATION, SHALL BE MADE WITHOUT THE EXPRESSED PRIOR WRITTEN CONSENT OF GEOWALL DESIGNS. 4.2 NO CHANGES TO THE WALL FACING WPE SHALL BE MADE WITHOUT THE EXPRESSED PRIOR WRITTEN CONSENT OF GEOWALL DESIGNS. 5,0 DRAINAGE 5.1 AT THE END OF EACH WORK DAY, BACKFILL SURFACE SHALL BE COMPACTED WITH A SMOOTH PLATE COMPACTOR TO MINIMIZE PONDING OF WATER AND SATURATION OF THE BACKFILL 5.2 PERMANENT AND TEMPORARY SURFACE WATER DIVERSION AND EROSION CONTROL SHALL BE AS REQUIRED AND PROVIDED BY THE OWNER OR OWNER'S REPRESENTATIVE. SURFACE WATER SHALL BE DIVERTED AWAY FROM THE REINFORCED FILL ZONE AND WALL FACE DURING WALL CONSTRUCTION OR AT THE END OF EACH WORK DAY. 1.1 3.4 2.4 2.6 SIEVE SIZE 1.s', 1.0, 1t2" No.4 No. I PERCENT PASSING 100% 95-100% 25-60Yo 0-10% 0-5% LOSS BY WASHING 2.0% MAX 1.1 ,4 LEVELING PAD SHALL CONSIST OF DENSE.GRADED, OPEN.GRADED CRUSHED STONE OR CRUSHED GRAVEL. IF OPEN GRADED AGGREGATE IS USED IN WATER APPLICATION, LEVELING PAD SHALL BE WRAPPED WITH NON.WOVEN GEOTEXTILE. 1,2 GEOGRID REINFORCING TYPE SHALL BE AS SHOWN OR APPROVED EQUAL, THE GEOGRID MANUFACTURER SHALL PROVIDE A MATERIAL CERTIFICATION THAT THE PRODUCT SHIPPED TO THE PROJECT MEETS OR EXCEEDS THE ULTIMATE, LONG TERM DESIGN STRENGTH, AND CONNECTION STRENGTH USED IN THE DESIGN. 1,3 BLOCK FACING SHALL BE REDI.ROCK, 28" AND 41' UNITS. UNITS SHALL MEET ASTM C1372 FOR DRY CAST BLOCK OR C1776 FOR WET CAST CONCRETE, EXCEPT MANUFACTURED CONCRETE VERTICAL DIMENSIONAL TOLERANCE SHALL BE +I- 1116"' CONCRETE SHALL BE OF ORIGINAL PRODUCTION MIX WITH A MINIMUM COMPRESSIVE STRENGTH OF 4,500 PSI. AIR CONTENT, MIX DESIGN, ABSORPTION, AND FREEZE THAW EXPOSURE CLASS SHALL MEET THE SPECIFICATIONS AS REQUIRED BY THE CONTRACT DOCUMENTS AND INDUSTRY BEST PRACTICES. 1.4 FTLTER FABRIC SHALL BE 4 ozlsy (MlN.) NON-WOVEN, NEEDLE PUNCHED, POLYPROPYLENE GEOTEXTILE - ERS 4OON OR EQUAL. 1,5 DRAIN PIPE SHALL BE 4" DIAMETER SINGLE WALL HDPE PIPE WITHOUT FILTER SOCK' OR APPROVED EQUAL, PIPE AND PIPE FITTINGS SHALL MEET ASTM F4O5 AND F667. 4- FLEX DRAIN IS A PRE APPROVED ALTERNATE. 2.8 8/6/23 '1 91 23SS1014 No: 06 AUG 2023 D¿te: ffi Çnnsrc*sF "I]UILT TROM TIIF, CROUND UP" \lN: l51lì(t.lIl ROÁl) t:. lll-lìNSVttl-l:. ltl¡l 55-l1r ( O: IsJO\\'OOl)\l0Otl ì)RlVlr Sl.JlIl, l0l. \1ONL]|rl|NT (O S0ll2 q5l.l0-ì.Jl 90 \\ \\ \\.GIl0\\,\t.l-Dl:Sl(iNS.( oitl Signaturs Stone Sales: 211 30th St., Greel6y, CO80631 Soth Clark )'"nr; (970) 539-2201 sclark@signaturestone.com (970) 351-0270 M.s¡gnaturestone.com Drawn Design CheckNo.Date Revision THIS DRAWING IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY, ANY PARTY ACCEPTING THIS OOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSED TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS @ 2023 Geowall Designs, LLC. 7 CONSTRUCTION NOTES Tit¡€: 6 4 â 2 CF BDCFRELEASEO FOR CONSTRUCTION006 AUG 2023 6.0 DESIGN PARAMETERS 6.1 DESIGN OF THE REINFORCED SOIL STRUCTURE IS BASED ON THE FOLLOWING EFFECTIVE PARAMETERS (COHESION ONLY APPLICABLE FOR GLOBAL STABILITY): ZONE DESCRIPTION 0 c'Y REINFORCED SOIL 1 RETAINED SOIL.l RETAINED SOIL 2 FOUNDATION SOIL 1 CLAYEY GRAVEL - GC 28"O PSF 125 PCF SANDY LEAN CLAY - CL 25'75 PSF 125PCF GRAVEL - GP 38"O PSF 1 10 PCF SANDY LEAN CLAY - CL 25'200 PsF 125 PCF 6.1.1 DESIGN METHODOLOGY: NCMA THIRD EDITION, IBC-2018' AND ASCE 7-16 6.2 FACTORS OF SAFETY 6,2.1 INTERNALSTABILITY: 6.6 HYDRAULICCONDITIONS 6.6.1 WATERAPPLICATION THE DESIGN DOES NOT CONSIDER HYDROSTATIC WATER PRESSURE AND ASSUMES WATER IS SUFFICIENTLY BELOW BOTTOM OF STRUCTURE SO AS NOT TO INFLUENCE STRUCTURE STABILIW. 6.6.2 EROSION CONTROUPREVENTION THE CONTRACTOR SHALL ENSURE POSITIVE DRAINAGE IS MAINTAINED BOTH DURING AND AFTER CONSTRUCTION. EROSION PREVENTION AND PROTECTION SHALL BE MAINTAINED ABOVE AND BELOW THE RETAININGW ALL AS DESIGNED BY OTHERS. ALL DOWNSPOUTS, SWALES, AND DRAINAGE FEATURES SHALL BE DIVERTED AWAY FROM THE WALL LOCATIONS. 