HomeMy WebLinkAboutConditions of PermitCONDITIONS OF PERMIT
BLCO -08-23-824s
Vasser-Heath Compressor Station
Replace Existing Housing of Air Compressor and Air Drying Packages
Towns h i p : ó Ra n g e:9 4 Sectio n :28 - Lat/Lo n g : 39 .497 63 9 N/- 1 07 .8847 43W
Parcel : 217528100024
i ) ALL WORK SHALL COMPLY WITH THE 20'I5 INTERNATIONAL BUILDING CODE (I.B.C.)AND
MANUFACTU RER'S I NSTALLATION I NSTRUCTIONS.
2) ALL WORK MUST COMply W|TH CONDITTONS OF THE CURRENT LAND USE PERMIT.
3) ALL WORK MUST COMPLY WITH STATE AND FEDERAL REGULATIONS.
4) LOCKS, LATCHES AND LANDTNGS SHALL COMPLY WlrH 2015 lBC, SECTION 1010.1.9 -
DOOR LATCH TO BE OPERABLE FROM INSIDE WITHOUT A KEY OR SPECIAL KNOWLEDGE.
s) pRovtDE A LANDTNG OUTSTDE THE EXTERTOR DOOR. CAN BE 7" BELOW THE INTERIOR
6) CONTRACTOR TO VERTFy CDOH CERTTFTCATION PR|OR TO SCHEDULTNG BUTLDING FINAL
INSPECTION
7) ELECTRTCAL PERMtTTtNG AND TNSpECTTONS BY COLORADO STATE ELECTRTC BOARD.
ELECTRICAL ROUGH-IN APPROVAL IS REOUIRED AT FRAME INSPECTION. ELECTRICAL
FINAL APPROVAL IS REOUIRED FOR FINAL INSPECTION & CERTIFICATE OF OCCUPANCY.
B) LTGHT AND VENTTLATTON PER 2015 lBC, CHAPTER 12 AND 2015 IMC CHAPTER 3-4
9) HIGH STRENGTH BOLTING / FIELD WELDING (IF ANY PERTAINS), SHALL BE REOUIRED BY
SPECIAL INSPECTOR. COPY OF SPECIAL INSPECTOR REPORT TO BE AVAILABLE FOR
BUILDING FINAL.
,IO) GARFIELD COUNTY FINAL / COMPLETION INSPECTION IS REOUIRED.
11) PROVIDE AN EXCAVATTON OBESERVATTON REPORT FROM A GEOTECH ENGTNEER AT THE
FOOTING INSPECTION, 2OOO PSF TO BE VERIFIED.