Loading...
HomeMy WebLinkAboutConditions of PermitCONDITIONS OF PERMIT BLCO -08-23-824s Vasser-Heath Compressor Station Replace Existing Housing of Air Compressor and Air Drying Packages Towns h i p : ó Ra n g e:9 4 Sectio n :28 - Lat/Lo n g : 39 .497 63 9 N/- 1 07 .8847 43W Parcel : 217528100024 i ) ALL WORK SHALL COMPLY WITH THE 20'I5 INTERNATIONAL BUILDING CODE (I.B.C.)AND MANUFACTU RER'S I NSTALLATION I NSTRUCTIONS. 2) ALL WORK MUST COMply W|TH CONDITTONS OF THE CURRENT LAND USE PERMIT. 3) ALL WORK MUST COMPLY WITH STATE AND FEDERAL REGULATIONS. 4) LOCKS, LATCHES AND LANDTNGS SHALL COMPLY WlrH 2015 lBC, SECTION 1010.1.9 - DOOR LATCH TO BE OPERABLE FROM INSIDE WITHOUT A KEY OR SPECIAL KNOWLEDGE. s) pRovtDE A LANDTNG OUTSTDE THE EXTERTOR DOOR. CAN BE 7" BELOW THE INTERIOR 6) CONTRACTOR TO VERTFy CDOH CERTTFTCATION PR|OR TO SCHEDULTNG BUTLDING FINAL INSPECTION 7) ELECTRTCAL PERMtTTtNG AND TNSpECTTONS BY COLORADO STATE ELECTRTC BOARD. ELECTRICAL ROUGH-IN APPROVAL IS REOUIRED AT FRAME INSPECTION. ELECTRICAL FINAL APPROVAL IS REOUIRED FOR FINAL INSPECTION & CERTIFICATE OF OCCUPANCY. B) LTGHT AND VENTTLATTON PER 2015 lBC, CHAPTER 12 AND 2015 IMC CHAPTER 3-4 9) HIGH STRENGTH BOLTING / FIELD WELDING (IF ANY PERTAINS), SHALL BE REOUIRED BY SPECIAL INSPECTOR. COPY OF SPECIAL INSPECTOR REPORT TO BE AVAILABLE FOR BUILDING FINAL. ,IO) GARFIELD COUNTY FINAL / COMPLETION INSPECTION IS REOUIRED. 11) PROVIDE AN EXCAVATTON OBESERVATTON REPORT FROM A GEOTECH ENGTNEER AT THE FOOTING INSPECTION, 2OOO PSF TO BE VERIFIED.