6.7 WrND LOADING (ASD) WIND LOAD HAS NOT BEEN EVALUATED IN THE DESIGN OF THE BELOW GRADE STRUCTURE. ALL ABOVE FREE STANDING STRUCTURES PLACED WITHIN A 1H:1V OF THE WALL FACING SHALL BE RELOCATED OR REDESIGNED AS TO NOT APPLY ANY ADDITIONAL LATERAL LOADING. 7.0 sPEclAL PROVISIONS 7.1 THE DESIGN PRESENTED HEREIN IS BASED ON SOIL PARAMETERS, FOUNDATION CONDITIONS, GROUNDWATER CONDITIONS, AND LOADINGS STATED IN SECTION 6.0., AND INTERPOLATED FROM INFORMATION PROVIDED BY OTHERS. GEOTECHNICAL DATA IS INTERPOLATED FROM REPORT PREPARED BY KUMAR & ASSOCIATES, INC., REPORT #:22-7.il}, DATED 1112312022, 7.2 WALL ELEVATION VIEWS AND LOCATIONS AND GEOMETRY OF EXISTING STRUCTURES AND GRADE ABOVE AND BELOW THE WALLS MUST BE VERIFIED BY THE CONTRACTOR, TO MATCH ELEVATIONS SHOWN IN THE CONTRACT DOCUMENTS, PRIOR TO CONSTRUCTION. 7,9 GEOWALL DESIGNS ASSUMES NO LIABILITY FOR INFORMATION SUPPLIED BY OTHERS SUCH AS GEOTECHNICAL REPORT, SITE PLAN, AND WATER ELEVATIONS. 7,4 THE SOIL DESIGN PARAMETERS STATED IN SECTION 6.0 SHALL BE VERIFIED BY THE PROJECT GEOTECHNICAL ENGINEER. WRITTEN VERIFICATION OF DESIGN PARAMETERS SHALL BE SUBMITTED TO GEOWALL DESIGNS AND THE OWNER'S REPRESENTATIVE PRIOR TO COMMENCING WITH CONSTRUCTION. 7.5 IF ANY ROCK FORMATIONS AND/OR GROUNDWATER (NOT ADDRESSED WITHIN THESE PLANS) ARE ENCOUNTERED DURING THE CONSTRUCTION OF THIS WALL, IMMEDIATELY CONTACT GEOWALL DESIGNS AT 952.3034190 AND THE OWNER'S REPRESENTATIVE. 7.6 ANY REVISIONS TO DESIGN PARAMETERS STATED IN SECTION 6.0 OR STRUCTURE GEOMETRY SHALL REQUIRE DESIGN MODIFICATIONS PRIOR TO PBOCEEDING WITH CONSTRUCTION. 7.7 ALL PIPES AND UTILITIES WITHIN lOO FEET OF THE RETAINING WALL MUST BE CONSTRUCTED WITH WATER TIGHT JOINTS. 7.8 THE SITE GEOTECHNICAL ENGINEER OR OWNER'S REPRESENTATIVE SHALL BE RESPONSIBLE FOR EVALUATING TOTAL AND DIFFERENTIAL SETTLEMENTS. 7.9 THE OWNER OR OWNER'S REPRESENTATIVE SHALL BE RESPONSIBLE FOR THE SELECTION OF PERMANENT EROSION PROTECTION AND PERMANENT VEGETATION FOR SLOPES LOCATED ABOVE OR BELOW THE PROPOSED RETAINING WALL(S). 8.0 OUALITY RANCE 8.1 DUTIES OF THE SPECIAL INSPECTOR: 8.1.1 THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK REQUIRING SPECIAL INSPECTION FOR CONFORMANCE WITH THE APPROVED DESIGN DRAWINGS AND SPECIFICATIONS. 8.,I.2 THE SPECIAL INSPECTOR SHALL FURNISH REPORTS TO BE KEPT AT THE SITE FOR USE BY THE BUILDING OFFICIAL, THE CONTRACTOR, AND THE ENGINEER OF RECORD. IF SPECIAL INSPECTION IS PROVIDED BY ANYONE OTHER THAN THE ENGINEER OF RECORD, REPORTS SHALL BE SUBMITTED TO THE OFFICE OF THE ENGINEER OF RÊCORD ON A WEEKLY BASIS. ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION, THEN IF UNCORRECTED, TO THE DESIGN AUTHORITY AND THE BUILDING OFFICIAL. 8.1.3 UPON COMPLETION OF THE ASSIGNED WORK, THE SPECIAL INSPECTOR SHALL COMPLETE AND SIGN A FINAL REPORT CERTIFYING THAT TO THE BEST OF HIS/HER KNOWLEDGE, THE WORK IS IN CONFORMANCE WITH THE APPROVED PLANS AND SPECIFICATIONS, AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE CODE. 8,2 SEE THE'SPECIAL INSPECTION SCHEDULE" FOR THE TYPES, EXTENTS, AND FREQUENCY OF SPECIFIC ITEMS REQUIRING SPECIAL INSPECTIONS AS PART OF THIS PROJECT. SPECIAL INSPECTION SCHEDULE REQUIRED SPECIAL INSPECTION AREAS FREQUENCY OF TESTING COMMENTS: CONTINUOUS PERIODIC RETAINING WALLS GEOGRID X INSPECTION SHALL BE MADE OF THE WPE, LOCATION, ORIENTATION, AND EXTENT OF GEOGRID PLACEMENT IN EACH WALL DRAIN TILE :NSTALLATION X INSPECTION SHALL BE MADE OF THE PLACEMENT, LOCATION, AND VENTING TO DAYLIGHT solLs EXCAVATIONS X VERIFY EXCAVATION ARE EXTENDED TO PROPER DEPTHS AND HAVE REACHED REQUIRED MATERIAL SUFFICIENT TO SUPPORT THE DESIGN FIELD DENSITY X IN ACCORDANCE WITH ASTM 0.6938 OR ASTM D-1556 MOISTURE-DENSITY RELATIONSHIPS X IN ACCORDANCE WITH AASHTO OR ASTM CRITERIA AS SPECIFIED FOR SUBGRADE, LEVELING PAD, AND BACKFILL GRADATION ANALYSIS X IN ACCORDANCE WITH ASTM D422 WALL BACKFILL X VERIFY USE OF PROPER MATERIALS DENSITIES, LIFT THICKNESS DURING PLACEMENT AND COMPACTION OF BACKFILL TESTING MAY BE PERIODIC IN NATIJRE BUTCONflNUOUS THROUGHOU¡CONSIRUCI/ONAS REQUIRED BY IgC. MIN, FACTOR OF SAFETY FOR GEOGRID