COLORADO STATE ELECTRICAL BOARD
,1560 Broadway, Suite 1350
Denver, Golorado 80202
Automatic email - Do not reply to this email.
982512
Site:
Ownen
Zakary White
53 Pine St Carbondale 81623
Phone: (970)274-9049 Fax:
Email; whiteelectricincorporation@gmail.com
1244 CR 106 Carbondale County: Ga¡field
andrew braudis
braudis
ACCEPTED
lnspection Type: Rough ln
Con¡tuction Type: NEW
lnspection Report
Permit #:
Permit
Holder:
Date I nspecte d: 22- AU G-23
Phone: (970\274-9049
Status:
Trim Permit: N
Building Type: OTHER
lnspector: David Sutton 303-869-3458
Corrections: 1 ) 110.26 Spaces About Electrical Equipment. Depth of Working Space. Table 110.26(AX1 ) Load center requires 3 ft clear distance
from the energized parts. Though this may have been approved before I'm unable to see any notes from previous inspector with
location being approved. The code requirement was in place at time of last inspection. This load center needs to be relocated to an
area that provides the minimum clearances 2) 210.8 Ground-Fault Circuit-lnterrupter Protection for Personnel. The GFCI shall be
installed in a readily accessible location. A height of no more than 6 ft 6 in
Comments: Walls and ceiling OK to cover