PULLOUT = MlN. FACTOR OF SAFETY FOR BLOCK CONNECTION = MlN. FACTOR OF SAFETY FOR FACING STABILITY = MlN. FACTOR OF SAFETY FOR SLIDING AT LOWEST GEOGRID = PERCENT COVERAGE OF GEOGRID = 6.2.2 EXTERNAL STABILITY: MlN. FACTOR OF SAFETY FOR OVERTURNING (GRAVITY)= MlN. FACTOR OF SAFETY FOR OVERTURNING (MSE) = MlN. FACTOR OF SAFETY FOR SLIDING = MlN. FACTOR OF SAFETY FOR BEARING (THEORETICAL)= 6.2.3 OVERALL / GLOBAL STABILITY: MlN. FACTOR OF SAFETY FOR GLOBAL STABILITY (NON-CRITICAL)= 6.2.4 SEtSMIC MIN. FACTORS OF SAFETY ARE 75% OF STATIC CONDITIONS 1-SECOND DESIGN PEAK GROUND ACCELERATION = 6.3 SURCHARGE LOADING LIVE LOAD (LANDSCAPE AREAS) = LIVE LOAD (ROAD/PARKING AREAS)= DEAD LOAD = 1.5 1.5 1.5 1.5 25% TOP/BOTTOM 50% MIDDLE 1.5 2.0 1.5 2.0 1.3 0.149 't00 PsF 250 PSF N/A 6.4 BEARING 6.4.1 APPLIED BEARING MAXIMUM APPLIED BEARING PRESSURE = (SEE ELEVATION VIEWS) 6.4.2 ULTIMATE BEARING CAPACITY CALCULATED USING SOIL PARAMETERS NOTED IN SECTION 6.0 AND GEOMETRIC PROPERTIES OF THE RETAINING WALL. GEOTECHNICAL ENGINEER SHALL DETERMINE ACTUAL BEARING CAPACITY BASED ON FIELD CONDITIONS AND LABORATORY RESULTS. 6.5 FENCE LOADING WALLS ARE NOT DESIGNED FOR ANY CONCENTRATED FENCE LOADS. SLEEVE-ITS SHALL BE USED WHERE POSTS CANNOT BE PLACED A MINIMUM OF 3.OO' FROM WALL FACE. CONTRACTOR TO VERIFY POST SPACING UTILIZED DOES NOT EXCEED LOAD LIMITS BASED ON IBC LOADING FOR PEDESTRIAN HANDRAILS OR THE DESIGN LOAÐ, WHICHEVER IS GREATER. N 816123 191 ffi ÉnBsrcNsg ,I]UILT FROM TIIE CROLJND UP' Projecl No:Shæt No: RW-2.1N,T.S Scals: 23SS1014 SEGMENTAL RETAINING WALL PLANS Dåtei 06 AUG 2023 SUNLIGHT MOUNTAIN SKI AREA. SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO i\'lN: I 513 ( l.lljf ROAI) l:. lllllìNSVI t t-l:. ltl\ 5i-1'i? ( Or 1350 \\'(lOl)\4OOR ì)RIIl: Stlrll' :()1. Nl(JNtiÑ11:\ L C() ll0l:Ì: t)5:.101.1¡90 \\\\ \\ .( i l:()\\'Àl-Ll)t:S l( i\S.C( )lt1 Drawn Design Check Signaturc Ston€ 211 30th St., Græley, CO 80631 (970) 351-0270 w,s¡gnaturestone,com Salos: Seth Clark (970) 539-2201 sclark@signatureslone.com )'j'ní No.Dete Revision THIS DRAWING IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY. ANY PARTY ACCEPTING THIS DOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IÏ SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSED TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS @ 2023 Geowall Designs, LLc. 7 WALL LOCATION PLAN VIEW fltlel 6 À 4 ? 2 I CF CF BD006 AUG 2023 RELËASED FOR CONSTRUCTION ?3 \l/4 NOTE: 1. SITE PLAN IS FOR ILLUSTRATIVE PURPOSES ONLY AND IS TAKEN FROM THE CONTRACT PLANS PREPARED BY IRON MOUTAIN ENGINEERING, INC. LAST DATED 06/1412023. *2. NORTH ARROW DIRECTION IS APPROXIMATE, REFER TO CONTRACT PLANS FOR ACTUAL HEADING,# 3. REFER TO CONTRACT PLANS FOR ALL HORIZONTAL ALIGNMENT AND ACTUAL SITE GEOMETRY. LEGEND: 9i' - TOPOFWALL F ììP APPROXIMATE GEOGRID COVERAGE 314i C1 . -: ú-a r?L E'41 41iLÊl ¿-41 !ì0 SCALE UNIT _ 1r¡r I 20 10 0 20 40 l¡ I EI f 'Çr!-.1, s: -a 0r; 61 42 5'42 Ft n1)a \Ë 48 83 l5I.. 812e 3C I ",¡.a ì.i. Knowwhafs BEI-OW CALL before you d¡9. BEGIN WALL 2 RW-STA. OO.OO END WALL 2 RW-STA.120.75 BEGIN WALL 1 RW-STA. OO,OO END WALL 1 RW-STA.65.17 0 0 8/6/23 191 ffi ÉoBsrcNsg.ÉB Sheet No: 23SS1014 No: RW-3.0 SEGMENTAL RETAINING WALL PLANS Dato: 06 AUG 2023 S€ls: 1" =20' SUNLIGHT MOUNTAIN SKI AREA - SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO 951..10.ì.41(Xl \\'\\'\\'.(ì l:()\\'Âl. l-l)l:S lGN S.( ON1 "BUILT FROM TI.IE CROUND UP'' [1¡i: 15.18 ( l-ll'l ROAI) [. l]URNSVII-LL. l\1h 5Jll? ( 0: I lì50 \\'OOl)N'lOOlì l)l{l \/ll SUI ll: 20 I. l\4ON tJ['l I]l\'¡ . ( 0 fif) I :Ì2 Drawn Design Check Signaturo Stono Salos; 211 30th Sl., Gmley, CO 80631 Seth Clarfi (970) 351.0270 (970) 539-2201 w.signaturestonê.com sclark@signalur€stone.com lt/"'n(; No.Date Rev¡sion THIS DRAWNG IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY. ANY PARTY ACCEPTING THIS DOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSED TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS @ 2023 Geowall Designs, LLC. 7 WALL LOCATION PLAN VIEW Title: 6 I 4 2 1 CF CF BD006 AUG 2023 RELEASED FOR CONSTRUCTION NOTE: 1, SITE PLAN IS FOR ILLUSTRATIVE PURPOSES ONLY AND IS TAKEN FROM THE CONTRACT PLANS PREPARED BY IRON MOUTAIN ENGINEERING, INC. LAST DATED 06/14/2023. 2. NORTH ARROW DIRECTION IS APPROXIMATE, REFER TO CONTRACT PLANS FOR ACTUAL HEADING. 3, REFER TO CONTRACT PLANS FOR ALL HORIZONTAL ALIGNMENT AND ACTUAL SITE GEOMETRY. \ 9¿90.LEGEND: - TOPOFWALLffiAPPROXIMATE GEOGRID COVERAGE SCALE UNIT 9?9 20 10 0 20 40 iW:9301 Oil E_:9297 4g- 00 EL 9298 Eaæ of€\,n i9 00 9305 00 Know what's BELOW. CALL before you dig. 3f c ð END WALL 3 RW-STA.8O.5O BEGIN WALL 3 RW-STA. OO.OO 0 0 N 8/6/23 191 Sheêt No: 23SS1014 RW-3,1 No: SEGMENTAL RETAINING WALL PLANS 95:..ì0i.1 I 90 \\'\\ \\' (ì liO\\':\l. l.l)l:Sl(iN S.COi\'l "ttUILT I"'ROlt4 TLIE GROUND UP" Datel 06 AUG 2023 Søl€: 1" =20' SUNLIGHT MOUNTAIN SKI AREA - SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO l\lN: l5.llt ( t.ll'l ROAf) L, lìURNS\rlLt.l:. N'lN 55ll? ((): lll50\\'OOl)l\'l(X)lì l)RlVt,StrlTli20l. l\lONtJNll:N].(()x0ll2 ÉrBslcNSF Design Check Signaluro gtono 21 I 30lh St., Greel€y, CO 80631 (970) 351-0270 w.signatureslone.com Sålos: S€th Clark (970) 539-2201 sclark@signaluresiono.com ','rili l:-/ DrawnNo.Date Revlsion THIS DRAWING IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY. ANY PARTY ACCEPTING THIS DOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSED TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS @ 2023 Geowall Designs, LLC. 7 WALL 1 ELEVATION Titlâ: 6 4 2 2 I CF CF BD0ô AUG 2023 RELEASED FOR CONSTRUCTION0 GENERAL NOTES:1. ALL ELEVATIONS AND DISTANCES ARE SHOWN IN FEET ALONG FACE OF WALL. LEGEND: TOp OF WALL ELEVATTON (TOP OF BLOCK) BOTTOM OF WALL ELEVATION (BOTTOM OF BLOCK) TW EL= XX.XX BW EL= XX.XX2. MINIMUM REINFORCEMENT LENGTH (RLMN) lS LISTED ALONG WALL FRONT FACE PROFILE. MINIMUM LENGTH IS MEASURED FROM FRONT FACE OF BLOCK TO TAIL OF GEOGRID, FINISHED GRADE LINE SFSO.PC GEOGRID3. THE WALLS SHALL BE CONSTRUCTED USING REDI'ROCK: 28" AND 41" UNITS AND SFSO-PC GEOGRID SOIL REINFORCEMENT. SEE SHEET RW.2.O FOR MATERIAL SPECIFICATIONS.-(SFB0-PC)--<- 4, SEE MANUFACTURER'S INFORMATION FOR ADDITIONAL DETAILS ON THE BLOCK SYSTEM SHOWN. oqo F U) =É. JU) Éãz.d6z Hg d¡ t\ oi Fa É É. U) U>ffıı É.tozñs dì oq (o rÜ FØI3 É. U)fo ú.ozul F- d(o t- U) =É. JJ =oz t¡J TW EL=8129.00 TW EL=8129.00 f- Lrlt¡lg zotr uJJt¡l 8130.00 8128.00 8126.00 8124.00 8122.00 8120.00 BW EL=8123.00 8130.00 8128.00 8126.00 8124.00 8122.00 8120.00 t- UJ UJ L.l- zo F utJ LIJ BW EL=8124,50 BW EL=8.124.50 BW EL=8121.50 F/G AT BOTTOM OF WALL MAX. APPLIED BEARING = 1,500 PSF 17 0 10 20 30 40 50 60 WALL 1 ELEVATION DISTANCE SHOWN IN FEET ALONG FRONT FACE A.A 28T , 28-t 28T . 28T ,, GC _28ï 28T 281 , 28r ,GC 281 ' 28T 281 281 -Pc 28¡¡-pc 28M-PC 28M-PC 28MÐe18N.PC 28M-PC 28M-PC 28M-PC 28M.tsï¡:ffi rC- 28M-PC 28M-PC:28M-PC 28[ tsM-pc 2sM-pC 28¡/tP4,28li[-Pc 288-Pc28M-PC 28M-PC 28¡-PC 2¡M-PC 28B.PC 288-PC28B-PC 288-PC 28B-PC RL y¡¡ = 13.0 (WALL FACING: REDI-ROCK 5.2") 8t6/23 191 1" = 10'06 AUG 2023 Scele:Dale: SEGMENTAL RETAINING WALL PLANS 95t tì0:Ì .1t90 \\'\\' \\'.(ìll)\\'^ LLDt:Sl(;NS.( Ol\'l ,BUII,T FROM TIIE GROUND UP' Shæt Nol RW4.O Projecl Nol 23SS1014 SUNLIGHT MOUNTAIN SKI AREA - SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO N1N: I 51li ( t |fl: ROA I) l:. IIUIìNSVII-t-!. ì\4N 55-ll7 c():Iris()\\jt)Ol)VlOa)lìl)llIVl,StÌl.ll:l(il.l\1O¡itjl\tl,N1.(0l{0l-12 ÉnssrcNs= Drawn Design Check Signaturo Stons Sales: 211 30th St., Græl€y, CO 80631 Ssth Clark (970) 351.0270 (970) 539-2201 M.slgnâtuÞstong,com sclark@signalursstone,com No.Date Revis¡on THIS DRAWING IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY, ANY PARTY ACCEPTING THIS DOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSED TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS @ 2023 Geowall Designs, LLC. 7 WALL 2 ELEVATION Titlê: 6 4 2 CF CF BD006 AUG 2023 RELEASED FOR CONSTRUCTION GENERAL NOTES:LEGEND ALL ELEVATIONS AND DISTANCES ARE SHOWN IN FEET ALONG FACE OF WALL.TOP OF WALL ELEVATION (TOP OF BLOCK) BOTTOM OF WALL ELEVATION (BOTTOM OF BLOCK) TW EL= XX.XX BW EL= )ü.XX2. THE WALLS SHALL BE CONSTRUCTED USING REDI-ROCK: 28'AND 41" UNITS. SEE SHEET RW.2.O FOR MATERIAL SPECIFICATIONS.FINISHED GRADE LINE 3. SEE MANUFACTURER'S INFORMATION FOR ADDITIONAL DETAILS ON THE BLOCK SYSTEM SHOWN. oqo <t-(h =É JcD J-sã zú6z HS cfì øc c{ <l- U) 3 É. (n =ô É.oz. Lrl ro\ ro <t-aII É. U)fo ú.z(, tll co oq¡-lo Fv)I =É. (t) fo É.ôz. uJ oc c{o) t-- U)I =t att (Ð -@eEÉ.<zt-oquJ>rr¡ è U)f,ô ú.oz UJ (f)cìt-o t- U) =t U)f,o É.z(, UJ co oq rl) <F U) Ét- Øfo É.oz u.l ro\oN <t- U) 3É. JJ =ozul TW EL=81 52.50 TW EL=8151.00 TW EL=8151.00 TW EL=8145.00 8154.00 8152.00 8'150,00 8148,00 8146.00 8144.00 8142.00 8140.00 8154.00 8152.00 8150.00 8148.00 8146.00 8144.00 8142.00 8140.00 TW EL=8149.50 TW EL=8149.50 TW EL=8146.50 TW EL=8'148.00 t- uJ UJ LL zo F t"llJul t- UJluIL z.o F- uJJ Lll BW EL=8146.50 BW EL=8145.00 F/G AT BOTTOM OF WALL BW EL=8143.50 BW EL=8142.00 MAX. APPLIED BEARING = 2,000 PSF 120.75 10 20 30 40 50 60 70 80 90 100 110 120 0 WALL 2 ELEVATION DISTANCE SHOWN IN FEET ALONG FRONT FACE B.B 287 28M --418 M 41M 41M 4 cc 281 28r 28f 287 28M 28M 28M 28M 28M 41M 4'1M 4rM 11\4 4 1M 41M 41M 4',lM 41M 281 281 281 zls--4418 418B 418 418 418 GC GC 28T 287 281 281 28M 28M -ZBB---,flM--llM- 418 418 4 B GC 28T 28Í 28M 28M41M - 4tÈ - -4+tvt - -41'fvl- 41M 41M 41 418 4'l 28128T 281 28T 287 M 28M 28M 41M :. 41 M41MM4M 4 MM-41 ¡/L _47 M- 44BB4B4B4B 28T GC 28M 28I TIB--"1M-- 418 4rM 41M 28M --28M-- 28T GC 418 418 -GC 288 28H RLur¡t = N/A (GRAVITY) (WALL FACING: REDI-ROCK 5.2") N 816123 191 €nssrcNsF\Ê= Shæt No: 1" = 10'RW4.106 AUG 2023 Datel Scalgl SEGMENTAL RETAINING WALL PLANS Project Nol 23SS1014 SUNLIGHT MOUNTAIN SKI AREA - SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO,BUILT þI<OM TI.IE CROUND UP" N1N: IJlli ( t.llrl'lì0Àl) l:. lll.rlì!'(SVlt.l-l:. l\{N 55-ì.ì7 ( O: Is50 \\'OOI)il4OOll Dl{IVl: StlIll: l0l. l\lONtil\llll\T. t() l{0I12 951.301.-l I e0 \\'\\'\\.(ìl:O\\ ^l.l,l)l:S'GNS.('Ol\'lDrawnDesignCheck S¡gnatur€ Stons 21 1 30th St., Greol6y, CO 80631 (970) 351-0270 M.signatur6Êton6.com SâlgB: Ssth Clark (970) 539-2201 sc!ark@signaturesto¡e.com ',,Wt-/ No.Date Revision THIS DRAWING IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY. ANY PARTY ACCEPTING THIS DOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSED TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS @ 2023 Geowall Designs, LLC. 7 WALL 3 ELEVATION Title: 6 5 4 3 2 1 CF BDCF06 AUG 2023 RELEASED FOR CONSTRUCTION0 GENERAL NOTES:LEGEND: ALL ELEVATIONS AND DISTANCES ARE SHOWN IN FEET ALONG FACE OF WALL.TOP OF WALL ELEVATION (TOP OF BLOCK) BOTTOM OF WALL ELEVATION (BOTTOM OF BLOCK) TW EL= XX.)C( BW EL= XX.XX2. THE WALLS SHALL BE CONSTRUCTED USING REDI-ROCK: 28" AND 41' UNITS. SEE SHEET RW.2.O FOR MATERIAL SPECIFICATIONS. FINISHED GRADE LINE 3. SEE MANUFACTURER'S INFORMATION FOR ADDITIONAL DETAILS ON THE BLOCK SYSTEM SHOWN. oqo F- U)*É. JJ =zou¡ co F-q Ir l- ..t) E É. at)fı É.zo uJo ¡r oi l--Ø ú U)Þô É.oz. t.ll @rO c.¡(o t--Ø =t ØNfa QEÉ.<zt-oqHã U)f (f É.oz. uJ @ u? 1¡l rO t- U) ts É. (,ôlrAeEÉ.<ZFıqlu>mã U)fı É.oz UJ or¡?o@ FØ =É. JJ =oz l..ll TW EL=8301.00 TW EL=8307.00 TW EL-8302.50 TW EL=8304.00 TW EL=8304.00 TW EL=8305.50 TW EL=8305.50 8308.00 8306.00 8304.00 8302.00 8300.00 8298.00 Fulul L¡- zot- I.JJJ l'r¡ 8308.00 8306.00 8304.00 8302.00 8300.00 8298.00 l-l¡llu1r z.ot- I.JJJut BW EL=8299.50 F/G AT BOTTOM OF WALL BW EL=8298.00 MAX. APPLIED BEARING = 2,000 PSF 80.50 0 10 20 30 40 50 60 70 80 WALL 3 ELEVATION DISTANCE SHOWN IN FEET ALONG FRONT FACE GC 287 4lM 28M 't 2t M4 41M 41M 28T 28T 287 28M 28M 41M 41M M 4,IM M28 41M 4 4 28f M 4'tM Fr-4 28f 28'l 28M 28M28M 28M 28M M 41M 41M 41M 41M 4 41M 41 M 41M 41M 41M -418--?lB--,fiB---418- 287 287 , 11\428M 4 41M 41M 281 28M 41M 4 418 418 GC 287 28H 28M 4 418 418 GC - - 4tM --.+1M - -28ÀA- -28tut -GC* 28T GC 418 418 418 418 288 28H 4'tM 28M 28I GC RL ¡¡r¡r = N/A (GRAVITY) (WALL FACING: REDI-ROCK 5.2") N 8t6t23 191 ffi ÉopsrcNsF\== Shæt No: RW-4.2 SEGMENTAL RETAINING WALL PLANS Datel 06 AUG 2023 Scâl€l 1" = 10' Project Noi 23SS10 14 SUNLIGHT MOUNTAIN SKI AREA SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO"BUILT FROM TIIE CROUND I]P" NIN: I 51tl ( l-llìl'R0Âl) L. llUllNSVll.l-l:. tt4li 5i-ì.ì7 CO; ì lì50 \\'OOI)l\lOOlì l)lìl V L SLi l'l L l0l. ñl0Nli l\1 I:NT ( () ltO I l: q5t.301.,¡¡ q0 \\,\\'\\' (ì Iio\ç^ l. l.l)ljsl(;NS.col\1 0râwn Design Check Slgnatum Stone 211 30th St., Græley, CO 80631 (970) 351.0270 w.signetuGslone,com ';n(; l:-/ (970) 539-2201 sclark@signaturestone,com Salos: Seth Clerk No.Date Revision lHIS DRAWING IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY. ANY PARTY ACCEPTING THIS DOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSED TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS @ 2023 Geowall Designs, LLC. 7 o 4 2 1 UT CF BD06 AUG 2023 RELEASED FOR CONSTRUCTION0 GENERAL NOTES:5. 4" CORRUGATED PERFORATED DRAINPIPE INSTALLED AS LOW AS POSSIBLE WITH POSITIVE DRAINAGE. OUTLET INTO ONSITE DRAINAGE OR THROUGH WALL FACE AT 5O.O' O.C. AND LOW ENDS OF WALL. SEE DETAIL 2/RW.6.0, 1. THE SECTION SHOWN IS A REPRESENTATIVE WALL SECTION. THE WALL HEIGHTS, ELEVATIONS, TOE SLOPES, AND BACK SLOPES VARY ACCORDING TO THE ELEVATION PLAN AND SITE PLAN RESPECTIVELY. 2. UPON EXCAVATION, WHERE UNSUITABLE SOILS ARE FOUND, SUBCUT AS REOUIRED BY THE ONSITE GEOTECHNICAL ENGINEER AND REPLACE WITH SUITABLE COMPACTED STRUCTURAL FILL TO ACHIEVE THE REQUIRED BEARING CAPACITY. THE STRUCTURAL FILL SHALL BE COMPACTED TO A MINIMUM 95% STANDARD PROCTOR DENSITY. 6. INSPECT EXCAVATION SLOPES FOR ACTIVE SEEPAGE AND PLACE ADDITIONAL DRAINS WHERE SEEPAGE OCCURS. 7 DO NOT BRING HEAVY COMPACTION OR PAVING EQUIPMENT WITHIN 3'OF THE BACK OF THE REDI-ROCK RETAINING WALL. 3. APPROXIMATE LIMITS OF EXCAVATION VARIES WHERE SUBCUT IS REQUIRED. ACTUAL LIMITS AND SIDE SLOPES SHALL BE DETERMINED BY OSHA REGULATIONS AND MATCH FIELD CONDITIONS AS DETERMINED BY THE CONTRACTOR. 8. SEE MANUFACTURER'S INFORMATION FOR ADDITIONAL DETAILS ON THE REDI-ROCK RETAINING WALL SYSTEM. 4. THE WALL IS DESIGNED AS A REINFORCED WALL REQUIRING SFSO.PC REINFORCEMENT AT THE ELEVATIONS SHOWN AND SHALL BE CONSTRUCTED WITH REDI'ROCK: 28" AND 41" UNITS USING THE 5.2" BATTER. CoNTROLLED F|LL (SANDY LEAN CLAY - RETNFORCED SO|L 1 (CLAYEY GRAVEL - 8" LOW PERMEABLE SOIL (2H:1V SLOPE MAX) 4oz NON-WOVEN FILTER FABRIC TW EL = 8129.00 7 RETAINED SOIL 1 (SANDY LEAN CLAY - CL) BW EL = 8121 .50 APPROXIMATE LIMITS OF EXCAVATION (1H:1V) PREPARED PER GEOTECHNICAL ENGINEERS RECOMMENDATIONS 6- X 40" UNREINFORCED CONCRETE OR CRUSHED STONE LEVELING PAD 4" DRAIN PIPE (SEE NOTE 5) WALLSECTIONA-A (SECTION CUT:WALL 1 AT RW-ST4.35.00) !q v{ )^ F/G BOTTOM OF WALL REDI-ROCK UNIT (5.2" BATTER) 24" MIN WALL ROCK (GRAVEL - GP) (2H:1V SLOPE MAX) LEGENDm ETA la 1. 'i,l LOW PERMEABLE SOIL WALL ROCK (GRAVEL - GP) RETNFORCED SOIL 1 (CLAYEY GRAVEL - GC) RETATNED SO|L I (SANDY LEAN CLAY - CL) LEVELING PAD (GRAVEL - GW) IN-SITU/STRUCTURAL FILL ffi a;77,Z l.'.\.. r I + SF80-PC GEOGRTD 4 oz NON-WOVEN FILTER FABRIC 3 191 816/2 Check SlgnatuÞ Stono Sales: 21 1 30th St., Grsolsy, CO 80631 Ssth ClËrk (970) 351-0270 (970) 539-2201 M.signâtureslone,com sclark@s¡gmlurestone.com ;nil:-/ WALL SECTION A.A Titl€l SEGMENTAL RETA¡NING WALL PLANS 23SS1014 Nol Date: 06 AUG 2023 Scale: 1"=5' Shæt No RW-5.0 SUNLIGHT MOUNTAIN SKI AREA - SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO 9_5:.t0-1.1t90 \\ \\'\\'.(ì l,O\\'A l- l-Dl:SltiNS.COl\'l ,BUILT FROA4 TI.IE GROUND UP' I{N: l5lti( l.llrl' ROÂl) l:. lJURNSVll.l.l:. À4N i5.ìi7 ( O: I 850 \\'OOI)\4O()ll ì)RI\rl, StII IL l{)l. l\loNlI NlI:N I. CO l{0l.ì2 ëoesrcNsF*=lE Drâwn DesignNo,Date Rev¡sion THIS DRAWING IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY, ANY PARTY ACCEPTING THIS DOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSED TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS @ 2023 Geowall Designs, LLC. 7 6 WALL SECTION B.B Titl€: 4 â SUNLIGHT MOUNTAIN SKI AREA - SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO SEGMENTAL RETAINING WALL PLANS 1 CF CF BD06 AUG 2023 RELEASED FOR CONSTRUCTION0 Scalsi 1"=5' Shæt No: RW-5.1 GENERAL NOTES THE SECTION SHOWN IS A REPRESENTATIVE WALL SECTION. THE WALL HEIGHTS, ELEVATIONS, TOE SLOPES, AND BACK SLOPES VARY ACCORDING TO THE ELEVATION PLAN AND SITE PLAN RESPECTIVELY. 2. UPON EXCAVATION, WHERE UNSUITABLE SOILS ARE FOUND, SUBCUT AS REOUIRED BY THE ONSITE GEOTECHNICAL ENGINEER AND REPLACE WTH SUITABLE COMPACTED STRUCTURAL FILL TO ACHIEVE THE REQUIRED BEARING CAPACITY, THE STRUCTURAL FILL SHALL BE COMPACTED TO A MINIMUM 95% STANDARD PROCTOR DENSITY. 3. APPROXIMATE LIMITS OF EXCAVATION VARIES WHERE SUBCUT IS REQUIRED. ACTUAL LIMITS AND SIDE SLOPES SHALL BE DETERMINED BY OSHA REGULATIONS AND MATCH FIELD CONDITIONS AS DETERMINED BY THE CONTRACTOR. 4. THE WALL IS DESIGNED AS A REINFORCED WALL REQUIRING SFSO-PC REINFORCEMENT AT THE ELEVATIONS SHOWN AND SHALL BE CONSTRUCTED WITH REDI.ROCK: 28'AND 4,I" UNITS USING THE 5.2" BATTER. 8'LOW PERMEABLE SOIL5. 4'CORRUGATED PERFORATED DRAINPIPE INSTALLED AS LOW AS POSSIBLE WITH POSITIVE DRAINAGE. OUTLET INTO ONSITE DRAINAGE OR THROUGH WALL FACE AT 5O.O' O.C. AND LOW ENDS OF WALL. SEE DETAIL 2/RW-6.0. (2H:1V SLOPE MAX) 4oz NON-WOVEN FILTER FABRIC 6. INSPECT EXCAVATION SLOPES FOR ACTIVE SEEPAGE AND PLACE ADDITIONAL DRAINS WHERE SEEPAGE OCCURS.TW EL = 8151.00 7 DO NOT BRING HEAVY COMPACTION OR PAVING EQUIPMENT WITHIN 3'OF THE BACK OF THE REDI-ROCK RETAINING WALL, AINED SOIL 2 I SEE MANUFACTURER'S INFORMATION FOR ADDITIONAL DETAILS ON THE REDI-ROCK REÏAINING WALL SYSTEM. (GRAVEL - GP) 7 APPROXIMATE LIMITS OF EXCAVATION (1H:2V) BW EL = 8143.50 4" DRA|N P|PE (SEE NOTE 5) 6" X 53" UNREINFORCED CONCRETE SUB-GRADE PREPARED PER GEOTECHNICAL ENGINEERS RECOMMENDATIONSOR CRUSHED STONE LEVELING WALLSECTIONB.B (SECTION CUT:WALL 2 AT RW-STA. 70.00) ìÉ F/G BOTTOM OF WALL REDI-ROCK UNIT (5.2" BA (FLAT SLOPE TYP LEGEND mLow PERMEABLE sorL ffi RETATNED sorL2 (GRAVEL-GP) ffi LEVELTNG PAD (GRAVEL - cw) K rN-srru/srRucruRAL FILL 4 oz NON-WOVEN FILTER FABRIC 8/6/23 191 ffi €opsrcNsF.É= "BL]ILT FROM THE CROUND UP' lvlN: '¡4E ( l-ll:l;ROAD l;. IIURNS\/lt.Lt:. À4N 55117 CO: lli50 \\'OOl)N{OL)lì l)l{ì\rl: Stll'l }: ?01. li4ONliÀ'll:NT. C() ¡{0132 952.10.1.4190 \\'\\'$'.(ìl:0\ Àl-l,Df:SICNS.C(lM Projecl Noi 23SS1014\ Dat9: 06 AUG 2023 Drawn Design Check Signãturs Stone 211 30lh St., Græley, CO 80631 (970) 3s1-0270 $/w.signatußston6,com $elss: Ssth Clerk (970) 539-2201 sclark@s¡gnaturestone.æm THIS DRAWING IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY. ANY PARTY ACCEPTING THIS DOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSEO TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS @ 2023 Geowall Designs, LLC.No.Date Revision NOTES: 1. FOUNDATION SOILS SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO PLACEMENT OF THE LEVELING PAD.2. LEVELING PAD SHALL BE CONSTRUCTED TO THE DIMENSIONS SHOWN USING CRUSHED STONE OR 2,OOO PSI UNREINFORCED CONCRETE. 60" 41'* 28' 6'MIN BLOCK DEPTH + 12.. SECTION D - D D ',l8'MtN 6"-l F D PROFILE VIEW N9]ES:.1. THE DRAINAGE SYSTEM SHALL CONSIST OF A 4" MINIMUM DIAMETER CORRUGATED PERFORATED PLASTIC DRAINPIPE. 4'DIA PERFORATED DRAINPIPE CUT BLOCK TO OUTLET DRAINPIPE AND GROUT IN PLACE 4" DIA SOLID DRAINPIPE 4'DIA PERFORATED DRAIN PIPE 4" DIA TEE FITTING I n DrREINFORCEMENT LENGTH (Rl_iflN) I l ,2// )//// u,,3'MIN SOIL BETWEEN OVERLAPPING GRID LAYERS u.,) -) l Il!REINFORCEMENT LENGTH (Rt_MrN) U o_ 1 LEVELING PAD DETAIL - N.T.S 2 DRAIN PIPE OUTLET DETAIL - N,T.S 3 GRID INSTALLATION ON CURVES DETAIL - N,T.S FIIL BLOCK VOIDS WTH DRAINAGE AGGREGATE 12'DRAINAGE ZONE NOTES: 1) 28" pC BLOCKS MAy BE USED tN LtE OF 28'STANDARD BLOCKS AS NEEDED BY THE BLOCK MANUFACTURER.2J 41" HOLLOW CORE BLOCKS SHALL NOT BE USED tN L|EU OF 41- STANDARD BLOCKS USED IN THIS DESIGN. 12'WIDE GEOGRID WRAP UPP BLOCK ll ll CG. GARDEN CORNER 28T - 28" TOP HEIGHT = 18" WIDTH=46å" DEPTH = 28" WEIGHT = 1,230 LBS 28M.28" MIDDLE 288 .28' BOTTOM .LOWER BLOCK HEIGHT - 18" WDTH = 46á" DEPTH = 24" WEIGHT = 1,070 LBS HEIGHT = 18" WIDTH=46å" DEPTH = 28" WEIGHT = 1,520 LBS HEIGHT = 18" WIDTH = 46 sl " DEPïH = 28" WEIGHT = 1,620 LBSSECTION VIEW 12" WIDE GEOGRID STRIP WRAPS THROUGH BLOCK EXTENDING INTO REINFORCED BACKFILL 41M - 41'MIDDLE 418 -41. BOTTOM 28M-PC.28- MIDDLE POSITIVE CONNECTION HEIGHT = 18" WTDTH=46å" DEPTH = 28" WEIGHT = 1,520 LBS 288-PC - 28" BOTTOM POSITIVE CONNECTION HEIGHT = 18" WTDTH=46å" DEPTH = 28" WEIGHT = 1,620 LBS HEIGHT = 18" WIDTH =46å" DEPTH = 41 " WEIGHT = 2,180 LBS HEIGHï = '18" WIDTH = 46 DEPTH = 41 1I ISOMETRIC VIEW AT BACK OF WALL WEIGHT = 2,280 LBS 4 POSITIVE CONNECTION DETAIL - N.T.S REDI-ROCK UNIT DETAIL - N.T.S THIS DRAWING IS BEING FURNISHED FOR THIS SPECIFIC PROJECT ONLY. ANY PARTY ACCEPTING THIS DOCUMENT DOES SO IN CONFIDENCE AND AGREES THAT IT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART, NOR DISCLOSED TO OTHERS WITHOUT THE CONSENT OF GEOWALL DESIGNS 7 ffi ËnpsrcNsFEg Tltlo: 6 CONSTRUCTION DETAILS 4 SUNLIGHT MOUNTAIN SKI AREA - SEGUNDO LIFT TERMINAL GLENWOOD SPRINGS, CO,,BUILT FROA4 TI'IE GROUND I]P' l\lN: I 511ì ( l- lffj RO,^ l) I:. llUIlNS\¡l I LI:. l\.1 N 55ll 7 CO: I 850 \\r()OI)I'lOOll l)R I \rl: StJ ffl ?{Jl. l\4ONtJl\l trNl . ('O ¡i0 l:12 2 Signaturu Stono Sales: 211 30lh Sl., Græley, CO 80631 Selh Clark (970) 351.0270 (970) 539-2201 w.signeturôslons,com sclâtk@sìgnaluæstone.com I SEGMENTAL RETAINING WALL PLANS 0 06 AUG 2023 RELEASED FOR CONSTRUCTION CF BD No:Date: 06 AUG 2023 Scal€: AS NOTED Shæt No: 8/6/23 191 @ 2023 Geowall Des¡gns, LLC.No.Date Revision 5 Drawn CF Check e5:.10-r.4t90 \\r\\r \\'.(ì l:O\\ ^ LLDhS l(;NS.(\)l\4 23SS1014 RW-ô.0 !o!,a¡ofL E ff i Url I (t )oz(t )W il # Le n g t h oc k Ar e a Fe e t ) -P C RL So i l 1 Gr a v e l - GG ub i c Ya r d s ) in e d So i l 1 dy Le a n Cl a y - CL ub i c Ya r d s ) So i l 2 -G P bi c Ya r d s ) Pa d .G W bi c Ya r d s ) I Ro c k -G P Ya r d s ) Fa b r i c ar e Ya r d s ) Dr a i n Pi p e " Ou t l e t s Ty p e Fe e t ) Fe e t ) 3I ô¡ ¿ n o =c ù ä- + €= å ã = 3 J? # - 8 Bä ã 8# É h) gF f i oo cL :, 1t ı CL trcl .B Ê ä Nã A xÀ tlo O) N J o *l\ )O) o)5l\ ) \l N) 9t too ËÉ s 8d - - (¡ \ ¡ À N( ¡ s (, ( o N i$ b \ (J t o ( ¡ N zz R >> Ë o zz ò >> 8 << d >> i ¡ 1\ ) zz 8 ÈÈ ; s( ¡ _ r< o z , sb > 9S o È (J | æ o @o l \ ) (^ ) .s l\ ) N) { S b' , ¿ù b¡ NN ( ¡ or @ N ) j9 0 N o( ¡ @ (t r (¡ r FÉ E gd ì NS ^ ) N oo o oo o (' l 90(¡N (¡s¡\o Jo J ¿^ ) (o No J\¡N)s N) o) Is N) :oo (p ı-c)tr üc f >= -o ß)c5 U' N (, o 0)-o 0)cJ (t ,o!)c5 Ø o 0)-o 0)C l.a t .ëoo Io o- o o) ı 0) N) N oP s s N N N ) N : n #Ë Ë ¿ i Ë Ë E x s¡ f¡ f¡ sr N s¡ f- n s¡ sr \\ ¡ \ \ @ \ \ \ ¡ \ (¡ ( J | ( ¡ ( ' t æ ( J t ( J t ( J t ( ¡ .- È 9 P N 9 P d N 88 8 8 8 8 8 8 8 Rü o o < ¡ o o P - üË 8 B d ã ã i l Ë e9 B à r r s " N B s " 88 S 8 8 8 8 8 8 rN ) . r r oo À S < ¡ ì < ¡ s o ì == ( b \ a ; ]{ ð ó ı : ' ıı g E . ì u g g d ee ô 8 p - ì d e " 88 B B 8 8 B B 8 9e Ê S s " s ' S E à 88 ñ È d d d E 8 dÈ à ð p ' ¡ l S ô bb ô b R P b b b oo a o v v o o o ËH U ã i u H $ Ë Es ; ; u B d B ü -{o o_ ı 0)5ÀN \l(¡IOo (J t N) f,N) (¡ rr r t t t 2 !Ð Ð Ð 5 = o E- & & 9 È È ã r ã ã 9 4€ " qo o S é E ı' Ø Ø o^ É. -. O O ¿^ i ' : = . f :: Y / ã (D O N -: ¿ . - (/ , F =' = - - ı - o ¡ ¿¿ J (D C) O =' ) X O i ãF É c n i, , öo - î J. ll a ñ - v E rr ; d = i 3 3 ä, ã q SE E is É x( o ( o o F- ' ¡ã o o l = ı =o o df h c8 8 8 e ö <d ı ' - á o ) Ð= 3 e ' : € ø ı ı +ã P o =' = o i ø, )f E ãã ¡ s. ä + ã ãi ã a (O -. - iì (D t *l r l Q . 5 r ä q4 ð å ı e € g I6 e 5 qË ü 5 ó = ã' q d â B J==i ı 8 o; . =' = *ñ q E ^r : (, ll rô E* d -f (. o v -* E ıÉ gr (o f o åH fl <o - o - +E B. -- <sı o Po - a *< o -- *a J :0 ) o xã ? g: r = oo u, f¡ );g oc 3oI :fo(o E o ct 0)c)x U)ırooI o c) ts 0 0 0 E E E s 6 E z # rE d Sf f l Zl l üJ l[ E g l E ll e f r t Eu r u ¡ e ¡ a ¡ 3u l 'l q E l F n s !$ g5 z 8 - E Z - 8 0 { 3 t E